HomeKohlerKohler 60RCL

Kohler 60RCL Generator Set

The Kohler 60RCL is a 60 kW (75 kVA) LPG/Natural Gas standby generator set powered by a General Motors Industrial Powertrain Vortec 5.7 L engine. It is available at 240 V, single-phase and 60 Hz. It holds about 4.7 L (1.2 gal) of oil and 22.5 L (5.9 gal) of coolant. The same Industrial Powertrain Vortec 5.7 L engine also powers generator sets from SDMO.

60 kW
Standby
5.7 L
Displacement
4.7 L
Oil capacity
6
Document types

How to read your Kohler serial & model number →

Typical fuel consumption for 60–65 kW Bi-Fuel (NG/LP) generators →

Compare with other 60–65 kW Bi-Fuel (NG/LP) generators →

Service parts for the 60RCL

Grouped by system, with how many of each the parts manual calls for.

Air intake

1 required

Oil system

1 required

Belts

1 required

Prices captured from merchant listings; some links are affiliate links. Confirm against your serial number before ordering.

Specifications

FuelLPG/Natural Gas
Frequency60.0 Hz
Standby power60 kW
Standby kVA75
EmissionsEPA NSPS
ControllerRDC2
Oil capacity4.7 L
Alternator4P10X
Voltage options240 V
PhaseSingle
Battery voltage12 V
Battery quantity1

Engine

General Motors Industrial Powertrain Vortec 5.7 L
Oil capacity6.2 L
Coolant capacity22.5 L
Displacement5.7 L
AspirationTurbocharged
Rated speed1800 rpm

Maintenance & consumables

for the General Motors Industrial Powertrain Vortec 5.7 L
ItemSpecCapacityPart #Interval
Air filterA--2736991000 hr Amazon Amazon eBay eBay
Oil filterFilter, oilGM16703 Amazon $9.06 eBay $58.00
BeltBelt, fan standardGM16132 Amazon eBay $86.00
CoolantLong-life coolant recommended; when used, change interval is 5000 hours or 5 years; do not mix coolant types5000 hr
Oil6.2 L100 hr

Service intervals

10
ItemActionHoursMonthsNotes
Engine oil levelCheck24 hrCheck the oil level in the crankcase every 24 hours of operation or before the engine is started each day
Air cleaner elementInspect100 hr
Change engine oil and filterChange100 hr
Check all bolts and nuts for tightnessCheck100 hr
Air cleaner elementReplace1000 hr
Belts and belt tensionCheck1000 hr
Engine coolantReplace5000 hr60 moWhen long-life coolant used
Check coolant levelCheck0 mo
Check engine oil levelCheck0 mo
Check for fluid leaksCheck0 mo

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Service specifications

12
TypeItemValueUnitCondition
GapSpark plug gap0.51mm (0.02 in.)
GapSpark plug gap0.7--0.8mm (0.028--0.030 in.)
GapSpark plug gap0.76mm (0.03 in.)
GapSpark plug gap0.8--0.9mm (0.03--0.04 in.)
GapSpark plug gap0.89mm (0.035 in.)
GapSpark plug gap0.9--1.0mm (0.036--0.04 in.)
TemperatureBlock heater thermostat cut-off temperature27--38°Ccoolant temperature
TemperatureBlock heater thermostat cut-off temperature80--100°Fcoolant temperature
TorqueSpark plug torque15Nm (11 ft. lb.)
TorqueSpark plug torque18Nm (13.3 ft. lb.)
TorqueSpark plug torque24.4--29.8Nm (18--22 ft. lb.)
TorqueSpark plug torque25Nm (18 ft. lb.)

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Recommended fluids

FluidGradeStandardAmbientCapacityNotes
Coolant50% ethylene glycol0.6 LProvides freezing protection to --37_C (--34_F) and overheating protection to 129_C (265_F). Do not use alcohol or methanol antifreeze. Coolant added after block heater installation is approximately 0.6 L (0.2 gal).
CoolantLong-life coolantChange interval 5000 hours or 5 years when long-life coolant used; do not mix coolant types
Engine oilSAE 5W-30API Starburst (for gasoline engines)below -18°C4.7 LFor below -18C (0F)
Engine oilSAE 10W-30API Starburst (for gasoline engines)above -18°C4.7 LFor -18C (0F) and above; CC/CD classification and straight-weight industrial/stationary oils not acceptable

