Kohler Fault Codes

340 Kohler generator fault/alarm codes with symptom, cause and remedy — compiled from Kohler service and controller documentation.

Fault / alarm codes

340
CodeMeaning / symptomCauseRemedy Models affected
000The 'AUT' pictogram is flashing, and the generating set stops unexpectedly.Pressing the 'STOP' button will stop the generating set immediately in general fault mode. The general fault LED will light up flashing and the following message will appear: 000 010 represents a fault code. Refer to the list of fault codes in Section 4.4.Kohler DEC 1000
000The generating set stops immediately when pressing the 'STOP' button during an external command.Resolve the fault which has required the emergency stop button to be pressed, release the emergency stop button by turning it clockwise, and acknowledge (reset) the fault by moving the key switch to OFF, waiting for the 'ON' LED to go out completely and then moving the key switch to ON.Kohler DEC 1000
1PARADA DE EMERGENCIA*Kohler FR II
1Engine starts hard, or runs roughly or stalls at idle speed.Adjust the low idle speed screw, then adjust the low idle fuel needle.Kohler Command 11, Kohler Command 12.5, Kohler Command 14
1Black, sooty exhaust smoke, engine sluggish.Readjust main fuel screwKohler KT17, Kohler KT17 Series II, Kohler KT19, Kohler KT19 Series II, Kohler KT21
1--23Local display shows chgr1/2 val 1--23 error.Kohler TP-6200
2AUXILIAR*Kohler FR II
2Engine runs rich.Kohler Command 11, Kohler Command 12.5, Kohler Command 14
2Engine misses and backfires at high speed.Readjust main fuel screwKohler KT17, Kohler KT17 Series II, Kohler KT19, Kohler KT19 Series II, Kohler KT21
3SOBREARRANQUE*Kohler FR II
3Engine runs lean.Kohler Command 11, Kohler Command 12.5, Kohler Command 14
3Engine starts, sputters and dies under cold weather starting.Turn main fuel adjustment 1/4 turn counterclockwiseKohler KT17, Kohler KT17 Series II, Kohler KT19, Kohler KT19 Series II, Kohler KT21
4SOBREVELOCIDAD*Kohler FR II
4Fuel leaks from carburetor.Kohler Command 11, Kohler Command 12.5, Kohler Command 14
4Engine runs rough or stalls at idle speed.Readjust speed then idle fuel screw if neededKohler KT17, Kohler KT17 Series II, Kohler KT19, Kohler KT19 Series II, Kohler KT21
5BAJA PRES. ACEITE*Kohler FR II
6ALTA TEMP. MOTOR*Kohler FR II
7SISTEMA LISTO*Kohler FR II
9NO ESTA EN AUTOM.*Kohler FR II
010The generating set stops immediately when pressing the emergency stop button.Acknowledge (reset) the fault by moving the key switch to OFF, waiting for the 'ON' LED to go out completely and then moving the key switch to ON.Kohler DEC 1000
10PREAL., ALTA TEMP. MOTOR*Kohler FR II
11PREAL., BAJA PRES. ACEITE*Kohler FR II
12BAJA TEMP. AGUA*Kohler FR II
12OVERCRANK - O.C.Kohler G-292806
12VDC +12VDC +Kohler FR II, Kohler FR1, Kohler G-292806
13BAJO VOLTAJE BAT.*Kohler FR II
14FALLA CARG. BAT.*Kohler FR II
15COMBUST. BAJO*Kohler FR II
16FALLA COMUNKohler FR II
21Engine Speed Synchronization — Loss of synchronizationEngine speed sensor related: sensor connector or wiring; sensor loose or air gap incorrect; speed sensor wheel related: damaged teeth, gap section not registering; engine wiring harness related: pin circuit wiring or connectors (pins 3 and/or 21 for "35 Pin" MA 1.7 Metal-Cased ECU; pins 9 and/or 10 for "24 Pin" MSE 1.0 Plastic-Cased ECU; pins 9 and/or 10 for "32 Pin" MSE 1.1 Plastic-Cased ECU); ECU/harness related: ECU-to-harness connection problemKohler CH Series
22Throttle Position Sensor (TPS) — Unrecognizable signal is being sent from sensor (too high, too low, inconsistent). A "limp-home" operating mode occurs, with an overall decrease in operating performance and efficiency. Fuel delivery is based upon the oxygen sensor and five mapped values only. Rich running (black smoke) will occur until "closed loop" operation is initiated. A stumble or misfire on hard acceleration and/or erratic operation may be exhibited.TPS sensor related: sensor connector or wiring; sensor output affected or disrupted by dirt, grease, oil, wear, or breather tube position (must be to side opposite the TPS); sensor loose on throttle body manifold; throttle body related: throttle shaft or bearings worn/damaged; engine wiring harness related "35 Pin" (MA 1.7) Metal-Cased ECU: pin circuits 12, 25 and/or 27 damaged (wiring or connectors), pin circuits 12, 25 and/or 27 routed near noisy electrical signal (coils, alternator), intermittent 5 volt source from ECU (pin circuit 25); engine wiring harness related "24 Pin" (MSE 1.0) Plastic-Cased ECU: pin circuits 4, 8, and/or 14 damaged (wiring, connectors), pin circuits 4, 8, and/or 14 routed near noisy electrical signal (coils, alternator), intermittent 5 volt source from ECU (pin circuit 14); engine wiring harness related "32 Pin" (MSE 1.1) Plastic-Cased ECU: pin circuits 4, 8, and/or 18 damaged (wiring, connectors), pin circuits 4, 8, and/or 18 routed near noisy electrical signal (coils, alternator), intermittent 5 volt source from ECU (pin circuit 18); ECU/harness related: ECU-to-harness connection problemKohler CH Series
23ECU — ECU is unable to recognize or process signals from its memory. Engine will not run.ECU (internal memory problem), diagnosable only through the elimination of all other system/component faultsKohler CH Series
24Engine Speed Sensor — No tooth signal from speed sensor. MIL light will not go out when cranking. None-engine will not start or run as ECU is unable to estimate speed.Engine speed sensor related: sensor connector or wiring, sensor loose or air gap incorrect; speed sensor wheel related: damaged teeth, gap section not registering; engine wiring harness related: pin circuit wiring or connectors (pins 3 and/or 21 for "35 Pin" MA 1.7 Metal-Cased ECU; pins 9 and/or 10 for "24 Pin" MSE 1.0 Plastic-Cased ECU; pins 9 and/or 10 for "32 Pin" MSE 1.1 Plastic-Cased ECU); ECU/harness related: ECU-to-harness connection problemKohler CH Series
26AUXILIARY - AUX.Kohler G-292806
31Fuel Mixture or Oxygen Sensor — "System too lean." Oxygen sensor not sending expected voltage to ECU. System operates under "open loop" control only. Until fault is detected and registered by ECU, engine will run rich if oxygen sensor is shorted to ground or lean if it is shorted to battery voltage. After fault is detected, performance can vary, depending on cause. If performance is pretty good, the problem is probably with the oxygen sensor, wiring, or connectors. If the engine is still running rich (laboring, short on power) or lean (popping or misfiring), the fuel mixture is suspect, probably incorrect TPS initialization or low fuel pressure.TPS initialization incorrect: lean condition (check oxygen sensor signal with VOA and see Oxygen Sensor section); engine wiring harness related: pin circuit wiring or connectors (pin 10 for "35 Pin" MA 1.7 Metal-Cased ECU; pin 11 for "24 Pin" MSE 1.0 Plastic-Cased ECU; pin 20 for "32 Pin" MSE 1.1 Plastic-Cased ECU); low fuel pressure; oxygen sensor related: sensor connector or wiring problem, exhaust leak, poor ground path to engine (sensor is case grounded); poor system ground from ECU to engine, causing rich running while indicating leanKohler CH Series
0031Oxygen Sensor Heater Circuit High VoltageKohler CV26, Kohler CV735, Kohler CV745, Kohler ECV630, Kohler ECV749, Kohler ECV940
32Oxygen Sensor — No change in the sensor output signal. "Open loop" operation only, may cause a drop in system performance and fuel efficiency.Engine wiring harness related: pin circuit wiring or connectors (pin 10 for "35 Pin" MA 1.7 Metal-Cased ECU; pin 11 for "24 Pin" MSE 1.0 Plastic-Cased ECU; pin 20 for "32 Pin" MSE 1.1 Plastic-Cased ECU); oxygen sensor related: sensor connector or wiring problem, sensor contaminated or damaged, sensor below the minimum operating temperature (375°C, 709°F), poor ground path from sensor to engine (sensor grounds through shell, see Oxygen Sensor section)Kohler CH Series
32High Coolant TemperatureKohler 125REOZJG, Kohler 150 REOZJ4, Kohler 150REZG, Kohler 175REOZT4, Kohler 2000REOZM, Kohler 2000REOZMD
32COMMON FAULTKohler FR II, Kohler FR1, Kohler G-292806
32Sensor de oxígenoRelacionado con el haz de cables del motor: Conectores o cableado del circuito de patillas. Patilla 20. Relacionado con el sensor de oxígeno: Problema con el cableado o el conector del sensor. Sensor contaminado o dañado. Sensor por debajo de la temperatura mínima de funcionamiento (375 °C/709 °F). Ruta de conexión a masa del sensor al motor deficiente (el sensor se conecta a masa a través del revestimiento, ver la sección Sensor de oxígeno).Kohler LH775
0032Oxygen Sensor Heater Circuit Low VoltageKohler CV26, Kohler CV735, Kohler CV745, Kohler ECV630, Kohler ECV749, Kohler ECV940
32AEmergency StopReset the emergency stop switch.Kohler 125REOZJG, Kohler 150 REOZJ4, Kohler 150REZG, Kohler 175REOZT4, Kohler 2000REOZM, Kohler 2000REOZMD
33Oxygen Sensor/Fuel System — "System too rich." Temporary fuel adaptation control is at the upper limit. Erratic performance. Will run rich (smoke).Fuel supply related (nothing lean – only rich): restricted return line causing excessive fuel pressure, fuel inlet screen plugged (in-tank fuel pump only), incorrect fuel pressure at fuel rail; oxygen sensor related: sensor connector or wiring problem, sensor contaminated or damaged, exhaust leak, poor ground path, pin circuit wiring or connectors (pin 10 for "35 Pin" MA 1.7 Metal-Cased ECU; pin 11 for "24 Pin" MSE 1.0 Plastic-Cased ECU; pin 20 for "32 Pin" MSE 1.1 Plastic-Cased ECU); TPS sensor related: throttle plate position incorrectly set or registered during "Initialization", TPS problem or malfunction; engine wiring harness related: difference in voltage between sensed voltage (pin circuit 17 for metal-cased ECU, pin circuit 2 for plastic-cased ECU) and actual injector voltage (circuit 45/45A); systems related: ignition (spark plug, plug wire, ignition coil), fuel (fuel type/quality, injector, fuel pump, fuel pressure), combustion air (air cleaner dirty/restricted, intake leak, throttle bores), base engine problem (rings, valves), exhaust system leak, fuel in the crankcase oil, blocked or restricted fuel return circuit to tank; ECU/harness related: ECU-to-harness connection problemKohler CH Series
34Oxygen Sensor/Fuel System Components — Long term fuel adaptation control is at the upper or lower limit. System operates "closed loop." No appreciable performance loss as long as the temporary adaptation can provide sufficient compensation.Oxygen sensor related: sensor connector or wiring problem, sensor contaminated or damaged, exhaust leak, poor ground path, pin circuit wiring or connectors (pin 10 for "35 Pin" MA 1.7 Metal-Cased ECU; pin 11 for "24 Pin" MSE 1.0 Plastic-Cased ECU; pin 20 for "32 Pin" MSE 1.1 Plastic-Cased ECU); TPS sensor related: throttle plate position incorrect during "Initialization" procedure, TPS problem or malfunction; system related: engine is operating above the 176°C (350°F) temperature sensor limit; engine wiring harness related: difference in voltage between sensed voltage (pin circuit 17 for metal-cased ECU, pin circuit 2 for plastic-cased ECU) and actual injector voltage (circuit 45/45A), problem in wiring harness, ECU-to-harness connection problem; systems related: ignition (spark plug, plug wire, ignition coil), fuel (fuel type/quality, injector, fuel pressure, fuel pump), combustion air (air cleaner dirty/restricted, intake leak, throttle bores), base engine problem (rings, valves), exhaust system leak (muffler, flange, oxygen sensor mounting boss, etc.), fuel in the crankcase oil, altitude, blocked or restricted fuel return circuit to tankKohler CH Series
35LOW WATER TEMPKohler FR II, Kohler FR1, Kohler G-292806
36HIGH ENG. TEMPKohler FR II, Kohler G-292806
36High Engine TemperatureKohler 10RFOY, Kohler 10ROY, Kohler 15RFOY, Kohler 15ROY, Kohler 6RFOY, Kohler 6ROY
38SPEED PREALKohler FR II
38Low Oil PressureKohler 10RFOY, Kohler 10ROY, Kohler 15RFOY, Kohler 15ROY, Kohler 6RFOY, Kohler 6ROY
39OVERSPEED - OS.Kohler G-292806
40Pre High Coolant Temp.Kohler 125REOZJG, Kohler 150 REOZJ4, Kohler 150REZG, Kohler 175REOZT4, Kohler 2000REOZM, Kohler 2000REOZMD
40PREAL. IMMEDIATE STOPKohler FR II
41Pre Low Oil PressureCheck and adjust oil level or replace oil pump.Kohler 125REOZJG, Kohler 150 REOZJ4, Kohler 150REZG, Kohler 175REOZT4, Kohler 2000REOZM, Kohler 2000REOZMD
41Engine OverheatsKohler K141, Kohler K161, Kohler K181, Kohler K241, Kohler K301, Kohler K321
