Kohler — Procedure to Reset the Controller after a Fault Shutdown
Testing & diagnosis · RDC2 controller
From a Kohler operator's manual covering: 38RCL, 48RCL, 60RCL. Check it applies to your exact model before use.
Applies to: Kohler 38RCL, Kohler 48RCL, Kohler 60RCL
Before you start
- Always identify and correct the cause of a fault shutdown before resetting the controller.
Procedure
- Press the Select button to go to the Overview menu.
- Press Select again to display the active fault.
- Press Select; Confirm Clear Fault: NO is displayed.
- Press the Up arrow button; Confirm Clear Fault: YES is displayed.
- Press the Select button to enter YES and clear the fault.
- Press the Select button to return to the overview menu.
- Press AUTO to put the generator set into automatic mode.
Full service-parts list: Kohler 38RCL →, Kohler 48RCL →, Kohler 60RCL →
Source: Kohler operator's manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.