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Fault codes

27
CodeNameMeaningSeverityAction
AC Sens LostAC Sensing LostIn Auto mode, generator output AC sensing is lost; starts 10 seconds after crank disconnect. Warning after 1 second if no output detected after crank disconnect; shutdown after 3 seconds if voltage was present and then lost.WarningContact an authorized distributor/dealer for service.
ATS Com ErrorATS Communication ErrorWarning is displayed if RXT interface connection is lost.WarningCheck communication wiring between transfer switch interface board and generator set.
ATS PhaseRotATS Phase Rotation MismatchTransfer switch phase rotation does not match; ATS will not transfer.WarningCorrect the ATS connection per the ATS Installation manual, wiring diagrams, and labels on the transfer switch.
Accy PwrOverAccessory Power OverloadOver current fault on the accessory controller power outputWarning
Accy PwrOver WarningAccessory Power OverloadAn over current fault (short circuit) on the accessory controller power output.WarningContact an authorized distributor/dealer for service.
Alt Protect ShtdwnAlternator Protection ShutdownHigh generator current detected; shuts down to protect alternator windings from overheating (38RCL only).ShutdownReduce the load.
Aux InputAuxiliary InputAn optional customer-connected input is closed (digital input from optional PIM).ShutdownCheck customer-supplied equipment.
Batt Chg FltBattery Charger FaultInput to PIM from an external battery charger (not the built-in charger).WarningCheck external battery charger.
Battery Voltage HighBattery Voltage HighEngine starting battery voltage rises above 125% of the battery voltage setting for more than 10 seconds; inhibited during crank cycle.WarningCheck the battery rating and condition; check the battery charger operation.
Battery Voltage LowBattery Voltage LowEngine starting battery voltage falls below the battery voltage setting (typically 12.5 volts) for more than 90 seconds when engine not running; inhibited during crank cycle.WarningCheck the battery rating and condition; check the battery charger operation; charge or replace the battery.
CAN comm faultCAN Communications FaultEngine CAN communications fault.ShutdownCheck wiring to ECM; check power to ECM.
Engine Coolant Temperature HighEngine Coolant Temperature HighEngine coolant temperature exceeds the maximum temperature for more than 5 seconds; active after crank disconnect.ShutdownCheck for blocked air inlets and exhaust outlets.
Engine Oil Pressure LowEngine Oil Pressure LowThe engine ECM indicates low oil pressure for more than 5 secondsShutdownCheck for leaks in the lubrication system; check the oil level and add oil if low.
EngineSpeed HighEngine Speed HighEngine speed exceeds 115% of normal running speed for more than 0.3 seconds.ShutdownContact an authorized distributor/dealer for service.
EngineSpeed LowEngine Speed LowEngine speed drops below 85% of normal running speed for more than 3 seconds.ShutdownReduce the load; contact an authorized distributor/dealer for service.
Exer Not SchExercise Not ScheduledNo exercise has been scheduled on the RDC2 controller.WarningSee exerciser setup instructions.
Generator Frequency HighGenerator Frequency HighGoverned frequency exceeds 110% of the system's frequency setpoint for more than 10 seconds; active 10 seconds after engine start.ShutdownContact an authorized distributor/dealer for service.
Generator Frequency LowGenerator Frequency LowGoverned frequency falls below 90% of system frequency setting for more than 10 seconds, or 1 Hz below setting for more than 60 seconds; active 10 seconds after engine start.ShutdownReduce the load and restart the generator set; contact an authorized distributor/dealer for service.
Generator VoltageL1-L2 HighGenerator Voltage HighOutput voltage exceeds 120% of the system nominal voltage for more than 2 seconds.ShutdownContact an authorized distributor/dealer for service.
Generator VoltageL1-L2 LowGenerator Voltage LowOutput voltage falls below 80% of the nominal system voltage for more than 10 seconds.ShutdownReduce the load and restart the generator set; contact an authorized distributor/dealer for service.
Lo Crank VltLow Cranking VoltageBattery voltage falls below 60% of system battery voltage for more than 6 seconds while the starter is engaged.WarningCharge or replace the battery.
Locked RotorLocked RotorNo engine rotation is sensed during cranking; shuts down 3 seconds after the fault is detected.ShutdownCheck the battery; check for loose connections; contact an authorized distributor/dealer for service.
MainPwrOverL ShutdownMain Power OverloadAn over current fault on the controller power output (short circuit).ShutdownContact an authorized distributor/dealer for service.
Not in AutoNot in Automatic ModeThe generator set is not in Automatic (standby) mode; remote start/stop commands from a transfer switch or remote switch will be ignored.WarningPress AUTO to place the generator set in Automatic mode, when appropriate.
Over CrankOver CrankThree unsuccessful starting attempts.ShutdownCheck the fuel supply, spark plug, and battery; check for loose connections; contact an authorized distributor/dealer for service.
Speed Sensor FaultSpeed Sensor FaultEngine speed sensor has failed or engine stalled.ShutdownContact an authorized distributor/dealer for service.
Total Power High ShtDwnTotal Power High ShutdownMeasured load is greater than 102% of the generator set power rating for more than 1 minute (38RCL only).ShutdownReduce the load.