42Engine (Oil) Temperature Sensor — Not sending proper signal to ECU. Engine may be hard to start because ECU can't determine correct fuel mixture.Temperature sensor related: sensor wiring or connection; engine wiring harness related "35 Pin" (MA 1.7) Metal-Cased ECU: pin circuits 14 and/or 27A damaged (wires, connectors) or routed near noisy signal (coils, alternator, etc.), ECU-to-harness connection problem; engine wiring harness related "24 Pin" (MSE 1.0) Plastic-Cased ECU: pin circuits 4, 6 and/or 4A damaged (wires, connectors) or routed near noisy signal (coils, alternator, etc.), ECU-to-harness connection problem; engine wiring harness related "32 Pin" (MSE 1.1) Plastic-Cased ECU: pin circuits 4, 6 and/or (4A) damaged (wires, connectors) or routed near noisy signal (coils, alternator, etc.), ECU-to-harness connection problemKohler CH Series
43TPS "Auto-Learn" initialization function failed, throttle angle out of learning range (Below Min. Limit) — While performing the TPS "Auto-Learn" function, the measured throttle angle was not within acceptable limits. MIL illuminated. Engine will continue to run but not properly. Upon restart TPS Auto-Learn function will run again unless voltage to ECU disconnected to clear memory.TPS related: TPS rotated on throttle shaft assembly beyond allowable range, TPS bad; engine wiring harness related: broken or shorted wire in harness (ECU pin 18 to TPS pin 1, ECU pin 4 to TPS pin 2, ECU pin 8 to TPS pin 3); throttle body related: throttle shaft inside TPS worn, broken, or damaged, throttle plate loose or misaligned, throttle plate bent or damaged allowing extra airflow past, or restricting movement; ECU related: circuit providing voltage or ground to TPS damaged, TPS signal input circuit damaged; oxygen sensor/harness related: oxygen sensor bad, wiring problem to oxygen sensor, muffler leak (causing O2 sensor to falsely indicate a lean condition), bad ground between ECU and EngineKohler CH Series
44TPS "Auto-Learn" initialization function failed, throttle angle out of learning range (Above Max. Limit) — While performing the TPS "Auto-Learn" function, the measured throttle angle was not within acceptable limits. MIL illuminated. Engine will continue to run but not properly. Upon restart TPS Auto-Learn function will run again unless voltage to ECU disconnected to clear memory.TPS related: TPS rotated on throttle shaft assembly beyond allowable range, TPS bad; engine wiring harness related: broken or shorted wire in harness (ECU pin 18 to TPS pin 1, ECU pin 4 to TPS pin 2, ECU pin 8 to TPS pin 3); throttle body related: throttle shaft inside TPS worn, broken, or damaged, throttle plate loose or misaligned, throttle plate bent or damaged allowing extra airflow past, or restricting movement; ECU related: circuit providing voltage or ground to TPS damaged, TPS signal input circuit damaged; oxygen sensor/harness related: oxygen sensor bad, wiring problem to oxygen sensor, muffler leak (causing O2 sensor to falsely indicate a lean condition), bad ground between ECU and EngineKohler CH Series
48Emergency StopKohler 125REOZJG, Kohler 150 REOZJ4, Kohler 150REZG, Kohler 175REOZT4, Kohler 2000REOZM, Kohler 2000REOZMD
51Injector #1 circuit open, shorted to ground, or shorted to battery — Injector #1 is not functioning because the circuit is open, shorted to ground, or shorted to battery. Engine will run very poorly with only one cylinder functioning.Injector related: injector coil shorted or opened; engine wiring harness related: broken or shorted wire in harness (ECU pin 14 to injector pin 2, ECU pin 28 to fuel pump relay pin 86, fuel pump relay pin 87 to injector pin 1), open main fuse F1; fuel pump relay related: bad fuel pump relay (primary side functional but pin 30 to pin 87 remains open; primary side pin 85 to pin 86 is either open, or shorted during engine operation); ECU related: circuit controlling injector #1 damaged, circuit controlling fuel pump relay damagedKohler CH Series
52Injector #2 circuit open, shorted to ground, or shorted to battery — Injector #2 is not functioning because the circuit is open, shorted to ground, or shorted to battery. Engine will run very poorly with only one cylinder functioning.Injector related: injector coil shorted or opened; engine wiring harness related: broken or shorted wire in harness (ECU pin 15 to injector pin 2, ECU pin 28 to fuel pump relay pin 86, fuel pump relay pin 87 to injector pin 1), opened main fuse F1; fuel pump relay related: bad fuel pump relay (primary side functional, but pin 30 to pin 87 remains open; primary side pin 85 to pin 86 is open or shorted during engine operation); ECU related: circuit controlling injector #2 damaged, circuit controlling fuel pump relay damagedKohler CH Series
55MIL (Diagnostic lamp) circuit open, shorted to ground, or shorted to battery — MIL is not functioning because the circuit is open, shorted to ground, or shorted to battery. Engine will run normally if no other errors are present.MIL (diagnostic lamp) related: MIL element opened or element shorted to ground, lamp missing; engine wiring harness related: broken or shorted wire in harness (ECU pin 29 to lamp open or shorted); vehicle wiring harness related: broken or shorted wire in harness (power lead to MIL open or shorted); ECU related: circuit controlling lamp damagedKohler CH Series
56Fuel pump relay circuit open, shorted to ground, or shorted to battery — Fuel pump, ignition coils, and fuel injectors will not function because the fuel pump relay circuit is either open, shorted to ground, or may be "on" continuously if shorted to battery. Engine will not run, or fuel pump will continue to run when switch is off.Fuel pump relay related: bad fuel pump relay (primary side open or shorted); fuel pump related: fuel pump open or shorted internally; engine wiring harness related: fuel pump fuse F1 open, broken or shorted wire in harness (ECU pin 28 to fuel pump relay pin 86, ignition switch to fuel pump relay pin 85); ECU related: circuit controlling fuel pump relay damagedKohler CH Series
56AIR DAMPER - A.D.Kohler G-292806
057-243ISSUE: 6Kohler se7310, Kohler se7320
60SYSTEM READYKohler FR II, Kohler FR1, Kohler G-292806
61Denotes the end of fault codes. If signaled first, no other fault codes are present.Kohler CH Series
61FALLA DEL CARGADOR DE BATERIAKohler FR II
62Low Battery VoltsKohler 125REOZJG, Kohler 150 REOZJ4, Kohler 150REZG, Kohler 175REOZT4, Kohler 2000REOZM, Kohler 2000REOZMD
62BAJO VOLTAJE DE LA BATERIAKohler FR II
63Low FuelRefuel the generator set.Kohler 125REOZJG, Kohler 150 REOZJ4, Kohler 150REZG, Kohler 175REOZT4, Kohler 2000REOZM, Kohler 2000REOZMD
72OverspeedKohler 7CCFKM, Kohler 7CCFKM / 7CCFKMR, Kohler 7CCKM, Kohler 7CCKM / 7CCKMR
80SW. NOT IN "AUTO"Kohler FR II, Kohler FR1, Kohler G-292806
90High Temperature Sensor ActivationReplace thermostat if function is questionable or defectiveKohler LH775
0107Manifold Absolute Pressure Sensor Circuit Low Voltage or OpenKohler CV26, Kohler CV735, Kohler CV745, Kohler ECV630, Kohler ECV749, Kohler ECV940
0107Circuit du TMAP basse tension ou ouvertKohler ECH940, Kohler ECH980
0108Manifold Absolute Pressure Sensor Circuit High VoltageKohler CV26, Kohler CV735, Kohler CV745, Kohler ECV630, Kohler ECV749, Kohler ECV940
0108Circuit du TMAP haute tensionKohler ECH940, Kohler ECH980
0112Intake Air Temperature Sensor Circuit Low VoltageKohler CV26, Kohler CV735, Kohler CV745, Kohler ECV630, Kohler ECV749, Kohler ECV940
0112Circuit basse tension de sonde de température d'air d'admissionKohler ECH940, Kohler ECH980
0113Intake Air Temperature Sensor Circuit High Voltage or OpenKohler CV26, Kohler CV735, Kohler CV745, Kohler ECV630, Kohler ECV749, Kohler ECV940
0113Circuit haute tension de sonde de température d'air d'admission ou circuit ouvertKohler ECH940, Kohler ECH980
0117Coolant/Oil Temperature Sensor Circuit Low VoltageKohler CV26, Kohler CV735, Kohler CV745, Kohler ECV630, Kohler ECV749, Kohler ECV940
0117Circuit basse tension de sonde de température d'huile/liquide de refroidissementKohler ECH940, Kohler ECH980
0118Coolant/Oil Temperature Sensor Circuit High Voltage or OpenKohler CV26, Kohler CV735, Kohler CV745, Kohler ECV630, Kohler ECV749, Kohler ECV940
0118Circuit haute tension de sonde de température d'huile/liquide de refroidissement ou circuit ouvertKohler ECH940, Kohler ECH980
0122Throttle Position Sensor Circuit Low Voltage or OpenKohler CV26, Kohler CV735, Kohler CV745, Kohler ECV630, Kohler ECV749, Kohler ECV940
0122Circuit du TPS basse tension ou ouvertKohler ECH940, Kohler ECH980
0123Throttle Position Sensor Circuit High VoltageKohler ECV940, Kohler ECV980
0123Circuit du TPS haute tensionKohler ECH940, Kohler ECH980
0131Oxygen Sensor 1 Circuit Low VoltageKohler ECV940, Kohler ECV980
0131Circuit basse tension de sonde d'oxygène 1Kohler ECH940, Kohler ECH980
0132Oxygen Sensor 1 Circuit High VoltageKohler ECV940, Kohler ECV980
0132Circuit haute tension de sonde d'oxygène 1Kohler ECH940, Kohler ECH980
0171Maximum Adaptation Limit ExceededKohler ECV940, Kohler ECV980
0172Minimum Adaptation Limit ExceededKohler ECV940, Kohler ECV980
0174Lean Fuel Condition at High Load (Open Loop)Kohler ECV940, Kohler ECV980
0201Injector 1 Circuit MalfunctionKohler ECV940, Kohler ECV980
0201Injecteur de carburant - Défaillance du circuit, injecteur 1Kohler ECH940, Kohler ECH980
0202Injector 2 Circuit MalfunctionKohler ECV940, Kohler ECV980
0202Injecteur de carburant - Défaillance du circuit, injecteur 2Kohler ECH940, Kohler ECH980
0230Fuel Pump Module Circuit Low Voltage or OpenKohler ECV940, Kohler ECV980
0230Pompe à carburant - Circuit basse tension ou ouvertKohler ECH940, Kohler ECH980
0232Pompe à carburant - Circuit haute tensionKohler ECH940, Kohler ECH980
0351Bobine d'allumage - Défaillance de la bobine d'allumage, cylindre 1Kohler ECH940, Kohler ECH980
0352Bobine d'allumage - Défaillance de la bobine d'allumage, cylindre 2Kohler ECH940, Kohler ECH980
503Engine Over SpeedReduce engine load or check for mechanical issues.Kohler APM804, Kohler KD103V20, Kohler KD27V12, Kohler KD36V16, Kohler KD4000, Kohler KD45V20
601Generator Over TemperatureCool down generator and monitor temperature.Kohler APM804, Kohler KD103V20, Kohler KD27V12, Kohler KD36V16, Kohler KD4000, Kohler KD45V20
794High Temperature Sensor ActivationReplace thermostat if function is questionable or defectiveKohler LH775
812VCC+REGISTRO TIRO DE AIRE*Kohler FR II
1001Low Water EmergencyKohler FR II
1002Auxiliary FaultKohler FR II
1003Pre-Alarm High Engine TemperatureKohler FR II
1693Sortie tach (microprocesseur) - Circuit tach basCâble tach défectueux (à la terre). Court-circuit à la masse du circuit GCU.Kohler ECH940, Kohler ECH980
1694Sortie tach (microprocesseur) - Circuit tach hautErreur du circuit du microprocesseur ou GCU.Kohler ECH940, Kohler ECH980
6269016Anomaly CodeKohler ECH940, Kohler ECH980
AAccidental Starts!Before servicing the engine or equipment, always disconnect the spark plug lead to prevent the engine from starting accidentally. Ground the lead to prevent sparks that could cause fires.Kohler Command 11, Kohler Command 12.5, Kohler Command 14
AC Sens Loss ShutdwnLoss of AC sensing shutdown — Shutdown: The controller shut down the generator because there was less than 5% of rated voltage measured on Phase A for 3 seconds, only in AUTO, only after acceptable voltage (> 5% of UV setting) has been detected.Check for loose wiring and connections; Check all AC leads; Troubleshoot alternator.Kohler 14RCA, Kohler 20RCA, Kohler 24VDC, Kohler 36VDC, Kohler 48VDC, Kohler 6VSG
AC Sens Loss WarningLoss of AC sensing warning — Warning: The controller has measured less than 5% of rated voltage on Phase A for 1 second, 10 seconds after crank disconnect.Check for loose wiring and connections; Check all AC leads; Troubleshoot alternator.Kohler 14RCA, Kohler 20RCA, Kohler 24VDC, Kohler 36VDC, Kohler 48VDC, Kohler 6VSG
Acc. 23-DAcc. 23-D timer contact does not open during the set exercise periodKohler Series S340
Acc. 26-DArea Protection Control initiates closing of the engine starting contactKohler Series S340
Accy PwrOver WarningAccy PwrOver WarningController internal circuit protection activatedPress OFF to reset. Contact an authorized Kohler dealer for serviceKohler 10RESV, Kohler 10RESV/10RESVL, Kohler 12RESV, Kohler 12RESV/12RESVL, Kohler 14/20RES, Kohler 14/20RESA/RESAL
Accy PwrOver WarningController internal circuit protection activatedPress OFF to reset; Contact an authorized Kohler distributor/dealer for serviceKohler 14/20RESA/RESAL, Kohler 14RCA, Kohler 20 kW Models, Kohler 20RCA, Kohler 20RESC/RESCL, Kohler Model RESA/L or RESC/L
AccyPwrOver WarningAccessory Power Overload — Warning: An overcurrent fault (short circuit) on the accessory controller power output.Check wiring to RBUS accessories; Troubleshoot the RBUS accessories; refer to the documentation provided with the accessories.Kohler 14RCA, Kohler 20RCA, Kohler 24VDC, Kohler 36VDC, Kohler 48VDC, Kohler 6VSG