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Procedures

12
RDC2 Voltage Calibration Using SiteTech adjustment

Tools: digital voltmeter, personal computer, SiteTech software

  1. Connect PC to controller via USB
  2. With generator off, connect multimeter across L1/L2 (AC volts)
  3. Start generator set
  4. Compare voltmeter reading to controller display
  5. Calculate new Genset Calibration Factor Voltage using (Vmeter / Vcontrol) x Fold = Fnew
  6. Enter new value into SiteTech and click Apply Changes
  7. Verify voltmeter matches controller display
  8. Repeat for L2-L3 and L3-L1 if three-phase
  9. Press OFF to stop generator set
RDC2 Voltage Calibration Using the Controller Keypad adjustment

Tools: digital voltmeter

  1. With generator off, connect digital multimeter across L1 and L2, set to AC volts
  2. Start generator set with RUN button
  3. Navigate to Generator Metering menu, press Select; Volts L1-L2 displayed
  4. Press Select; voltage number flashes
  5. Use up/down arrows to match voltmeter reading
  6. Press Select to confirm
  7. Step to Return screen
  8. Press OFF to stop generator set
VSC Current (Load) Calibration Using the Controller Keypad adjustment

Tools: clamp-on DC current probe or DC current meter

  1. Connect DC current probe/clamp meter to measure generator current
  2. Start generator with RUN button
  3. Adjust system voltage to obtain rated current output with battery bank attached (or use load bank)
  4. Trip output breaker
  5. Navigate to Generator Metering menu, select Generator Load
  6. Press and hold Select for No-Load Calibration; verify breaker open, confirm Yes
  7. Close output breaker; verify rated output current, confirm Yes
  8. Verify displayed load is correct; recalibrate if necessary
  9. Press OFF to stop generator set
Procedure to Reset the Controller after a Fault Shutdown diagnostic

⚠ Always identify and correct the cause of a fault shutdown before resetting the controller.

  1. Press the Select button to go to the Overview menu.
  2. Press Select again to display the active fault.
  3. Press Select; Confirm Clear Fault: NO is displayed.
  4. Press the Up arrow button; Confirm Clear Fault: YES is displayed.
  5. Press the Select button to enter YES and clear the fault.
  6. Press the Select button to return to the overview menu.
  7. Press AUTO to put the generator set into automatic mode.
Install the block heater installation

⚠ Block heater damage. The block heater will fail if the energized heater element is not immersed in coolant. Fill the cooling system before turning on the block heater.

⚠ Do not add coolant to a hot engine. Wait until the engine has cooled.

⚠ Hot coolant and steam. Stop the generator set and allow it to cool before removing the pressure cap.