AFAuxiliary fault input shutdown — input from a customer-supplied switch that closes when the fault is active; the generator set shuts down 0.3 seconds after the fault is detected and will not start when the fault is active (input is grounded); this protection becomes active 3 seconds after crank disconnectInput from a customer-supplied switch that closes when the fault is active.Check the cause of the auxiliary fault.Kohler 10/13/15ERG, Kohler 10ERG, Kohler 12RES, Kohler 12TRES, Kohler 13ERG, Kohler 15ERG
Always OffOnCue Plus has been used to control this PIM digital output. The digital output is no longer controlled by the generator set. Applies to digital outputs B3 through B6 on the PIM onlyClick on the PIM output in OnCue Plus to turn the output on or off. See the OnCue Plus Operation Manual; To reset the PIM digital output to a function controlled by the generator set, use SiteTech software to re-assign the output eventKohler 14RCA, Kohler 20RCA, Kohler RCA
Always OffAlways Off — Notice: OnCue's Power Chain view has been used to control this digital output. The digital output is no longer controlled by the generator set. Applies to digital outputs B3 through B6 on the PIM only.Click on the output in OnCue's Power Chain view to turn the output on or off. See the OnCue Operation Manual; To reset the digital output to a function controlled by the generator set, use SiteTech software to re-assign the output event.Kohler 24VDC, Kohler 36VDC, Kohler 48VDC, Kohler 6VSG, Kohler 6VSG-24V, Kohler 6VSG-36V
Always OnAlways OnKohler 14RCA, Kohler 20RCA, Kohler 24VDC, Kohler 36VDC, Kohler 48VDC, Kohler 6VSG
ATS ComError WarningATS communication error — Warning: The controller has lost communication with the RXT ATS that had previously been communicating properly.Check connection to ATS module.Kohler 14RCA, Kohler 20RCA, Kohler RCA, Kohler RDC2 or DC2 generator set controller, Kohler RXT, Kohler TP-6808
ATS Fail Xfr WarningATS fail to transfer — Warning: The RXT ATS has reported a fail to transfer, the digital output for ATS Fail To Transfer (PIM) is active (contacts closed).Consult ATS manual for troubleshooting.Kohler 14RCA, Kohler 20RCA, Kohler RCA, Kohler RDC2 or DC2 generator set controller, Kohler RXT, Kohler TP-6808
ATS PhaseRot WarningWarning: The RXT ATS has reported a phase rotation mismatch (3-phase only) and the ATS will not transfer.Check wiring to the ATS; Consult ATS manual for troubleshooting.Kohler 14RCA, Kohler 20RCA, Kohler RCA
AUTOAUTOKohler FR II, Kohler FR1, Kohler G-292806
Auto LockedChicago Code Active — The digital output for Chicago Code Active (PIM) is active (contacts closed), indicating the digital input for Chicago Code Active (PIM) is active (low) and thus master switch is locked in the AUTO positionCheck customer equipment connected to the PIM moduleKohler 14RCA, Kohler 20RCA, Kohler 24VDC, Kohler 36VDC, Kohler 48VDC, Kohler 6VSG
Aux Input ShutdwnAuxiliary input shutdown — Shutdown: The controller shut down the generator because the digital input for a custom shutdown (AuxiliaryInputShutdown - PIM) was activated (low).Check customer equipment connected to the PIM module.Kohler 14RCA, Kohler 20RCA, Kohler 24VDC, Kohler 36VDC, Kohler 48VDC, Kohler 6VSG
Aux Input WarningAuxiliary input warning — Warning: The digital input for a custom warning (AuxiliaryInputWarning - PIM) is active (low).Check customer equipment connected to the PIM module.Kohler 14RCA, Kohler 20RCA, Kohler 24VDC, Kohler 36VDC, Kohler 48VDC, Kohler 6VSG
Auxiliary faultAuxiliary faultKohler 10ERG, Kohler 25EFOZD, Kohler 28EFOZD, Kohler 28EOZ, Kohler 32EOZ, Kohler G2
Auxiliary InputAuxiliary Input — An optional customer-connected input is closed. (Digital input from optional PIM.)Check customer-supplied equipment.Kohler 24RCL, Kohler 30RCL, Kohler 38RCLB
Auxiliary Switch FaultAuxiliary Switch Fault — GEN Position and Utility Source Position LEDs flash alternately 2 times/second.Controller cannot determine the transfer switch position.Check wiring and connections to position microswitches. See the schematic drawing for connections. Test position microswitch operation. Replace microswitch if necessary. See Section 7. Transfer switch in intermediate position. Disconnect power and manually operate the transfer switch. See instructions in the ATS operation/installation manual. Inspect for signs of coil damage or overheating and replace coil if necessary.Kohler RDT, Kohler SE-ILC
BElectrical Shock!Never touch electrical wires or components while the engine is running. They can be sources of electrical shock.Kohler Command 11, Kohler Command 12.5, Kohler Command 14
Batt Chg Flt WarningBattery charger fault warning — Warning: The digital input for Battery Charger Fault Warning (PIM) is active (low). For an external battery charger only, not applicable to the RDC2 built-in battery charging.Check customer equipment connected to the PIM module.Kohler 14RCA, Kohler 20RCA, Kohler 24VDC, Kohler 36VDC, Kohler 48VDC, Kohler 6VSG
Battery CrLoCritically Low Battery Voltage — Engine starting battery voltage falls below 11 V for more than 10 seconds. Inhibited during the engine crank cycle. Clears when the battery voltage returns to an acceptable level.Check the battery rating and condition.; Check the battery charger operation.; Charge or replace the battery.Kohler 24RCL, Kohler 30RCL, Kohler 38RCLB
Battery CRLow WarningWarning: Battery voltage dropped to 11 VDC or less for 30 seconds or more.Check engine starting battery; Check battery charger DC output voltage from RDC2. See Section 5.12.2.Kohler 14RCA, Kohler 20RCA, Kohler RCA
Battery CRLow WarningBattery CRLow Warning — Warning: Battery voltage dropped to 11 VDC or less for 30 seconds or more.Check engine starting battery; Check battery charger DC output voltage from VSC on lead CHO to the battery.Kohler 24VDC, Kohler 36VDC, Kohler 48VDC, Kohler 6VSG, Kohler 6VSG-24V, Kohler 6VSG-36V
Battery HighHigh Battery Voltage — Engine starting battery voltage rises above 133% (16 V) of the battery voltage setting for more than 10 seconds. Inhibited during the engine crank cycle. Clears when the battery voltage returns to an acceptable level.Check the battery rating and condition.; Check the battery charger operation.Kohler 24RCL, Kohler 30RCL, Kohler 38RCLB
Battery High WarningWarning: The controller has measured battery voltage that is above the high warning setting for 10 seconds or more. Operates during exercise and normal operation.Check engine starting battery.Kohler 14RCA, Kohler 20RCA, Kohler 24VDC, Kohler 36VDC, Kohler 48VDC, Kohler 6VSG
Battery LowLow Battery Voltage — Engine starting battery voltage falls below the battery voltage setting (typically 12.5 volts) for more than 90 seconds when the engine is not running. Inhibited during the engine crank cycle. Clears when the battery voltage returns to an acceptable level.Check the battery rating and condition.; Check the battery charger operation.; Charge or replace the battery.Kohler 24RCL, Kohler 30RCL, Kohler 38RCLB
Battery Low WarningWarning: The controller has measured battery voltage that is below the low warning setting for 90 seconds or more.Check engine starting battery; Check battery charger DC output voltage from RDC2. See Section 5.12.2.Kohler 14RCA, Kohler 20RCA, Kohler 24VDC, Kohler 36VDC, Kohler 48VDC, Kohler 6VSG
Battery Low WarningsLow battery voltage warnings are displayed on the controller display.Check the battery connections and ensure they are secure. Replace the battery if it is low on charge.Kohler 14RCA, Kohler 20RCA, Kohler RCA
Blinking Fast (1 1/2 Hz)Governor controller is powered and an engine speed signal is being detected. If the engine is not running, this indicates electrical noise on the speed signal wiresKohler Basic, Kohler Digital, Kohler Digital 550, Kohler Microprocessor-Plus, 16-Light
Blinking Slow (1/2 Hz)Governor controller is powered, but not sensing a speed signal. OK if engine is not running. If the engine is running, this indicates a fault with the speed signalKohler Basic, Kohler Digital, Kohler Digital 550, Kohler Microprocessor-Plus, 16-Light
BLOWN F1 FUSE (REMOTE ANNUNCIATOR-3 AMP)Blown controller fuse F1DEFECTIVE DECISION DEFECTIVE MONITOR (IF EQUIPPED) REMOTE ANNUNCIATOR (IF EQUIPPED) DEFECTIVE REMAINING ACCESSORIES AUDIO-VISUAL CONNECTED TO TB1-42A ALARM (IF EQUIPPED)Kohler 10RFOY, Kohler 10ROY, Kohler 15RFOY, Kohler 15ROY, Kohler 6RFOY, Kohler 6ROY
BLOWN F2 FUSE (CONTROLLER-3 AMP)Blown controller fuse F2BATTERY CONNECTIONS REVERSED SHORTED DC SUPPLY TO INDICATOR PANEL SHORTED CONTROLLER CIRCUIT BOARDKohler 10RFOY, Kohler 10ROY, Kohler 15RFOY, Kohler 15ROY, Kohler 6RFOY, Kohler 6ROY
BusDeadLiveThe bus is measured to be dead when one of the generators is supposed to be supplying voltage to the bus (closed contactor).Bus metering V9A and V9B connections to V9 of paralleling protection harness are connected incorrectly.Kohler 14/20RESA/RESAL, Kohler 14RCA, Kohler 14RCA/14RCAL, Kohler 14RCA/L, Kohler 18RCAL, Kohler 20 kW Models
BusLiveDeadThe bus is measured to be live when no generators are connected to it (both contactors open).Bus metering V9A and V9B connections to V9 of paralleling protection harness are connected incorrectly.Kohler 14/20RESA/RESAL, Kohler 14RCA, Kohler 14RCA/14RCAL, Kohler 14RCA/L, Kohler 18RCAL, Kohler 20 kW Models
CLethal Exhaust Gases!Avoid inhaling exhaust fumes, and never run the engine in a closed building or confined area.Kohler Command 11, Kohler Command 12.5, Kohler Command 14
CfgModelNumThe two generators that are intended to be paralleled have incompatible model numbers.Incorrect configuration of one of the generators. Different generator types. The paralleled generator sets must be the same kW model. (i.e. two 14 kW or two 20 kWor 26 kW models).The paralleled generator sets must be the same kW model. (i.e. two 14 kW or two 20 kW models.)Kohler 14/20RESA/RESAL, Kohler 14RCA, Kohler 14RCA/14RCAL, Kohler 14RCA/L, Kohler 18RCAL, Kohler 20 kW Models
CfgSysVoltThe system voltage of the two generators intended to be paralleled is not the same.One of the two generators is incorrectly configured. Intermittent connections on RBUS network wiring.Kohler 14/20RESA/RESAL, Kohler 14RCA, Kohler 14RCA/14RCAL, Kohler 14RCA/L, Kohler 18RCAL, Kohler 20 kW Models
Chk DateTimeVerify Date Time Setting — The time and date have not been set on the generator controller.Enter the date and time using the RDC2 controller. See Figure 3-8 and Figure 3-16.Kohler 24RCL, Kohler 30RCL, Kohler 38RCLB
Chk DateTime WarningCheck date and time warning — Warning: DC power to the controller has been interrupted and the date and time may not be correct. Event history may not have accurate time/date stamps.Verify the time and date settings to ensure proper operation of scheduled operations and for event history logging.Kohler 14RCA, Kohler 20RCA, Kohler 24VDC, Kohler 36VDC, Kohler 48VDC, Kohler 6VSG
ChkngMeterThis generator has paralleled to the other generator and is verifying that the metering is connected and establishing the connection directionStatus message appears the first time the two generators are paralleledKohler 14/20RESA/RESAL, Kohler 14RCA, Kohler 14RCA/14RCAL, Kohler 18RCAL, Kohler 20 kW Models, Kohler 20RCA
Common FaultThe digital output for Common Fault (PIM) is active (contacts closed), indicating the generator is shutdown for any (all) faultCheck for faults and troubleshoot any/all fault conditions individuallyKohler 14RCA, Kohler 20RCA, Kohler 24VDC, Kohler 36VDC, Kohler 48VDC, Kohler 6VSG
Common WarngThe digital output for Common Warning (PIM) is active (contacts closed), indicating that any (all) warning is activeCheck for warnings and troubleshoot any/all warning conditions individuallyKohler 14RCA, Kohler 20RCA, Kohler RCA
Common WarngCommon Warng — Notice: The digital output for Common Warning (PIM) is active (contacts closed), indicating that any (all) warning is active.Check for warnings and troubleshoot any/all warning conditions individually.Kohler 24VDC, Kohler 36VDC, Kohler 48VDC, Kohler 6VSG, Kohler 6VSG-24V, Kohler 6VSG-36V
ConCheckFailFailure to Auto-Discover APM connections.Wires 9A and 9B crossed between the generators. Wires 9A or 9B not connected.Kohler 14/20RESA/RESAL, Kohler 14RCA, Kohler 14RCA/14RCAL, Kohler 14RCA/L, Kohler 18RCAL, Kohler 20 kW Models
ConCheckingPerforming APM connection auto-discoveryThis generator has started in RUN, the other generator is in OFFKohler 14/20RESA/RESAL, Kohler 14RCA, Kohler 14RCA/14RCAL, Kohler 18RCAL, Kohler 20 kW Models, Kohler 20RCA
ConNotDetermAPM connection auto-discovery is not complete. This means that the generator does not know which contactor is connected to it.Generators not yet started in RUN with other generator in OFF. See the APM instruction sheet for instructions to perform the auto-discovery procedure.See the APM instruction sheet for instructions to perform the auto-discovery procedureKohler 14/20RESA/RESAL, Kohler 14RCA, Kohler 14RCA/14RCAL, Kohler 14RCA/L, Kohler 18RCAL, Kohler 20 kW Models