Tools: pipe sealant, cable tie

  1. Secure the block heater to the block heater mounting bracket (GM78546) using 4 screws (M933-06020-60), 4 washers (M125A-06-80), and 4 hex nuts (M6923-06-80).
  2. Secure the mounting bracket with block heater to the skid using 2 screws (M933-06016-60) and 2 hex nuts (M6923-06-80).
  3. Locate the 2 shutoff valves on opposite sides of the engine block and verify they are closed.
  4. Remove the pipe plug from each shutoff valve and discard the plugs.
  5. Apply pipe sealant to the threads of hose connectors X-391-19 and X-582-1.
  6. Install the 90 degree hose connector (X-391-19) in the shutoff valve closest to the block heater.
  7. Install the straight connector (X-582-1) in the shutoff valve on the opposite side of the engine.
  8. Hold the molded hose (276206 or GM103656) in place and cut to fit if necessary.
  9. Install the shorter heat shield (GM17809) over the molded hose and secure with a cable tie.
  10. Connect the molded hose to the hose connector and secure with a hose clamp (X-426-12 or GM103203).
  11. Connect the other end of the hose to the block heater outlet and secure with a hose clamp (X-426-12 or GM103203).
  12. Install the longer heat shield (GM23718) over the inlet hose (X-312-53 or X-312-47) and secure with a cable tie.
  13. Connect the hose to the block heater inlet with a hose clamp (X-426-12); route the hose under the engine.
  14. Secure the hang tag (279047) to the power cord.
  15. Open the two block heater shutoff valves and, after the block heater is full, add approximately 0.6 L (0.2 gal) coolant to the cooling system.
Air Cleaner Element and Precleaner maintenance
  1. Disable set: press OFF button, disconnect battery charger power, remove battery cables, negative (--) lead first.
  2. Loosen the cover retaining knob(s) or release the retaining clips and remove the cover.
  3. Remove and discard the old air cleaner element and precleaner (if equipped).
  4. Install the precleaner over the new air cleaner element.
  5. Install the paper element onto the air cleaner base, making sure it is flat and properly seated.
  6. Reinstall the element cover, element cover nut, and the air cleaner cover; secure with the knob(s) or clips.
  7. 15RES/30RES and RCL models: wipe cover and housing with a clean rag and make sure sealing surfaces fit correctly.
  8. Reconnect the battery cable, negative (--) lead last.
Air Cleaner Service Procedure maintenance

⚠ Do not clean the element in any liquid or use compressed air; this will damage the filter element.

  1. Remove the cover from the air cleaner housing.
  2. Remove the air cleaner element.
  3. Examine the element and housing for damage; replace if damaged.
  4. Tap the element lightly against a flat surface to dislodge loose surface dirt.
  5. Wipe the cover and housing with a clean rag to remove dirt.
  6. Replace the air cleaner cover.
Firmware Update Using SiteTech maintenance

⚠ Do not load RDC2.4 firmware onto a red- or green-board controller

Tools: personal computer, USB cable, SiteTech software

  1. Download latest firmware file (.bin) from Kohler Power Resource Center or dealer portal
  2. Connect controller to PC via USB cable
  3. Start SiteTech; program recognizes connected device
  4. Click Update Firmware
  5. Browse to and select firmware file, click Open
  6. Verify current/new version and file name, click Update Firmware
  7. Wait for 'Firmware Updated Successfully' message, click Close
Oil and Filter Change maintenance

⚠ Dispose of waste materials (oil, fuel, filter) in an environmentally safe manner.

Tools: oil filter wrench, drain hose

  1. Press the OFF button on the RDC2 generator set controller.
  2. Disconnect the power for the battery charger.
  3. Disconnect the generator set engine starting battery, negative lead first.
  4. Remove the housing side panel.
  5. Remove the plug from the oil drain fitting and install a drain hose.
  6. Open the oil drain valve on the engine and allow oil to drain completely.
  7. Close the oil drain valve and replace the oil drain plug.
  8. Remove the oil filter by rotating counterclockwise with an oil filter wrench.
  9. Clean the contact surface of the oil filter adapter; apply light coat of clean oil to new filter's rubber seal.
  10. Install the new oil filter.
  11. Fill with oil per oil selection chart and capacity (4.7 L / 5.0 qt).
  12. Reconnect the battery negative lead last and reconnect battery charger power.
  13. Start the generator set and check for leaks around the oil filter; tighten if necessary.
  14. Stop the generator set, check oil level, and add oil to bring to the Full mark.
  15. Reset the maintenance timer on the RDC2 controller.
Oil and Oil Filter maintenance

⚠ Hot engine oil can cause severe injury or death. Avoid skin contact with hot oil.

⚠ Do not work on the generator set until it cools.

⚠ Accidental starting can cause severe injury or death. Remove the negative (--) lead first when disconnecting the battery.