ContactorOkSuccessful auto-discovery of APM connections.Auto-discovery was activated by placing other generator in OFF and this generator in RUN.Kohler 14/20RESA/RESAL, Kohler 14RCA, Kohler 14RCA/14RCAL, Kohler 14RCA/L, Kohler 18RCAL, Kohler 20 kW Models
Coolant Lvl LowLow Coolant Level Shutdown — The coolant level switch input has been activated.Check coolant level.; Check radiator hoses for leaks.; Contact an authorized distributor/dealer for service.Kohler 24RCL, Kohler 30RCL, Kohler 38RCLB
CoolntTemp 0Coolant Temp 0 Shutdown — The ECM reported a problem with the coolant temperature sensor reading: 0 = high temperature.Check coolant level.; Check radiator and fans for obstruction.; Contact an authorized distributor/dealer for service and provide the fault code.Kohler 24RCL, Kohler 30RCL, Kohler 38RCLB
CoolntTemp 3Coolant Temp 3 Shutdown — The ECM reported a problem with the coolant temperature sensor reading: 3 = high voltage.Contact an authorized distributor/dealer for service and provide the fault code.Kohler 24RCL, Kohler 30RCL, Kohler 38RCLB
CoolntTemp 4Coolant Temp 4 Shutdown — The ECM reported a problem with the coolant temperature sensor reading: 4 = low voltage.Contact an authorized distributor/dealer for service and provide the fault code.Kohler 24RCL, Kohler 30RCL, Kohler 38RCLB
CoolntTemp 5Coolant Temp 5 Shutdown — The ECM reported a problem with the coolant temperature sensor reading: 5 = open circuit.Contact an authorized distributor/dealer for service and provide the fault code.Kohler 24RCL, Kohler 30RCL, Kohler 38RCLB
CoolTemp VhiEct Higher Than Expected 2 — Coolant temperature is extremely high.Check coolant level.; Check radiator and fans for obstruction.; Contact an authorized distributor/dealer for service and provide the fault code.Kohler 24RCL, Kohler 30RCL, Kohler 38RCLB
CoolTempHighEct Higher Than Expected 1 — Coolant temperature is too high.Check coolant level.; Check radiator and fans for obstruction.; Contact an authorized distributor/dealer for service and provide the fault code.Kohler 24RCL, Kohler 30RCL, Kohler 38RCLB
Crank LostCrank Signal Lost — Crankshaft Position Sensor (CPS) timeout error occurred.Contact an authorized distributor/dealer for service and provide the fault code.Kohler 24RCL, Kohler 30RCL, Kohler 38RCLB
Current A High WarningOver CurrentKohler 14/20RESA/RESAL, Kohler 14RCA, Kohler 14RCA/14RCAL, Kohler 18RCAL, Kohler 20 kW Models, Kohler 20RCA
DCB1Relé de falla común DCB1Llene el sistema de enfriamiento antes de encender el calentador de bloque. Ponga en marcha el motor hasta que este se caliente y llene el radiador para purgar el aire del sistema antes de energizar el calentador de bloque.Kohler 25CCL, Kohler 30CCL, Kohler 36CCL
DCB2Relé de falla común DCB2Kohler 25CCL, Kohler 30CCL, Kohler 36CCL
Default Pars WarningDefault Parameters — Warning: The controller has been loaded with default parameters.Configure settings as required for desired operation.Kohler 14RCA, Kohler 20RCA, Kohler 24VDC, Kohler 36VDC, Kohler 48VDC, Kohler 6VSG
E0Controller memory failureReplace governor controller.Kohler Basic, Kohler Digital, Kohler Digital 550, Kohler Microprocessor-Plus, 16-Light
E1Loss of remote speed potentiometer signalKohler Basic, Kohler Digital, Kohler Digital 550, Kohler Microprocessor-Plus, 16-Light
E2Overspeed detected. Governor controller must be turned off and reset to allow an engine restartKohler Basic, Kohler Digital, Kohler Digital 550, Kohler Microprocessor-Plus, 16-Light
E3Actuator drive overcurrent detectedCheck wiring. Check actuator loading and linkage.Kohler Basic, Kohler Digital, Kohler Digital 550, Kohler Microprocessor-Plus, 16-Light
E-28LAMP TEST — INDICATOR LAMP DOES NOT LIGHTKohler R1237K05
ECM warningsECM warnings (any warnings with ECM in the fault name) — This group of faults includes a wide variety of faults that originate from the engine ECM and also contain ECM in the fault name.Contact an authorized distributor/dealer for service and provide the fault code.Kohler 24RCL, Kohler 30RCL, Kohler 38RCLB
ED0053030050Warning YELLOW light turn onEngine ECU has detect a malfunctionsContact KOHLER authorised workshopsKohler KDI 3404 TCR
Emerg Pwr OnEmergency Power System Supplying Load — The digital output for EPS Supplying Load (PIM) is active (contacts closed), indicating there is current output (>5%) from the alternator, only if CTs are installedKohler 14RCA, Kohler 20RCA, Kohler 24VDC, Kohler 36VDC, Kohler 48VDC, Kohler 6VSG
Emerg StopEmergency Stop Shutdown — The emergency stop switch has been activated, or there has been an open circuit in the wiring.Contact an authorized distributor/dealer for service.Kohler 24RCL, Kohler 30RCL, Kohler 38RCLB
Emerg Stop ShutdwnEmerg Stop ShutdwnRemote emergency stop button activated or shutdown (prime mover) switch turned to the off (open, O) positionReset the emergency stop switch(es) and reset the controller by pressing the OFF/RESET buttonKohler 14RCA, Kohler 14RCA/L, Kohler 14RES, Kohler 20RCA, Kohler 20RCA/L, Kohler 20RES
Emerg Stop ShutdwnShutdown: The optional emergency stop button has been pressed or emergency stop leads ESS and/or ESN are not connected.Reset the emergency stop button and clear the fault as described in Section 5.6; Check lead ESS and ESN connections to the emergency stop button. If there is no E-stop button, connect ESS and ESN together.Kohler 14RCA, Kohler 20RCA, Kohler RCA
Enclosure Intrusion AlarmEnclosure Intrusion Alarm — Warning: Enclosure door is open. (Optional communications kit required.)Close and secure the enclosure door; Check for signs of unauthorized entry.Kohler 24VDC, Kohler 36VDC, Kohler 48VDC, Kohler 6VSG, Kohler 6VSG-24V, Kohler 6VSG-36V
Eng CooldownThe digital output for Engine Cooldown Active (PIM) is active (contacts closed), indicating the generator is running in cooldown. (Delay 5 min.)Check remote start circuit if it was expected that the generator should be running; Consult ATS operations manualKohler 14RCA, Kohler 20RCA, Kohler RCA
Eng CooldownEng Cooldown — Notice: The digital output for Engine Cooldown Active (PIM) is active (contacts closed), indicating the generator is running in cooldown. (Delay 5 min.)Check remote start circuit if it was expected that the generator should be running.Kohler 24VDC, Kohler 36VDC, Kohler 48VDC, Kohler 6VSG, Kohler 6VSG-24V, Kohler 6VSG-36V
Eng Speed HighHigh Engine Speed — Engine speed exceeds 115% of the normal running speed for more than 0.3 seconds.Contact an authorized distributor/dealer for service.Kohler 24RCL, Kohler 30RCL, Kohler 38RCLB
Eng Speed LowLow Engine Speed — Engine speed drops below 85% of the normal running speed for more than 3 seconds.Reduce the load by turning off appliances.; Contact an authorized distributor/dealer for service.Kohler 24RCL, Kohler 30RCL, Kohler 38RCLB
Engine M/N Invalid ShutdwnShutdown: Generator model number has not been entered. (Engine model number is selected automatically based on generator set model.)Enter the generator set model number from the RDC2 keypad, or use SiteTech to select the genset model number.Kohler 14RCA, Kohler 20RCA, Kohler RCA
Engine M/N Invalid ShutdwnEngine M/N Invalid Shutdwn — Shutdown: Generator model number has not been entered. (Engine model number is selected automatically based on generator set model.)Enter the generator set model number from the VSC keypad, or use SiteTech to select the genset model number.Kohler 24VDC, Kohler 36VDC, Kohler 48VDC, Kohler 6VSG, Kohler 6VSG-24V, Kohler 6VSG-36V
Engine Speed High ShutdwnShutdown: The controller shut down the generator because engine speed, as calculated from AC frequency, was above the high speed setting for 0.3 seconds or more.Troubleshoot engine operation per the engine service manual.Kohler 14RCA, Kohler 20RCA, Kohler RCA
Engine Speed High ShutdwnEngine Speed High Shutdwn — Shutdown: The controller shut down the generator because engine speed, as calculated from AC frequency, was above the high speed setting for 0.3 seconds or more.Troubleshoot engine operation per the engine service manual.Kohler 24VDC, Kohler 36VDC, Kohler 48VDC, Kohler 6VSG, Kohler 6VSG-24V, Kohler 6VSG-36V
Engine Speed Low ShutdwnShutdown: The controller shut down the generator, after crank disconnect, because engine speed, as calculated from AC frequency, was below the low speed setting for 3 seconds or more. The enclosure thermostat has tripped.Troubleshoot engine operation per the engine service manual; Check for evidence of high temperatures inside the enclosure. Reset the thermostat. See Section 5.8.Kohler 14RCA, Kohler 20RCA, Kohler RCA
Engine Speed Low ShutdwnEngine Speed Low Shutdwn — Shutdown: The controller shut down the generator, after crank disconnect, because engine speed, as calculated from AC frequency, was below the low speed setting for 3 seconds or more.Troubleshoot engine operation per the engine service manual.Kohler 24VDC, Kohler 36VDC, Kohler 48VDC, Kohler 6VSG, Kohler 6VSG-24V, Kohler 6VSG-36V
ErraticSigThe power metering on this controller gives a signal that is not consistent with the system configuration. Reversing the power direction does not resolve the problem.Bad wiring to the CT. Too much tension on wires from the CT to the controller.Kohler 14/20RESA/RESAL, Kohler 14RCA, Kohler 14RCA/14RCAL, Kohler 14RCA/L, Kohler 18RCAL, Kohler 20 kW Models
ESEEngine Stop EventKohler SH255, Kohler SH255, SH265, SH270, Kohler SH265, Kohler SH270
Exer Not SchATS Exercise Not Scheduled — Exercise Not Scheduled. No exercise has been scheduled on the RDC2 controller.See Section 2.5 for instructions to set the exerciser.Kohler 24RCL, Kohler 30RCL, Kohler 38RCLB
Exer Not Sch WarningWarning: There is no exercise scheduled.Set the exercise schedule.Kohler 14RCA, Kohler 20RCA, Kohler RCA
Exer Not Sch WarningExer Not Sch Warning — Warning: There is no exercise scheduled.Set the exercise schedule.Kohler 24VDC, Kohler 36VDC, Kohler 48VDC, Kohler 6VSG, Kohler 6VSG-24V, Kohler 6VSG-36V
F1No AC output.Auxiliary winding fuse (F1) blownReplace the fuse. Contact an authorized distributor/dealer for service if fuse blows repeatedly.Kohler 12RES, Kohler 12TRES, Kohler 17RES, Kohler 18RES, Kohler 18TRES, Kohler 8.5RES
F1Generator set stops suddenly.Auxiliary winding fuse (F1) blownReplace the fuse. Contact an authorized distributor/dealer for service if fuse blows repeatedly.Kohler 12RES, Kohler 12TRES, Kohler 17RES, Kohler 18RES, Kohler 18TRES, Kohler 8.5RES
F1Blown F1 fuse (remote annunciator: 3 amp)Defective Decision Monitor; Defective Remote Annunciator; Defective Audio-Visual Alarm (accessories connected to controller TB42A)Kohler Basic, Kohler Digital, Kohler Digital 550, Kohler Fast-Response I, Kohler Microprocessor-Plus, 16-Light
F1Aux. winding fuse F1 blownCheck fuse F1 and replace if blown. If fuse blows again, check statorKohler 12RES, Kohler 12TRES, Kohler 8.5RES
F1Auxiliary Winding Fuse — A replaceable 10-amp fuse protects the alternator.Kohler 15REYG, Kohler 30REYG
F1Fuse F1, 5 ampsKohler 38RCL, Kohler 48RCL, Kohler 60RCL
F1Fuse F1 (3-amp) on the controller circuit board protects the engine and controller circuitryIf the generator set will not crank or accessories will not work, and the battery/connections appear okay, one of these fuses may be blownReplace fuseKohler 10-18RY/RZ, Kohler 6.5RMY, Kohler TP-5631
F1Generator will not start when power fails or with test switch depressed.Check generator. YES Jumper main logic board terminals 57 and 58. Does generator start? NO Check wiring harness to contactor. YES Jumper main logic board terminals 57 and 59. Does generator start? NO Is jumper installed between 58 and 59? YES NO Remove TDES and wait 30 seconds. Is there continuity between terminals 1 and 7 on the TDES relay?Kohler S340 Logic Board
F01Error code F01Corrective action not statedKohler KD83V16
F2The generator set does not crank.Fuse F2 blownReplace the fuse. Contact an authorized distributor/dealer for service if fuse blows repeatedly.Kohler 12RES, Kohler 12TRES, Kohler 17RES, Kohler 18RES, Kohler 18TRES, Kohler 8.5RES
F2Blown F2 fuse (controller: 3 amp)Battery connections reversed; shorted DC supply to indicator panel circuit board; shorted controller circuit boardReplace blown fuses and resume operation; if the fuse blows again, use the chart to identify the faulty component(s)Kohler Basic, Kohler Digital, Kohler Digital 550, Kohler Fast-Response I, Kohler Microprocessor-Plus, 16-Light
F2Blown fuse F2, relay interface board (RIB)Replace fuse. If fuse blows again, disconnect the board leads one at a time to identify the cause of the blown fuse: Lead 70A at the fuel valve; Lead IGN at the ignition module; Lead 71A at the starter relay; Leads FP and FN at the rotor. Repair or replace the component causing the blown fuse. If fuse continues to blow and the previous step did not identify the cause, check the continuity of leads FP and FN and the leads from the P14 connector. Replace any bad leads. Use a pin pusher to remove leads from the connector, if necessary. If replacing the leads does not solve the problem, replace the RIB.Kohler 12RES, Kohler 12TRES, Kohler 15REYG, Kohler 30REYG, Kohler 8.5RES
F2Blown fuse F2 (ADC-RES)Replace fuse. If fuse blows again, disconnect the leads one at a time to identify the cause of the blown fuse: Lead 70C at the fuel valve; Lead IGN at the ignition module; Lead 71A at the starter relay; Leads FP and FN at the rotor. Repair or replace the component causing the blown fuse. If fuse continues to blow and the previous step did not identify the cause, check the continuity of leads FP and FN and the leads from the P14 connector. Replace any bad leads. Use a pin pusher to remove leads from the connector, if necessary. If replacing the leads does not solve the problem, replace the controller circuit board.Kohler 12RES, Kohler 12TRES, Kohler 8.5RES
F2The battery is discharged, but the charger has power and is operating. — Blown fuse.Blown fuse.Check the 5-amp fuse F2 (5A-T) inside the battery charger and replace if necessary. Check inline fuse F4 and replace if necessary.Kohler 12RES, Kohler 12TRES, Kohler 17RES, Kohler 18RES, Kohler 18TRES, Kohler 8.5RES
F2Fuse F2, ECM 10 ampsKohler 38RCL, Kohler 48RCL, Kohler 60RCL
F2Fuse F2 (3-amp) on the controller circuit board protects the engine and controller circuitryIf the generator set will not crank or accessories will not work, and the battery/connections appear okay, one of these fuses may be blownReplace fuseKohler 10-18RY/RZ, Kohler 6.5RMY, Kohler TP-5631
F02Low Oil PressureCheck oil level and condition. Replace oil if necessary.Kohler KD62V12, Kohler KD83V16
F3Controller LED display is offController fuse (F3) is blown.Replace the fuse. If the fuse blows again, contact the distributor/dealer.Kohler 12RES, Kohler 18RES, Kohler 8.5RES
F3The generator set does not crank.Fuse F3 blownReplace the fuse. Contact an authorized distributor/dealer for service if fuse blows repeatedly.Kohler 12RES, Kohler 12TRES, Kohler 17RES, Kohler 18RES, Kohler 18TRES, Kohler 8.5RES
F3Generator set stops suddenly.Controller fuse (F3) blownReplace the fuse. If the fuse blows again, contact the distributor/dealer.Kohler 12RES, Kohler 12TRES, Kohler 17RES, Kohler 18RES, Kohler 18TRES, Kohler 8.5RES
F3Blown F3 fuse (engine and accessories: 15 amp)Defective engine electrical (wire 70) components; defective panel lamps or engine gauges; defective dry contact kit, audio/visual alarm kit, and other accessories connected to TB1-42AReplace blown fuses and resume operation; if the fuse blows again, use the chart to identify the faulty component(s)Kohler Basic, Kohler Digital, Kohler Digital 550, Kohler Fast-Response I, Kohler Microprocessor-Plus, 16-Light
F3Blown fuse F3, controllerReplace fuse; if fuse blows again, check circuit and components.Kohler 12RES, Kohler 12TRES, Kohler 15REYG, Kohler 30REYG, Kohler 8.5RES
F3F3 - Engine and Accessories (15 Amp.) blown (genset not equipped with K4 relay)Defective gauges; Defective safeguard breaker/voltage regulator; Defective engine run circuit; Defective crank circuitKohler Fast-Response I
F3Fuse F3 (15-amp) on the controller circuit board protects the engine and controller circuitryIf the generator set will not crank or accessories will not work, and the battery/connections appear okay, one of these fuses may be blownReplace fuseKohler 10-18RY/RZ, Kohler 6.5RMY, Kohler TP-5631
F4Aux. winding fuse F4 blown (lead 55)Replace blown fuse; If fuse blows again, check stator.Kohler 10REOZD, Kohler 15REOZD, Kohler 20REOZD
F4Fuse F4, ignition, 15 ampsKohler 38RCL, Kohler 48RCL, Kohler 60RCL
F6Fuse F6, starter, 20 ampsKohler 38RCL, Kohler 48RCL, Kohler 60RCL
F13High Coolant TemperatureReduce load or allow engine to cool down. Check coolant level and condition.Kohler KD62V12
F14Low Coolant LevelAdd coolant to proper level.Kohler KD62V12
Failure to Acquire Emergency SourceFailure to Acquire Emergency Source Warning — the transfer switch does not sense voltage from the generator set within 75 seconds after signaling the generator set to start.Engine start circuit or generator set operation problem; generator set shuts down when the engine start contacts are closed (for example, shutting the generator set down by moving the master switch to OFF during the engine cooldown time delay).Check the engine start circuit and the generator set operation. Determine the reason for the generator set shutdown and then reset the fault as described in Section 4.4.1. The fault clears when the system acquires the emergency source.Kohler RDT, Kohler SE-ILC
Failure to Acquire StandbyFailure to Acquire Standby — GEN Available LED flashes 2 times/second.Open circuit breaker.Check and close ATS source and generator set circuit breakers.Kohler RDT, Kohler SE-ILC
Failure to TransferFailure to Transfer — GEN or Utility Source Position LED flashes 2 times/second.Source not available.Check source voltage, frequency, stability.Kohler RDT, Kohler SE-ILC
Frequency HighHigh Frequency — Governed frequency exceeds 110% of the system’s frequency setpoint for more than 10 seconds. Function becomes active 10 seconds after engine start (10 second inhibit).Contact an authorized distributor/dealer for service.Kohler 24RCL, Kohler 30RCL, Kohler 38RCLB
Frequency High ShutdwnShutdown: The controller shut down the generator because the frequency measured on Phase A exceeded the high frequency setting for 10 seconds, 10 seconds or more after crank disconnect.Troubleshoot engine operation per the engine service manual.Kohler 14RCA, Kohler 20RCA, Kohler RCA
Frequency High WarningOver FrequencyKohler 14/20RESA/RESAL, Kohler 14RCA, Kohler 14RCA/14RCAL, Kohler 18RCAL, Kohler 20 kW Models, Kohler 20RCA
Frequency LowLow Frequency — Governed frequency falls below 90% of the system frequency setting for more than 10 seconds, or 1 Hz below the system frequency setting for more than 60 seconds. Function becomes active 10 seconds after engine start (10 second inhibit).Reduce the load by turning off appliances and restart the generator set.; Contact an authorized distributor/dealer for service.Kohler 24RCL, Kohler 30RCL, Kohler 38RCLB
Frequency Low ShutdwnShutdown: The controller shut down the generator because the frequency measured on Phase A was less than the low limit for 10 seconds or the measured frequency was 10 Hz or more less than rated for 60 seconds or more, 10 seconds or more after crank disconnect. The enclosure thermostat has tripped.Troubleshoot engine operation per the engine service manual; Check for evidence of high temperatures inside the enclosure. Reset the thermostat. See Section 5.8.Kohler 14RCA, Kohler 20RCA, Kohler RCA
Frequency Low WarningUnder FrequencyKohler 14/20RESA/RESAL, Kohler 14RCA, Kohler 14RCA/14RCAL, Kohler 18RCAL, Kohler 20 kW Models, Kohler 20RCA
Fuel Leak ShutdwnShutdown: The controller shut down the generator because the digital input for Fuel Tank Leak Shutdown (PIM) was activated (low).Check customer equipment connected to the PIM module.Kohler 14RCA, Kohler 20RCA, Kohler RCA
Fuel Leak ShutdwnFuel Leak Shutdwn — Shutdown: The controller shut down the generator because the digital input for Fuel Tank Leak Shutdown (PIM) was activated (low).Check customer equipment connected to the PIM module.Kohler 24VDC, Kohler 36VDC, Kohler 48VDC, Kohler 6VSG, Kohler 6VSG-24V, Kohler 6VSG-36V
Fuel Leak WarningWarning: The digital input for Fuel Tank Leak Warning (PIM) is active (low).Check customer equipment connected to the PIM module.Kohler 14RCA, Kohler 20RCA, Kohler 24VDC, Kohler 36VDC, Kohler 48VDC, Kohler 6VSG
Fuel Level CrHi WarningWarning: The digital input for Critically High Fuel Level Warning (PIM) is active (low).Check customer equipment connected to the PIM module.Kohler 14RCA, Kohler 20RCA, Kohler RCA
Fuel Level CrHi WarningFuel Level CrHi Warning — Warning: The digital input for Critically High Fuel Level Warning (PIM) is active (low).Check customer equipment connected to the PIM module.Kohler 24VDC, Kohler 36VDC, Kohler 48VDC, Kohler 6VSG, Kohler 6VSG-24V, Kohler 6VSG-36V
Fuel Level High WarningWarning: The digital input for High Engine Fuel Level Warning (PIM) is active (low).Check customer equipment connected to the PIM module.Kohler 14RCA, Kohler 20RCA, Kohler 24VDC, Kohler 36VDC, Kohler 48VDC, Kohler 6VSG
Fuel Level Low ShutdwnShutdown: The controller shut down the generator because the digital input for Low Fuel Level Shutdown (PIM) was activated (low).Check customer equipment connected to the PIM module.Kohler 14RCA, Kohler 20RCA, Kohler RCA
Fuel Level Low ShutdwnFuel Level Low Shutdwn — Shutdown: The controller shut down the generator because the digital input for Low Fuel Level Shutdown (PIM) was activated (low).Check customer equipment connected to the PIM module.Kohler 24VDC, Kohler 36VDC, Kohler 48VDC, Kohler 6VSG, Kohler 6VSG-24V, Kohler 6VSG-36V
Fuel Level Low WarningWarning: The digital input for Low Fuel Level Warning (PIM) is active (low).Check customer equipment connected to the PIM module.Kohler 14RCA, Kohler 20RCA, Kohler 24VDC, Kohler 36VDC, Kohler 48VDC, Kohler 6VSG
Fuel Pressure LowFuel Pressure Low — Warning: Fuel pressure sensor has measured fuel pressure below 4.5 inches of water column. (Optional communications kit required.)Check fuel supply and fuel lines; Check the fuel pressure at the regulator. See Section 5.8.2.Kohler 24VDC, Kohler 36VDC, Kohler 48VDC, Kohler 6VSG, Kohler 6VSG-24V, Kohler 6VSG-36V
Fuel SpillThe digital output for Fuel Spill (PIM) is active (contacts closed), indicating any of the digital inputs for Fuel Tank Leak Warning, Fuel Tank Leak Shutdown, Engine Fuel Level Warning or Engine Fuel Level Critically High (PIM) is active (low)Check customer equipment that is connected to the Fuel Tank Leak Warning, Fuel Tank Leak Shutdown, Engine Fuel Level Warning or Engine Fuel Level Critically High input on the PIMKohler 14RCA, Kohler 20RCA, Kohler 24VDC, Kohler 36VDC, Kohler 48VDC, Kohler 6VSG
Gen RunningGen Running — Notice: The digital output for Generator Running (PIM) is active (contacts closed), indicating the generator is running.Check controller front panel buttons for potential RUN command; If in AUTO, check remote start lines.Kohler 24VDC, Kohler 36VDC, Kohler 48VDC, Kohler 6VSG, Kohler 6VSG-24V, Kohler 6VSG-36V
GenBrkerOpen WarningGenerator Circuit Breaker Open — There is voltage at the generator set but no voltage measured on the emergency side of the ATS (Model RXT transfer switch required)Check line circuit breaker; Check for and correct short circuits or overloading on the load side before resetting the circuit breakerKohler 14RCA, Kohler 20RCA, Kohler 24VDC, Kohler 36VDC, Kohler 48VDC, Kohler 6VSG
Generator Management OffThis generator has been stopped by generator management because it is not presently needed to supply the load. The generator is available and will start if it is needed againKohler 14/20RESA/RESAL, Kohler 14RCA, Kohler 20 kW Models, Kohler 20RCA, Kohler 20RESC/RESCL, Kohler Model RESA/L or RESC/L
Genset S/N UnavalUnavailable Genset Serial Number — Generator set serial number is unavailable.Contact an authorized distributor/dealer for service. See section 3.11.Kohler 24RCL, Kohler 30RCL, Kohler 38RCLB
Ground FaultGround Fault Warning — The digital input for Ground Fault Warning is active (low). (PIM required.)Check customer equipment connected to the PIM.Kohler 24RCL, Kohler 30RCL, Kohler 38RCLB
Ground Fault WarningThe digital input for Ground Fault Warning (PIM) is active (low)Check customer equipment connected to the PIM moduleKohler 14RCA, Kohler 20RCA, Kohler 24VDC, Kohler 36VDC, Kohler 48VDC, Kohler 6VSG
HBHigh battery voltage warning — fault code is displayed if the engine starting battery voltage rises above 16 VDC for a 12 VDC system or above 30 VDC for a 24 VDC system for more than 10 seconds when the engine is not running; this fault condition does not inhibit engine starting; the fault condition clears when the battery voltage returns to a voltage within the limits for more than 10 secondsBattery rating or conditionCheck the battery rating and condition.Kohler 10/13/15ERG, Kohler 10ERG, Kohler 12RES, Kohler 12TRES, Kohler 13ERG, Kohler 15ERG
HEHigh engine temperature shutdown — Shutdown occurs if the engine coolant temperature exceeds the maximum temperature for more than 5 seconds. This protective becomes active after the engine reaches the crank disconnect speed.Low engine coolant levelCheck for blocked air inlets and exhaust outlets.Kohler 10/13/15ERG, Kohler 10ERG, Kohler 12RES, Kohler 12TRES, Kohler 13ERG, Kohler 15ERG