Tools: Funnel, Drain tube (3/8 in. inside diameter), Catch basin / drain pan

  1. Disable set: press OFF button, disconnect battery charger power, remove battery cables, negative (--) lead first.
  2. Drain the oil while it is warm. On most models a drain plug is on the service side, opposite the starter.
  3. For most models remove one oil drain plug and the oil fill cap/dipstick; aim the drain tube into a catch basin.
  4. For most models open the valve near the oil sump and allow ample time for complete drainage.
  5. Close the valve and place the tube back in the clip on the bulkhead wall.
  6. For 8/10/12RESV(L), cover the alternator with rags near the oil drain valve and oil filter.
  7. For 8/10/12RESV(L), place a drain tube (3/8 in. inside diameter) onto the oil drain valve into a drain pan.
  8. For 8/10/12RESV(L), open the oil drain valve, remove the dipstick and oil fill cap, and drain completely.
  9. For 8/10/12RESV(L), close the oil drain valve and remove the oil drain tube.
  10. Remove the old filter, tilting it upward to prevent spilling, and wipe off the adapter/base on the engine.
  11. Place a new replacement filter open end up in a shallow pan; pour new oil (provided) through the threaded center hole to the bottom of threads.
  12. Allow a minute or two for the oil to be absorbed by the filter material.
  13. Apply a thin film of clean oil to the rubber gasket on the new oil filter.
  14. Install the new oil filter; hand tighten clockwise until the gasket contacts the adapter, then tighten an additional 3/4--1 turn.
  15. Fill the crankcase with new oil to the F/FULL mark on the dipstick; reinstall cap/dipstick, reconnect battery cable negative (--) lead last, test run, check for leaks, and recheck oil level.
Remove the generator set from service maintenance

⚠ Disconnect the battery cables before working on the generator set. Remove the negative (--) lead first when disconnecting and reconnect it last.

  1. Press the OFF button on the generator set controller.
  2. Disconnect the utility power to the generator set.
  3. Disconnect the generator set engine starting battery, negative (--) lead first.
Spark Plugs maintenance

⚠ Servicing the air cleaner: a sudden backfire can cause severe injury. Do not operate with the air cleaner removed.

Tools: 13/16 in. socket, 5/8 in. spark plug socket, Wire feeler gauge, Torque wrench

  1. Disable set: press OFF button, disconnect battery charger power, remove battery cables, negative (--) lead first.
  2. Clean or blow out the area around the base of the plug(s) before removal to keep dirt out of the engine; wear eye protection.
  3. Using a spark plug socket, remove and discard the old spark plug(s).
  4. 24RCL, 30RCL, and 38RCLB: use a 13/16 in. socket. Other models: use a 5/8 in. spark plug socket.
  5. Check and set the gap of the new spark plug(s) using a wire feeler gauge.
  6. Adjust the gap by carefully bending the ground electrode.
  7. Apply a light coating of anti-seize lubricant to the spark plug threads and wipe away any excess compound.
  8. Install the new spark plug(s) and torque as shown in Figure 4.
  9. Reconnect the spark plug lead(s).
  10. Reconnect the battery cable, negative (--) lead last.

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Voltage reconnection

VoltagePhaseConnectionLeadsNotes
100/2001Single
100/2003Delta
110/2201Single
110/2203Delta
115/2301Single
1201SingleGenset System Voltage/Frequency/Phase table for controller setup
120/2083Wye
120/2401Single
120/2403Delta
127/2203Wye
2201Single
220/3803Wye
2301Single
230/4003Wye
2401Single
240/4163Wye
277/4803Wye

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Common questions

How many kW is the Kohler 60RCL?

The Kohler 60RCL is rated 60 kW standby (75.0 kVA).

What engine is in the Kohler 60RCL?

The Kohler 60RCL is powered by the General Motors Industrial Powertrain Vortec 5.7 L engine.

What kind of fuel does the Kohler 60RCL run on?

The Kohler 60RCL runs on LPG/Natural Gas.

What's the oil capacity on a Kohler 60RCL?

The General Motors Industrial Powertrain Vortec 5.7 L engine in the Kohler 60RCL has an oil capacity of 6.2 liters.

Which alternator is fitted to the Kohler 60RCL?

The Kohler 60RCL uses a 4P10X alternator.

What oil filter fits the Kohler 60RCL?

The Kohler 60RCL uses oil filter part number GM16703.

What air filter does the Kohler 60RCL use?

The Kohler 60RCL uses air filter part number A--273699.