HESTHigh Exhaust System TemperatureKohler se7310, Kohler se7320
HETHigh Engine Temperature (HET) ShutdownNormally open K1 contacts (F) close and fault lamp lights. Normally—closed K1 contacts (G) open to de-energize engine components. Generator shuts down.Kohler 10C, Kohler 10CC, 12CC Mobile Generator Set, Kohler 10CFC, Kohler 10CFZ, Kohler 10CZ, 12CZ Mobile Generator Set, Kohler 10RFOY
High battery voltageHigh battery voltageKohler 25EFOZD, Kohler 28EFOZD, Kohler 28EOZ, Kohler 32EOZ, Kohler G2
High battery voltageBattery voltage exceeds normal rangeKohler 10ERG
High engine temperatureEngine runtime, hoursKohler 12RES, Kohler 18RES
High engine temperatureHigh engine temperature shutdownKohler 25EFOZD, Kohler 28EFOZD, Kohler 28EOZ, Kohler 32EOZ, Kohler G2
High engine temperatureEngine overheatingKohler 10ERG
High Lube Oil Temperature ShutdownOil temperature higher than 325_F (163_C)Kohler 14RCA, Kohler 20RCA, Kohler RCA
High Lube Oil Temperature ShutdownHigh Lube Oil Temperature Shutdown — Shutdown: Oil temperature higher than 325°F (163°C).Kohler 24VDC, Kohler 36VDC, Kohler 48VDC, Kohler 6VSG, Kohler 6VSG-24V, Kohler 6VSG-36V
High Lube Oil Temperature WarningOil temperature higher than 300_F (149_C)See Overheats in the troubleshooting charts in Section 5.14Kohler 14RCA, Kohler 20RCA, Kohler RCA
High Lube Oil Temperature WarningHigh Lube Oil Temperature Warning — Warning: Oil temperature higher than 300°F (149°C).See Overheats in the troubleshooting charts in Section 4.9.Kohler 24VDC, Kohler 36VDC, Kohler 48VDC, Kohler 6VSG, Kohler 6VSG-24V, Kohler 6VSG-36V
IAT High 1Iat Higher Than Expected 1 — Engine manifold air temperature is too high.Contact an authorized distributor/dealer for service and provide the fault code.Kohler 24RCL, Kohler 30RCL, Kohler 38RCLB
IAT Volt LoIat Low Voltage — The ECM reported an Engine Air Temperature/Manifold Absolute Pressure Sensor (TMAP) error.Contact an authorized distributor/dealer for service and provide the fault code.Kohler 24RCL, Kohler 30RCL, Kohler 38RCLB
K1 relay LEDEngine Run RelayKohler 7CCFKM, Kohler 7CCFKM / 7CCFKMR, Kohler 7CCKM, Kohler 7CCKM / 7CCKMR
K2 relay LEDEngine Crank RelayKohler 7CCFKM, Kohler 7CCFKM / 7CCFKMR, Kohler 7CCKM, Kohler 7CCKM / 7CCKMR
K3Flash relay (K3) on RIB (ADC 2100)Check flash LED on RIB; Check fuse F2 and troubleshoot RIBKohler 12RES, Kohler 12TRES, Kohler 8.5RES
K3Flash relay (K3) on controller board (ADC-RES)Check fuse F2; Check flash LED1 on controller board. If LED1 indicates power to K3 but relay does not operate, replace controller circuit boardKohler 12RES, Kohler 12TRES, Kohler 8.5RES
K3 relay LEDAC Crank Disconnect RelayKohler 7CCFKM, Kohler 7CCFKM / 7CCFKMR, Kohler 7CCKM, Kohler 7CCKM / 7CCKMR
K4 relay LEDFault Shutdown RelayKohler 7CCFKM, Kohler 7CCFKM / 7CCFKMR, Kohler 7CCKM, Kohler 7CCKM / 7CCKMR
K5 relay LEDTime Delay Control (Start/Run)Kohler 7CCFKM, Kohler 7CCFKM / 7CCFKMR, Kohler 7CCKM, Kohler 7CCKM / 7CCKMR
KA-01-BTime Delay on Transfer from Normal to EmergencyKohler S340 Logic Board
KA-02-ATime Delay on Engine StartingKohler S340 Logic Board
L.F.Low FuelKohler Fast Response, Kohler Kohler Control Fast Response I
LBLow battery voltage warning — Fault code is displayed if the engine starting battery voltage falls below 11 VDC for more than 30 seconds when the engine is not running. Not operative during the engine crank cycle, this fault condition does not inhibit engine starting. The fault condition clears when the battery voltage returns to an acceptable level.Battery rating or conditionCheck the battery rating and condition.; Check the battery charger operation.; Charge or replace the battery.Kohler 10/13/15ERG, Kohler 10ERG, Kohler 12RES, Kohler 12TRES, Kohler 13ERG, Kohler 15ERG
LCLLow coolant level — not usedNot used on air-cooled models.Kohler 12RES, Kohler 12TRES, Kohler 15RES, Kohler 15REYG, Kohler 30RES, Kohler 30REYG
Lo Crank VltLow Cranking Voltage — Low cranking voltage. Battery voltage falls below 60% of system battery voltage for more than 6 seconds while the starter is engaged.Charge or replace the battery.Kohler 24RCL, Kohler 30RCL, Kohler 38RCLB
Lo Crank Vlt WarningDuring cranking, the controller measured battery voltage less than 60% (7.2V or 14.4V) for 6 seconds or more during crankingCheck cranking batteryKohler 14RCA, Kohler 20RCA, Kohler RCA
Lo Crank Vlt WarningLo Crank Vlt Warning — Warning: During cranking, the controller measured battery voltage less than 60% (7.2V or 14.4V) for 6 seconds or more during cranking.Check cranking battery.Kohler 24VDC, Kohler 36VDC, Kohler 48VDC, Kohler 6VSG, Kohler 6VSG-24V, Kohler 6VSG-36V
LO PLow oil pressure shutdown — Shutdown occurs if a low oil pressure condition exists for more than 5 seconds. This protective becomes active 30 seconds after the engine has reached crank disconnect speed (30 second inhibit). Note: The low oil pressure shutdown does not protect against low oil level. Check the oil level at the engine.Check for leaks in the lubrication system.; Check the oil level and add oil if the level is low.Kohler 12RES, Kohler 18RES
LOCLoss of coolant — not usedNot used on air-cooled models.Kohler 12RES, Kohler 12TRES, Kohler 15RES, Kohler 15REYG, Kohler 30RES, Kohler 30REYG
Locked rotorThe generator set also shuts down on OC if no engine rotation is sensed during cranking. Shuts down 3 seconds after the fault is detected.Kohler 12RES, Kohler 12TRES, Kohler 17/18RES, Kohler 17RES, Kohler 17RES/18RES, Kohler 18RES
Locked RotorLocked Rotor — No engine rotation is sensed during cranking. Shuts down 3 seconds after the fault is detected.Check the battery.; Check for loose connections.; Check for obstruction of alternator or engine.; Contact an authorized distributor/dealer for service.Kohler 24RCL, Kohler 30RCL, Kohler 38RCLB
Locked Rotor ShutdwnThe controller shut down the generator because no rotation of the engine or alternator was detected, for 3 seconds or more, during crankingCheck cranking circuit; Troubleshoot the engine. See Engine Service Manuals; Check alternator connections to controller and auxiliary winding circuit breaker; Troubleshoot the alternatorKohler 14RCA, Kohler 20RCA, Kohler RCA
Locked Rotor ShutdwnLocked Rotor Shutdwn — Shutdown: The controller shut down the generator because no rotation of the engine or alternator was detected, for 3 seconds or more, during cranking.Check cranking circuit; Troubleshoot the engine. See Engine Service Manuals; Check alternator connections to controller and auxiliary winding circuit breaker; Troubleshoot the alternator.Kohler 24VDC, Kohler 36VDC, Kohler 48VDC, Kohler 6VSG, Kohler 6VSG-24V, Kohler 6VSG-36V
LOPLow oil pressure shutdown — Shutdown occurs if a low oil pressure condition exists for more than 5 seconds. This protective becomes active 30 seconds after the engine has reached crank disconnect speed (30 second inhibit). Note: The low oil pressure shutdown does not protect against low oil level. Check the oil level at the engine.Leaks in the lubrication system; low oil levelCheck for leaks in the lubrication system; Check the oil level and add oil if the level is low.Kohler 10/13/15ERG, Kohler 10C, Kohler 10CC, 12CC Mobile Generator Set, Kohler 10CFC, Kohler 10CFZ, Kohler 10CZ, 12CZ Mobile Generator Set
Loss of coolantSeawater pump impeller failure shutdownKohler 25EFOZD, Kohler 28EFOZD, Kohler 28EOZ, Kohler 32EOZ
Loss of coolantLoss of coolantKohler 25EFOZD, Kohler 28EFOZD, Kohler 28EOZ, Kohler 32EOZ, Kohler G2
LossOfComAPMThe Automatic Paralleling Module has stopped communicating on RBUS. (An APM was detected on the RBUS network but is no longer communicating).APM is unplugged. Primary controller is powered down. Check the battery connections. See previous page for more information. Intermittent connections on RBUS network wiring.Check the battery connections. See previous page for more information; Check RBUS communication connectionsKohler 14/20RESA/RESAL, Kohler 14RCA, Kohler 14RCA/14RCAL, Kohler 14RCA/L, Kohler 18RCAL, Kohler 20 kW Models
LossOfComm2The primary controller has lost communication with the secondary controller. (A secondary controller was detected, then communication was lost.)RBUS disconnected, secondary controller battery disconnected, updating firmware in secondary controller, or intermittent RBUS connections.Kohler 14/20RESA/RESAL, Kohler 14RCA, Kohler 14RCA/14RCAL, Kohler 14RCA/L, Kohler 14RES, Kohler 18RCAL
LossOfFieldThis generator has absorbed more than 25% reactive power (magnetic excitation current) for 20 seconds.Generator voltage on this generator is not calibrated correctly. Generator voltage on other generator is not calibrated correctly. Bus voltage on this generator is not calibrated correctly. Bus voltage on the other generator is not calibrated correctly.Kohler 14/20RESA/RESAL, Kohler 14RCA, Kohler 14RCA/14RCAL, Kohler 14RCA/L, Kohler 18RCAL, Kohler 20 kW Models
Low battery voltageCrank cycle statusKohler 12RES, Kohler 18RES
Low battery voltageLow battery voltageKohler 25EFOZD, Kohler 28EFOZD, Kohler 28EOZ, Kohler 32EOZ, Kohler G2
Low battery voltageBattery voltage is below normalKohler 10ERG
Low FuelLow Fuel — Notice: The digital output for Low Fuel (PIM) is active (contacts closed), indicating any of the digital inputs for Low Fuel Pressure Warning, Low Fuel Level Warning or Low Fuel Level Shutdown (PIM) is active (low).Check customer equipment connected to the PIM module.Kohler 24VDC, Kohler 36VDC, Kohler 48VDC, Kohler 6VSG, Kohler 6VSG-24V, Kohler 6VSG-36V
Low oil pressureLow oil pressure shutdownKohler 10ERG, Kohler 25EFOZD, Kohler 28EFOZD, Kohler 28EOZ, Kohler 32EOZ, Kohler G2
Low Oil PressureLow Oil Pressure — Shutdown occurs approximately 8 seconds after fault; fault occurs when engine oil pressure drops below specified limitKohler 10-18RY/RZ, Kohler 6.5RMY, Kohler TP-5631
LOWTLow Water TemperatureKohler 10RFOY, Kohler 10ROY, Kohler 15RFOY, Kohler 15ROY, Kohler 6RFOY, Kohler 6ROY
LWLLow Water Level (LWL) ShutdownNormally open K1 contacts (F) close and fault lamp lights. Normally—closed K1 contacts (G) open to de-energize engine components. Generator shuts down.Kohler 10RFOY, Kohler 10RFOZ, Kohler 10ROY, Kohler 10ROZ, Kohler 15RFOY, Kohler 15RFOZ
M3Fuse M3, battery charging alternator, 70 ampsKohler 38RCL, Kohler 48RCL, Kohler 60RCL
M3.212APM INTERNAL power BATTERY WARNINGKohler APM802, Kohler KD1000, Kohler KD1250, Kohler KD1350, Kohler KD1500, Kohler KD1750
Main Power Overload ShutdownThe generator shuts down due to a main power overload.Check the circuit breaker and ensure it is not tripped. If necessary, replace the circuit breaker.Kohler 14RCA, Kohler 20RCA, Kohler RCA
MainPwrOverLMain Power Overload — Main power overload. An over current fault on the 70 controller power output (short circuit).Check for shorted run relay. Check wiring for short circuits.; Contact an authorized distributor/dealer for service.Kohler 24RCL, Kohler 30RCL, Kohler 38RCLB
MainPwrOverL ShutdownMainPwrOverL ShutdownController internal circuit protection activatedPress OFF to reset. Contact an authorized Kohler dealer for serviceKohler 10RESV, Kohler 10RESV/10RESVL, Kohler 12RESV, Kohler 12RESV/12RESVL, Kohler 14/20RES, Kohler 14/20RESA/RESAL
MainPwrOverL ShutdownController internal circuit protection activatedPress OFF to reset; Contact an authorized Kohler distributor/dealer for serviceKohler 14/20RESA/RESAL, Kohler 14RCA, Kohler 20 kW Models, Kohler 20RCA, Kohler 20RESC/RESCL, Kohler Model RESA/L or RESC/L
MainPwrOverL ShutdwnThe internal current limit circuit has tripped, indicating an overcurrent condition on the DC power supply circuitCheck crank, run, and flash relay circuits for short circuits. See Section 5.12.1Kohler 14RCA, Kohler 20RCA, Kohler RCA
MainPwrOverL ShutdwnMainPwrOverL Shutdwn — Shutdown: The internal current limit circuit has tripped, indicating an overcurrent condition on the DC power supply circuit.Check crank, run, and flash relay circuits for short circuits.Kohler 24VDC, Kohler 36VDC, Kohler 48VDC, Kohler 6VSG, Kohler 6VSG-24V, Kohler 6VSG-36V
Maint Req'd WarningEngine run time, or calendar days, has exceeded the maintenance reminder settingChange the oil and perform other maintenance according to the service schedule in Section 2.1 and in the engine manuals; Reset the maintenance timer after service. See Section 2.7.5Kohler 14RCA, Kohler 20RCA, Kohler RCA
Maint Req'd WarningMaint Req'd Warning — Warning: Engine run time, or calendar days, has exceeded the maintenance reminder setting.Change the oil and perform other maintenance according to the service schedule in Section 2.1; Reset the maintenance timer after service. See Section 2.3.Kohler 24VDC, Kohler 36VDC, Kohler 48VDC, Kohler 6VSG, Kohler 6VSG-24V, Kohler 6VSG-36V
Maint Req’dMaintenance Required Warning — Engine maintenance is due.Check the maintenance schedule in the operation manual for tasks such as changing the oil, spark plugs or the air filter.Kohler 24RCL, Kohler 30RCL, Kohler 38RCLB
MeteringOkThe generator has verified that the metering is connected correctly and that the direction is consistent with expected power direction.Status message indicates that the CT is connected to the generator correctly.Kohler 14/20RESA/RESAL, Kohler 14RCA, Kohler 14RCA/14RCAL, Kohler 14RCA/L, Kohler 18RCAL, Kohler 20 kW Models
MeterUnknownThis generator does not know if the metering is connected or the orientation of the connection. This means that the generators can’t share load accurately until this information is known.System commissioning and startup not yet complete. See the APM instructions.See the APM instructionsKohler 14/20RESA/RESAL, Kohler 14RCA, Kohler 14RCA/14RCAL, Kohler 14RCA/L, Kohler 18RCAL, Kohler 20 kW Models
Minor FaultMinor Fault — Notice: The digital output for Minor Fault (PIM) is active (contacts closed), indicating either the digital input for Ground Fault Indicator Warning (PIM) is active (low) or the controller detected Low Cranking Voltage.Check customer equipment connected to the PIM module; Check cranking battery condition.Kohler 24VDC, Kohler 36VDC, Kohler 48VDC, Kohler 6VSG, Kohler 6VSG-24V, Kohler 6VSG-36V
NoCurrentThe generator has applied load (using the other generator) and has observed no current on the power sensing inputs.The CT is not connected to the controller. The output leads from the generator do not go through the CT in the correct direction. See the APM instructions.See the APM instructionsKohler 14/20RESA/RESAL, Kohler 14RCA, Kohler 14RCA/14RCAL, Kohler 14RCA/L, Kohler 18RCAL, Kohler 20 kW Models
NormSrcUnavlRXT required — Notice: The normal power source (source 1) is disconnected, unavailable or unacceptableCheck for utility source power outage; check wiring and connections to the ATSKohler RDC2 or DC2 generator set controller, Kohler RXT, Kohler TP-6808
Not in AutoNot In Auto — The generator set is not in Automatic (standby) mode. Remote start and stop commands from a transfer switch or remote switch will be ignored.Press AUTO to place the generator set in Automatic mode, when appropriate.Kohler 24RCL, Kohler 30RCL, Kohler 38RCLB
Not In Auto WarningThe RDC2 controller is not in AUTO. The generator will not start from an ATS or remote device. The digital output for Not In Auto (PIM) is active (contacts closed)Press the Auto button to ensure automatic system operationKohler 14RCA, Kohler 20RCA, Kohler 24VDC, Kohler 36VDC, Kohler 48VDC, Kohler 6VSG
nullDefective exhaust valve.Kohler M18, Kohler M20
OB1 CommLossCommunication with option board #1 has been lostCheck RBUS wiring to inoperative option boardKohler 14RCA, Kohler 20RCA, Kohler RCA
OB1 CommLoss (PIM)OB1 CommLoss (PIM) — Warning: Communications with option board #1 has been lost.Check RBUS wiring to inoperative option board.Kohler 24VDC, Kohler 36VDC, Kohler 48VDC, Kohler 6VSG, Kohler 6VSG-24V, Kohler 6VSG-36V
OB2 CommLossCommunication with option board #2 has been lostCheck RBUS wiring to inoperative option boardKohler 14RCA, Kohler 20RCA, Kohler RCA
OB3 CommLossCommunication with option board #3 has been lostCheck RBUS wiring to inoperative option boardKohler 14RCA, Kohler 20RCA, Kohler RCA
OB4 CommLossCommunication with option board #4 has been lostCheck RBUS wiring to inoperative option boardKohler 14RCA, Kohler 20RCA, Kohler RCA
OCOvercrank shutdown — Shutdown occurs after 3 unsuccessful starting attempts. The crank cycle is set for three starting attempts of 15 seconds cranking and 15 seconds rest.Fuel supply or battery problem; no output voltage; line circuit breaker; loose connectionsCheck the fuel supply, spark plug, and battery.; Check for loose connections.; Contact an authorized distributor/dealer for service if problem continues.Kohler 10/13/15ERG, Kohler 10ERG, Kohler 10RFOY, Kohler 10ROY, Kohler 12RES, Kohler 12TRES
OCLocked rotor — The generator set also shuts down on OC if no engine rotation is sensed during cranking. Shuts down 3 seconds after the fault is detected.Contact an authorized distributor/dealer for service if problem continues.Kohler 12RES, Kohler 12TRES, Kohler 17/18RES, Kohler 17RES, Kohler 17RES/18RES, Kohler 18RES
OFOverfrequency shutdown — Shutdown occurs when the governed frequency exceeds 110% of the system's frequency setpoint for more than 5 seconds. This protective becomes active 10 seconds after engine start (10 second inhibit).OverfrequencyContact an authorized distributor/dealer for service if problem continues.Kohler 10/13/15ERG, Kohler 10ERG, Kohler 12RES, Kohler 12TRES, Kohler 13ERG, Kohler 15ERG
OffGovernor controller is either not currently powered or is being reverse poweredCheck polarity of supplied power. If correctly powered, governor controller is malfunctioning.Kohler Basic, Kohler Digital, Kohler Digital 550, Kohler Microprocessor-Plus, 16-Light
Oil Level Low ShutdwnThe controller shut down the generator because the digital input for Low Oil Level Shutdown (PIM) was activated (low)Check customer equipment connected to the PIM moduleKohler 14RCA, Kohler 20RCA, Kohler RCA
Oil Level Low ShutdwnOil Level Low Shutdwn — Shutdown: The controller shut down the generator because the digital input for Low Oil Level Shutdown (PIM) was activated (low).Check customer equipment connected to the PIM module.Kohler 24VDC, Kohler 36VDC, Kohler 48VDC, Kohler 6VSG, Kohler 6VSG-24V, Kohler 6VSG-36V
Oil Level Low WarningThe digital input for Low Oil Level Warning (PIM) is active (low)Check customer equipment connected to the PIM moduleKohler 14RCA, Kohler 20RCA, Kohler 24VDC, Kohler 36VDC, Kohler 48VDC, Kohler 6VSG
Oil Pres LowLow Oil Pressure — The engine ECM indicates low oil pressure. Note: The low oil pressure shutdown does not protect against low oil level. Check the engine oil level regularly as recommended in Section 4.Check for leaks in the lubrication system.; Check the oil level and add oil if the level is low.; Check the oil pressure switch and wiring.Kohler 24RCL, Kohler 30RCL, Kohler 38RCLB
Oil Pressure Low ShutdwnThe low oil pressure switch was closed for 5 seconds or more, indicating low oil pressure. Function is inhibited until 30 seconds after crank disconnectCheck for oil leaks; Check the oil level and add oil if low; Check the oil pressure sensor; see Engine Service ManualsKohler 14RCA, Kohler 20RCA, Kohler RCA
Oil Pressure Low ShutdwnOil Pressure Low Shutdwn — Shutdown: The low oil pressure switch was closed for 5 seconds or more, indicating low oil pressure. Function is inhibited until 30 seconds after crank disconnect.Check for oil leaks; Check the oil level and add oil if low; Check the oil pressure sensor; see Engine Service Manuals.Kohler 24VDC, Kohler 36VDC, Kohler 48VDC, Kohler 6VSG, Kohler 6VSG-24V, Kohler 6VSG-36V
Oil Pressure OpenCR WarningOil pressure switch closure has not been detected after shutdownCheck the oil pressure switch connection. Test the LOP switch as described in Section 6.10.2Kohler 14RCA, Kohler 20RCA, Kohler RCA
Oil Pressure OpenCR WarningOil Pressure OpenCR Warning — Warning: When the generator set is not running and controller is in OFF or AUTO, the low oil pressure switch is not working properly.Check the oil pressure switch connection; Replace the LOP switch if necessary. See Section 5.7.2.Kohler 24VDC, Kohler 36VDC, Kohler 48VDC, Kohler 6VSG, Kohler 6VSG-24V, Kohler 6VSG-36V
ON and Not BlinkingGovernor controller is powered and is malfunctioningReplace governor controller.Kohler Basic, Kohler Digital, Kohler Digital 550, Kohler Microprocessor-Plus, 16-Light
OSOverspeed shutdown — Shutdown occurs if the engine speed exceeds 110% of the normal running speed for more than 0.3 seconds.OverspeedContact an authorized distributor/dealer for service if problem continues.Kohler 10/13/15ERG, Kohler 10ERG, Kohler 10RFOY, Kohler 10ROY, Kohler 12RES, Kohler 12TRES
OUOvervoltage shutdown — Shutdown occurs if the voltage exceeds 120% of the system nominal voltage for more than 2 seconds.OvervoltageContact an authorized distributor/dealer for service.Kohler 10/13/15ERG, Kohler 10ERG, Kohler 12RES, Kohler 12TRES, Kohler 13ERG, Kohler 15ERG
Over CrankOver Crank — Three unsuccessful starting attempts.Check the fuel supply, spark plug, and battery.; Check for loose connections.; Contact an authorized distributor/dealer for service.Kohler 24RCL, Kohler 30RCL, Kohler 38RCLB
Over Crank ShutdwnThe engine did not start during the crank cycle. Time delay is 15 seconds. If noted on the first engine crank cycle, an alternator issue may be indicatedCheck the alternator; see Section 6 for alternator test procedures; Check fuel supply. Check cranking circuit. Check cranking battery. Troubleshoot engine; see Engine Service ManualsKohler 14RCA, Kohler 20RCA, Kohler RCA
Over Crank ShutdwnOver Crank Shutdwn — Shutdown: The controller shut down the generator, and ceased cranking, because the engine was not successfully started after the completion of the last of the crank cycles setting delay 15 seconds.Check fuel supply; Check cranking circuit; Check cranking battery; Troubleshoot engine; see Engine Service Manuals.Kohler 24VDC, Kohler 36VDC, Kohler 48VDC, Kohler 6VSG, Kohler 6VSG-24V, Kohler 6VSG-36V
Over/under frequencyOver/under frequencyKohler 25EFOZD, Kohler 28EFOZD, Kohler 28EOZ, Kohler 32EOZ, Kohler G2
Over/under frequencyFrequency deviates from nominal valueKohler 10ERG
Over/under voltageOver/under voltageKohler 25EFOZD, Kohler 28EFOZD, Kohler 28EOZ, Kohler 32EOZ, Kohler G2
Over/under voltageVoltage is outside the normal rangeKohler 10ERG
OvercrankRemote two-wire start/stop capabilityKohler 10-18RY/RZ, Kohler 12RES, Kohler 18RES, Kohler 6.5RMY, Kohler TP-5631
OvercrankSystem shuts down on an overcrank fault if the generator set does not start in three attemptsReset the controller. If the overcrank fault occurs again, contact an authorized distributor/dealerKohler 14/20RESA/RESAL, Kohler 20 kW Models, Kohler 20RESC/RESCL, Kohler Model RESA/L or RESC/L, Kohler RDC2
Overcrank safetyOverspeedKohler 25EFOZD, Kohler 28EFOZD, Kohler 28EOZ, Kohler 32EOZ, Kohler G2
Overcrank safetyExcessive cranking durationKohler 10ERG
Overcrank safetyOvercrank safetyKohler 25EFOZD, Kohler 28EFOZD, Kohler 28EOZ, Kohler 32EOZ
OverfrequencyDigital voltage regulation: ±1.5% RMS no-load to full-loadKohler 12RES, Kohler 18RES
OverspeedAutomatic start for programmed cranking cycleKohler 10-18RY/RZ, Kohler 12RES, Kohler 18RES, Kohler 25EFOZD, Kohler 28EFOZD, Kohler 28EOZ
OverspeedEngine speed exceeds safe limitsKohler 10ERG
P3-4SDR RelayKohler 4.5 CKM
P26Fuel Pump/ValveKohler 4.5 CKM
P0107TMAP circuit malfunctionCheck continuity of wiring and connections, replace faulty components if necessaryKohler ECH940, Kohler ECH980
P0108TMAP circuit malfunctionCheck continuity of wiring and connections, replace faulty components if necessaryKohler ECH940, Kohler ECH980
P0122Low voltage condition on TPS circuitKohler ECH940, Kohler ECH980
P0123High voltage condition on TPS circuitKohler ECH940, Kohler ECH980
PrimLoopOpnPrimary Loop Open — Ignition coil 1 voltage is below normal or there is an open circuit.Check the battery voltage.; Contact an authorized distributor/dealer for service and provide the fault code.Kohler 24RCL, Kohler 30RCL, Kohler 38RCLB
PrimLoopShtPrimary Loop Shorted — Ignition coil 1 voltage is abnormal.Check the battery voltage.; Contact an authorized distributor/dealer for service and provide the fault code.Kohler 24RCL, Kohler 30RCL, Kohler 38RCLB
ProtectiveRelayTrippedContactorThe contactor has been forced to open to protect one of the generators or the customer's loadKohler 14/20RESA/RESAL, Kohler 14RCA, Kohler 20 kW Models, Kohler 20RCA, Kohler 20RESC/RESCL, Kohler Model RESA/L or RESC/L
RWater Temperature IndicatorKohler STTII-52V-25CH-LP-EFI, Kohler STTII-52V-26CH-EFI, Kohler STTII-52V-31BV, Kohler STTII-61V-25CH-LP-EFI, Kohler STTII-61V-25KBD, Kohler STTII-61V-31BV
RBUS ComError WarningThe controller has lost communication with an RBUS device that had previously been communicating properlyCheck connection to the RBUS deviceKohler 14RCA, Kohler 20RCA, Kohler RCA
RBUS ComError WarningRBUS ComError Warning — Warning: The controller has lost communications with a PIM that had previously been communicating properly.Check connection to the PIM.Kohler 24VDC, Kohler 36VDC, Kohler 48VDC, Kohler 6VSG, Kohler 6VSG-24V, Kohler 6VSG-36V
Reactive Power Low WarningLoss of FieldKohler 14/20RESA/RESAL, Kohler 14RCA, Kohler 14RCA/14RCAL, Kohler 18RCAL, Kohler 20 kW Models, Kohler 20RCA