Troubleshooting

6

Symptoms & remedies

SymptomCauseRemedy
Controller resetElectromagnetic interference (EMI)Inspect the distributor cap and rotor for specific features. Replace them if necessary with updated parts.
Rough operationElectromagnetic interference (EMI)
The generator set does not crank.Battery weak or dead, Battery connections reversed or poor, Blown fuse(s)Recharge or replace the battery, Check the connections, Replace the fuse. Contact an authorized Kohler distributor/dealer for service if fuse blows repeatedly
The generator set cranks but does not start, starts hard, lacks power, or operates erratically.Air cleaner clogged, Battery weak or dead, Battery connection poor, Spark plug wire connection loose, Low oil pressure shutdown, Fuel pressure insufficient, Engine fuse blown, Engine malfunctionClean and/or replace the air cleaner, Recharge or replace the battery, Clean and tighten the battery connections, Check the spark plug wires, Check for oil leaks. Check the oil level and add oil if necessary, Check the fuel supply and valves, Replace the fuse. If the fuse blows again, contact an authorized Kohler distributor/dealer, Contact an authorized Kohler distributor/dealer
No AC output.AC circuit breaker in the OFF position, AC circuit breaker tripping because of overload, AC circuit breaker tripping because of short circuitPlace the circuit breaker in the ON position, Reduce the load on the generator set, Contact an authorized Kohler distributor/dealer for service
Generator set stops suddenly.Low oil pressure shutdown, Out of fuel, Overcrank shutdownCheck for oil leaks. Check the oil level and add oil if necessary, Check fuel supply, Reset the controller. If the overcrank fault occurs again, contact an authorized Kohler distributor/dealer

Fault codes and symptom→remedy steps extracted from this model’s service/owner documentation; verify against the official manual before servicing. Full Kohler 60RCL troubleshooting guide (12 entries) →

Parts

76
Part #DescriptionQtySystem
359249Hose, 45 deg. elbow (3.00 in. ID)1Air filter Amazon eBay
A--253104Air Cleaner Element1Air filter Amazon Amazon eBay eBay
A--273699Air Cleaner Element1Air filter Amazon Amazon eBay eBay
GM103656Hose, coolant SAE J20R2--DI 5/8 in. ID1Hose eBay $23.00
GM16132Belt, fan standard1Belt Amazon eBay $86.00
GM16133Gasket, intake manifold1Gasket eBay
GM16140Cap, Bypass 5/8” (includes cap, connector, hose, clamps)1Hose eBay
GM16180Alternator, 70 amp1Alternator eBay
GM16199Gasket, manifold exhaust2Gasket eBay
GM16202Gasket, intake manifold1Gasket eBay
GM16348Gasket, valve rocker arm cover2Gasket eBay
GM16353Gasket, cylinder head (60 kw)2Gasket eBay
GM16360Gasket, distributor1Gasket Amazon eBay
GM16362Gasket, oil pan1Gasket eBay
GM16366Seal, crankshaft front oil1Seal Amazon eBay
GM16385Seal, intake valve stem oil6Seal Amazon eBay
GM16474Seal, crankshaft rear oil1Seal eBay
GM16482Pump, oil, .742 dia. tube (incl. items 38--43)1Pump Amazon eBay
GM16483Gasket, water pump cover1Gasket Amazon eBay
GM16496Seal, exhaust valve stem oil6Seal Amazon eBay
GM16536Gasket, thermostat cover2Gasket Amazon eBay
GM16582Gasket, water pump (part of item 31)1Gasket Amazon eBay
GM16703Filter, oil1Oil filter Amazon $9.06 eBay $58.00
GM22171Spark plug8Oil filter Amazon eBay
GM38981Gasket, crankshaft rear oil seal housing1Gasket eBay
GM39227Sensor, 1 bar TMAP1Sensor eBay
GM39601Sensor, coolant1Sensor eBay
GM42579Hose, fuel 3/8 in. 14.5 in.1Hose eBay
GM60238Gasket, man. adapter Venturi1Gasket Amazon eBay
GM69504O-ring1Seal eBay
GM72292Sensor, O21Sensor Amazon eBay
GM72303Sender, oil pressure1Sensor Amazon eBay
GM75023Seal, crankshaft pos. sensor1Seal Amazon eBay
GM75083Sensor, crishf posn1Sensor eBay
GM75088Seal, oil pan drn plug(o ring)1Seal eBay
GM75133Hose, WP to Int Man1Hose eBay
GM75159Wires, Spark Plug1Spark plug eBay
GM75237Pump kit, wat (incls plug, seal, cover, gasket)1Pump eBay
GM79585-SThermostat, Service Kit (includes gasket)1Thermostat Amazon eBay eBay
GM85017Belt, Alt1Belt Amazon eBay $52.00
GM88993-GR1Mount, Air Cleaner (6.76”ID)1Air filter Amazon eBay
GM89979Air Filter, Oil, qts. 5.7L GM899791Air filter eBay
GM90280Air Cleaner Assy1Air filter Amazon eBay
GM90281Element, Air Cleaner1Air filter Amazon $35.66 eBay KuduParts $43.00
GM90538Camshaft Position Sensor (part of item 1)1Sensor Amazon eBay $154.89
GM90969-KP1-QS3" Concrete Mounting Pad (only comes in quantities of 5)Physical Amazon eBay
GM90969-KP2-QS4" Concrete Mounting Pad (only comes in quantities of 5)Physical Amazon eBay
GM92228-KP1-QS3" Concrete Mounting Pad (only comes in quantities of 5)Physical Amazon eBay
GM92228-KP2-QS4" Concrete Mounting Pad (only comes in quantities of 5)Physical Amazon eBay
X-312-47Hose (0.63 in. ID x 36 in.)1Hose eBay
X-391-19Connector, 90 degrees (5/8 in. ID hose)1Hose eBay $30.00
X-582-1Connector, hose (5/8 in. x 1/2 in. MIP brass)1Hose Amazon eBay
X-6014-137Hose, Wire Insert 3 in. ID1Hose Amazon eBay
100ERESDKOHLER 100ERESD generatorService part / kit eBay
352945Block heater (kit GM78529-KP1-QS)1Service part / kit eBay FridayParts $69.99
352946Block heater (kit GM78529-KP2)1Service part / kit eBay
60RCLKOHLER 60RCL generatorService part / kit Amazon eBay
GM1018238.8L breather retrofit kit with oil cooler1Service part / kit Amazon eBay
GM16159Valve, PCV1Service part / kit Amazon eBay
GM17809Shield, heat (32 mm ID x 152 mm)1Service part / kit eBay
GM23718Shield, heat (32 mm ID x 455 mm)1Service part / kit eBay
GM29586Valve, throttle, 60 mm1Service part / kit Amazon eBay
GM62348-SKP1-QSMaintenance Kit1Service part / kit Amazon eBay
GM69500Mixer1Service part / kit eBay
GM71622-MA1X-612-141Service part / kit Amazon eBay
GM75155Distributor HVS (includes item 10)1Service part / kit eBay
GM75164Coil, Ignition1Service part / kit eBay
GM83718-SKP1-QSMaintenance Kit1Service part / kit Amazon eBay
GM86771-SKP1-QSMaintenance Kit1Service part / kit Amazon eBay
GM87989updated distributor capService part / kit Amazon eBay
GM87990rotor with the properly coated contactService part / kit Amazon eBay
GM89979-SKP1-QSMaintenance Kit1Service part / kit Amazon eBay
GM93396-SKP1-QSMaintenance Kit1Service part / kit Amazon eBay
GM93491EPR assembly (60RCL)1Service part / kit eBay
M6923-08-80Nut, Hex 8MM2Service part / kit Amazon eBay
M933-08016-60Screw2Service part / kit Amazon eBay