Real Power High WarningOver PowerKohler 14/20RESA/RESAL, Kohler 14RCA, Kohler 14RCA/14RCAL, Kohler 18RCAL, Kohler 20 kW Models, Kohler 20RCA
Real Power Low WarningReverse PowerKohler 14/20RESA/RESAL, Kohler 14RCA, Kohler 14RCA/14RCAL, Kohler 18RCAL, Kohler 20 kW Models, Kohler 20RCA
Reserve Oil EmptyReserve Oil Empty — Warning: The oil makeup kit reservoir bottle is empty. (Optional communications kit and oil makeup kit required.)Add oil to the oil makeup kit reservoir. See TT-1591, provided with the oil makeup kit, if necessary.Kohler 24VDC, Kohler 36VDC, Kohler 48VDC, Kohler 6VSG, Kohler 6VSG-24V, Kohler 6VSG-36V
Rmt StartCmdRemote Start Command Issued — Notice: The controller has received a remote start signal while the master switch is in AUTO, and will go to normal running.Verify remote start signal.Kohler 24VDC, Kohler 36VDC, Kohler 48VDC, Kohler 6VSG, Kohler 6VSG-24V, Kohler 6VSG-36V
RUNRUNKohler FR II, Kohler FR1, Kohler G-292806
Run Btn AckRun Button Acknowledged — Notice: The RUN button on the controller has been pushed.Kohler 24VDC, Kohler 36VDC, Kohler 48VDC, Kohler 6VSG, Kohler 6VSG-24V, Kohler 6VSG-36V
SCF0Software Communication Fault 0 — Indicates a software or communication problem within the ADC 2100Software or communication problem within the ADC 2100Replace the controller. Contact an authorized distributor/dealer for service.Kohler 12RES, Kohler 12TRES, Kohler 15RES, Kohler 15REYG, Kohler 30RES, Kohler 30REYG
SCF0Controller error — Indicates a software or communication problem within the ADC 2100Contact an authorized distributor/dealer for service if problem continues.Kohler 10/13/15ERG, Kohler 10ERG, Kohler 13ERG, Kohler 15ERG, Kohler TP-6334
SDROverspeed ShutdownDeenergize engine componentsKohler 10C, Kohler 10CC, 12CC Mobile Generator Set, Kohler 10CFC, Kohler 10CFZ, Kohler 10CZ, 12CZ Mobile Generator Set, Kohler 12C
Seawater pump impeller failureSeawater pump impeller failure shutdownKohler G2
SL001Check coolant levelKohler KD36V16
SL003Check the ventilation holes on the water pumpKohler KD36V16
SL004Check/drain water trap on the primary fuel filterKohler KD36V16
SL100Take oil sample and perform oil analysisKohler KD36V16
SL105Replace main fuel filterKohler KD36V16
SL106Replace the primary fuel filterKohler KD36V16
SL107Replace the oil separator filter insert of the crankcase breatherKohler KD36V16
SL108Change air filter main elementKohler KD36V16
SL109Check and change the V-ribbed belt for the battery charging alternatorKohler KD36V16
SL118Check state of fan drive belt drive and replace if necessaryKohler KD36V16
SL120Take coolant sample and perform coolant analysisKohler KD36V16
SL121Replace diesel engine oil and oil filterKohler KD36V16
SOS 010General fault — pressing the "STOP" button when the external command is active ("AUT" pictogram flashing) will stop the generating set immediately in general fault mode (the general fault LED will light up flashing and the SOS 010 fault code appears)Kohler DEC 1000
Spd Sens FltSpeed Sensor Fault — Engine speed sensor has failed or engine stalled. ECM is no longer reporting valid speed.Contact an authorized distributor/dealer for service.Kohler 24RCL, Kohler 30RCL, Kohler 38RCLB
Spd Sens Flt ShutdwnSpeed sensor fault — The controller shut down the generator because the speed signal was lostCheck leads 55, 66, F+, and F- between the alternator and the controller. This fault also occurs if the engine stalls; check the engine and see the troubleshooting chart in Section 5.14Kohler 14RCA, Kohler 20RCA, Kohler 24VDC, Kohler 36VDC, Kohler 48VDC, Kohler 6VSG
SQChoke Will Not Fully Open1. Adjust choke. 2. Repair with kit or replace choke.Kohler KT17, Kohler KT17 Series II, Kohler KT19, Kohler KT19 Series II, Kohler KT21
Start DelayEngine Start Delay Active — Notice: The digital output for Engine Start Delay (PIM) is active (contacts closed), indicating the engine is in between active cranking cycles.Kohler 24VDC, Kohler 36VDC, Kohler 48VDC, Kohler 6VSG, Kohler 6VSG-24V, Kohler 6VSG-36V
SyncFailureThe generator has been attempting to synchronize for over 2 minutes without success.Generator is hunting. Advanced speed control settings need adjustment. Load is changing frequently to disturb the online generator.Kohler 14/20RESA/RESAL, Kohler 14RCA, Kohler 14RCA/14RCAL, Kohler 14RCA/L, Kohler 18RCAL, Kohler 20 kW Models
SynchronizingThe generator is actively trying to match frequency, voltage and phase with that of the paralleling busKohler 14/20RESA/RESAL, Kohler 14RCA, Kohler 20 kW Models, Kohler 20RCA, Kohler 20RESC/RESCL, Kohler Model RESA/L or RESC/L
System ReadySystem Ready — Notice: The digital output for System Ready (PIM) is active (contacts closed), indicating the generator has no active faults or warnings.Kohler 24VDC, Kohler 36VDC, Kohler 48VDC, Kohler 6VSG, Kohler 6VSG-24V, Kohler 6VSG-36V
TestTestKohler Series S340
TP-5393Will not crankWeak or dead battery, 15-amp controller fuse blown, Defective start switch, Remote start cable disconnected, Defective starter solenoid, Battery connections made in reverseRecharge or replace, Replace fuse, Replace, Reconnect, Replace, CorrectKohler 4 and 5 kW, Kohler 4CFKM, Kohler 4CFKM/CFKMR, Kohler 4CKM, Kohler 4CKM/CKMR, Kohler 5CKM
TP-6905 4/16Generator set serial number is unavailable.Contact an authorized distributor/dealer for service. See section 3.11.Kohler 24RCL, Kohler 30RCL, Kohler 38RCLB
TP-7092Engine starting battery is deadCheck and clean the battery, terminals, cables. If necessary, recharge or replace the battery.Kohler 14RCA, Kohler 20RCA
TP-7092Loose connectionsTighten all loose connectionsKohler 14RCA, Kohler 20RCA
TP-7092Open circuit breakerCheck and close any open circuit breakersKohler 14RCA, Kohler 20RCA
TP-7092The controller displays fault messagesKohler 14RCA, Kohler 20RCA
UFUnderfrequency shutdown — Shutdown occurs if the governed frequency falls below 54 Hz for more than 5 seconds. Shutdown also occurs if the governed frequency falls below 56.5 Hz for more than 60 seconds. This protective becomes active 10 seconds after engine start. (10 second inhibit).UnderfrequencyReduce the load and restart the generator set.; Contact an authorized distributor/dealer for service if problem continues.Kohler 10/13/15ERG, Kohler 10ERG, Kohler 12RES, Kohler 12TRES, Kohler 13ERG, Kohler 15ERG
UnderfrequencyMaster control switch mounted on the junction box: Run/Off-Reset/AutoKohler 12RES, Kohler 18RES
UndervoltageUpgradeable application softwareKohler 12RES, Kohler 18RES
UnloadingThe generator is actively trying to transfer load from itself to the other generatorKohler 14/20RESA/RESAL, Kohler 14RCA, Kohler 20 kW Models, Kohler 20RCA, Kohler 20RESC/RESCL, Kohler Model RESA/L or RESC/L
UUUndervoltage shutdown — Shutdown occurs if the voltage falls below 80% of the nominal system voltage for more than 10 seconds.UndervoltageReduce the load and restart the generator set.; Contact an authorized distributor/dealer for service if problem continues.Kohler 10/13/15ERG, Kohler 10ERG, Kohler 12RES, Kohler 12TRES, Kohler 13ERG, Kohler 15ERG
V7Fuse V7 on the AC terminal block (TB2) protects the controller meters and lightsIf the controller lights and meters are not functioning, check the condition of the V7, V8, and V9 fusesReplace fuseKohler 10-18RY/RZ, Kohler 6.5RMY, Kohler TP-5631
V8Fuse V8 on the AC terminal block (TB2) protects the controller meters and lightsIf the controller lights and meters are not functioning, check the condition of the V7, V8, and V9 fusesReplace fuseKohler 10-18RY/RZ, Kohler 6.5RMY, Kohler TP-5631
V9Fuse V9 on the AC terminal block (TB2) protects the controller meters and lightsIf the controller lights and meters are not functioning, check the condition of the V7, V8, and V9 fusesReplace fuseKohler 10-18RY/RZ, Kohler 6.5RMY, Kohler TP-5631
Voltage L1-L2 High WarningOver VoltageKohler 14/20RESA/RESAL, Kohler 14RCA, Kohler 14RCA/14RCAL, Kohler 18RCAL, Kohler 20 kW Models, Kohler 20RCA
Voltage L1-L2 Low WarningUnder VoltageKohler 14/20RESA/RESAL, Kohler 14RCA, Kohler 14RCA/14RCAL, Kohler 18RCAL, Kohler 20 kW Models, Kohler 20RCA
Volts L1-L2Generator voltage high. Output voltage exceeds 120% of the system nominal voltage for more than 2 seconds.Contact an authorized distributor/dealer for service.Kohler 14RCA/L, Kohler 20RCA, Kohler 20RCA/L, Kohler RDC2 Controller
Volts L1-L2 (AB) High ShutdwnThe controller shut down the generator because the voltage measured from Phase A to Phase B exceeded the high limit for a time greater than the delay setting 2 secondsTroubleshoot alternator. See Section 5.14, Troubleshooting Charts, and Section 6, Component Testing and AdjustmentKohler 14RCA, Kohler 20RCA, Kohler RCA
Volts L1-L2 (AB) Low ShutdwnThe controller shut down the generator because the voltage measured from Phase A to Phase B was greater 5% of rated, but less than the low voltage setting for a time greater than the delay setting 10 secondsThe enclosure thermostat has trippedTroubleshoot alternator. See Section 5.14, Troubleshooting Charts, and Section 6, Component Testing and Adjustment; Check for evidence of high temperatures inside the enclosure. Reset the thermostat. See Section 5.8Kohler 14RCA, Kohler 20RCA, Kohler RCA
Volts L1-L2 DC High ShutdwnVolts L1-L2 DC High Shutdwn — Shutdown: The controller shut down the generator because the voltage measured from Phase A to Phase B exceeded the high limit for a time greater than the delay setting 2 seconds.Troubleshoot alternator. See Section 4.9, Troubleshooting Charts, and Section 5, Component Testing and Adjustment.Kohler 24VDC, Kohler 36VDC, Kohler 48VDC, Kohler 6VSG, Kohler 6VSG-24V, Kohler 6VSG-36V
Volts L1-L2 HighHigh Generator Voltage L1-L2 — Generator Voltage High. Output voltage exceeds 120% of the system nominal voltage for more than 2 seconds.Contact an authorized distributor/dealer for service.Kohler 24RCL, Kohler 30RCL, Kohler 38RCLB
Volts L1-L2 LowLow Generator Voltage L1-L2 — Generator Voltage Low. Output voltage falls below 80% of the nominal system voltage for more than 10 seconds.Reduce the load by turning off appliances and restart the generator set.; Contact an authorized distributor/dealer for service.Kohler 24RCL, Kohler 30RCL, Kohler 38RCLB
Volts L2-L3 HighHigh Generator Voltage L2-L3 — Generator Voltage High. Output voltage exceeds 120% of the system nominal voltage for more than 2 seconds.Contact an authorized distributor/dealer for service.Kohler 24RCL, Kohler 30RCL, Kohler 38RCLB
Volts L2-L3 LowLow Generator Voltage L2-L3 — Generator Voltage Low. Output voltage falls below 80% of the nominal system voltage for more than 10 seconds.Reduce the load by turning off appliances and restart the generator set.; Contact an authorized distributor/dealer for service.Kohler 24RCL, Kohler 30RCL, Kohler 38RCLB
Volts L3-L1 HighHigh Generator Voltage L3-L1 — Generator Voltage High. Output voltage exceeds 120% of the system nominal voltage for more than 2 seconds.Contact an authorized distributor/dealer for service.Kohler 24RCL, Kohler 30RCL, Kohler 38RCLB
Volts L3-L1 LowLow Generator Voltage L3-L1 — Generator Voltage Low. Output voltage falls below 80% of the nominal system voltage for more than 10 seconds.Reduce the load by turning off appliances and restart the generator set.; Contact an authorized distributor/dealer for service.Kohler 24RCL, Kohler 30RCL, Kohler 38RCLB
VSpdStartCmdVariable Speed Start Command — Notice: A diagnostic exercise request has been received by the controller.Check for a remote exercise command from OnCue.Kohler 24VDC, Kohler 36VDC, Kohler 48VDC, Kohler 6VSG, Kohler 6VSG-24V, Kohler 6VSG-36V

Compiled from Kohler service manuals and controller documentation. 69 code numbers mean different things on different controllers; each meaning is listed with the models it applies to. Cause/remedy shown where extracted; always verify against the manual for your exact model.

Common questions

What does Kohler fault code 010 mean?

The generating set stops immediately when pressing the emergency stop button.. Remedy: Acknowledge (reset) the fault by moving the key switch to OFF, waiting for the 'ON' LED to go out completely and then moving the key switch to ON..

What does Kohler fault code 21 mean?

Engine Speed Synchronization — Loss of synchronization. Cause: Engine speed sensor related: sensor connector or wiring; sensor loose or air gap incorrect; speed sensor wheel related: damaged teeth, gap section not registering; engine wiring harness related: pin circuit wiring or connectors (pins 3 and/or 21 for "35 Pin" MA 1.7 Metal-Cased ECU; pins 9 and/or 10 for "24 Pin" MSE 1.0 Plastic-Cased ECU; pins 9 and/or 10 for "32 Pin" MSE 1.1 Plastic-Cased ECU); ECU/harness related: ECU-to-harness connection problem.