Service, wear & replacement parts referenced for this model and its engine — confirm the exact part for your serial number. See the full parts catalog to search and cross-reference.

Fuel consumption

RatingLoadL/hgal/h
Standby25%9.92.62
Standby50%14.73.88
Standby75%19.45.12
Standby100%22.45.92

Available documents

Spec sheet (Kohler)Operator's manual (Kohler)Operator's manual — tp6928 (Kohler)Reference (Kohler)Reference — RES Consumer Referral Rebate (Kohler)Reference — Referral Rebate Form EDITABLE (Kohler)Reference — g6120 g11124 (Kohler)Reference — g6132 (Kohler)Reference — tp6809 (Kohler)Reference — tp6809f (Kohler)Owner's manual (Kohler)Owner's manual — tp6810 (Kohler)Parts manual (Kohler)Parts manual — Kohler 2017 Referral Rebate Consumer RES (Kohler)Parts manual — Kohler 2019 RES Consumer Referral Rebate (Kohler)Parts manual — tp6731 (Kohler)Service manual — Controllers tt1589 (Kohler)Service manual — SB-777 (Kohler)Service manual — tp6811 (Kohler)Service manual — tp7007 (Kohler)Service manual — tt1445 (Kohler)Service manual — tt1587 (Kohler)Service manual — tt1742 (Kohler)
Full service, cheapest listings

Priced items from this model's own parts manual.

Oil filter GM16703$9.06
Belt GM16132$86.00
2 priced items$95.06