HomeKohlerKohler 70REZGT

Kohler 70REZGT Generator Set

The Kohler 70REZGT is a 62 kW (77 kVA) LP/NG standby generator set powered by a General Motors Industrial Powertrain Vortec 5.7 L engine. It is available at 120/208 V, 277/480 V and 120/240 V, 3-phase and 60 Hz. It holds about 6.2 L (1.6 gal) of oil and 22.5 L (5.9 gal) of coolant. The set measures 4339×2118×2691 mm (170.8×83.4×105.9 in), weighs about 2145 kg (4729 lb) and produces 70 dBA at 7 m. An integrated tank holds 625 L (165.1 gal), roughly 26 hours of runtime. The same Industrial Powertrain Vortec 5.7 L engine also powers generator sets from SDMO.

62 kW
Standby
5.7 L
Displacement
6.2 L
Oil capacity
5
Document types

How to read your Kohler serial & model number →

Typical fuel consumption for 60–65 kW Bi-Fuel (NG/LP) generators →

Compare with other 60–65 kW Bi-Fuel (NG/LP) generators →

Service parts for the 70REZGT

Grouped by system, with how many of each the parts manual calls for.

Air intake

1 required

Prices captured from merchant listings; some links are affiliate links. Confirm against your serial number before ordering.

Specifications

FuelLP/NG
Frequency60.0 Hz
Standby power62 kW
Standby kVA77
Prime power56 kW
EmissionsEPA Certified Prime
ControllerDecision-Maker 3500
Oil capacity6.2 L
Voltage options120/208 V, 277/480 V, 120/240 V
Phase3 Ph
Circuit breaker150 A
Dimensions (L×W×H)4339×2118×2691 mm
Dry weight2145 kg
Sound level70.0 dBA @ 7 m
Fuel tank625.0 L
Tank runtime26 hr

Engine

General Motors Industrial Powertrain Vortec 5.7 L
Oil capacity6.2 L
Coolant capacity22.5 L
Displacement5.7 L
AspirationTurbocharged
Rated speed1800 rpm

Maintenance & consumables

for the General Motors Industrial Powertrain Vortec 5.7 L
ItemSpecCapacityPart #Interval
Air filterAir Cleaner AssyGM90280 Amazon eBay
Oil filterCartridge×1
Oil6.2 L100 hr

Service intervals

2
ItemActionHoursMonthsNotes
Paralleling boxInspect12 moAnnually by a Kohler authorized distributor/dealer, or when wear, damage, deterioration, or malfunction is evident or suspected.
Paralleling box internal componentsInspect1 moMonthly or when a condition noticed during external inspection may have affected internal components; enclosure cover must be removed by trained personnel.

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Service specifications

6
TypeItemValueUnitCondition
OtherEngine speed adjustment50default setting; settings between 40 and 60 acceptable; 52 increases speed by 2 RPM, 49 decreases by 1 RPM
OtherGenerator to bus phase angle-10 to 10degreesverify with contactor closed
OtherReactive droop1%default setting; range 0.5 - 2%
TorquePGEN terminal block connections0.5Nm
TorquePGEN terminal block connections4.4in. lbs.
VoltageController measurement accuracy2%without calibration; requires a calibrated multimeter for calibration

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Procedures

12
Calibration adjustment

⚠ Copying personality profiles from one controller to another can overwrite calibration coefficients and requires re-calibration.

Tools: Calibrated multimeter with recent calibration verification

  1. Use a calibrated multimeter to measure the generator voltage and enter the correct value in the CONTROLLER CONFIG -> CALIBRATION screen.
  2. Use a calibrated multimeter to measure the bus voltage and enter the correct value in the CONTROLLER CONFIG -> CALIBRATION screen.
Verify Generator Operation diagnostic

⚠ Generators must all operate at the same frequency, voltage, and phase connection in order to parallel.

Tools: SiteTech software

  1. Ensure the load is not connected or is drawing less power than a single generator can provide.
  2. Navigate to CONTROLLER CONFIG -> COMMUNICATION SETUP and verify PGEN Nodes Online indicates the correct number of nodes.
  3. Verify alternator connection (voltage selector switch position), system voltage, and voltage regulator target on each generator.
  4. Start a single generator by pressing the Run button; the paralleling box contactor should close and the Generator Connected to Bus indicator should light.
  5. Verify bus and generator voltages match and generator to bus phase angle is between -10 and 10 degrees.
  6. Verify the load bus is energized and available at the load.
  7. Stop the generator by pressing the OFF button; the contactor should open.
  8. Repeat for each generator in the paralleling system.
Verify Paralleling and Load Sharing diagnostic

Tools: Load bank (optional)

  1. Place all generators in automatic mode by pressing the Auto button; verify the red shutdown indicator is not illuminated.
  2. Provide a local start request by holding AUTO, pressing RUN, releasing RUN, then releasing AUTO.
  3. Verify all generators start, one generator closes its contactor, and the others synchronize and close their contactors.
  4. Verify that the % of rated power of the generators matches, showing the generators are sharing load equally.
  5. If a load bank is available, test the system under load.
Control Harness Connections installation

⚠ The control harness connections for GEN 1 and GEN 2 must correspond to the source camlock cable connections.

  1. Connect the control harness from the generator set connected to the GEN 1 camlock connectors to GEN 1 CONTROL.
  2. Connect the control harness from the generator set connected to the GEN 2 camlock connectors to GEN 2 CONTROL.
  3. When not used, store the control harnesses on the storage rack inside the enclosure.
Grounding installation

⚠ Grounding electrical equipment: hazardous voltage can cause severe injury or death. Turn off the main circuit breakers of all power sources before servicing.

  1. Connect the ground lug on the paralleling box to earth ground according to applicable state and local codes.
  2. Follow NEC guidelines for grounding electrical equipment.
  3. The neutral is bonded to ground inside the paralleling box; if required, remove the bonding bus to disconnect neutral from ground.
Load Connections installation

⚠ Multiple power sources can automatically energize the distribution bus. Disconnect all power sources before connecting to the distribution bus.

  1. Remove the camlock security guard from one row of connectors for each generator and store the guard.
  2. Connect the load side ground (green) camlock cables to the distribution bus and then to the paralleling box.
  3. Connect the load side neutral (white) camlock cables to the distribution bus and then to the paralleling box.
  4. Connect the load side L1 (black), L2 (red), and L3 (blue) camlock cables to the distribution bus and then to the paralleling box.
Multiple Paralleling Boxes (PGEN Connections) installation
  1. Connect one or two generators to each paralleling box.
  2. Use Belden cable #9841 (or equivalent) shielded twisted-pair communication cable to connect the PGEN terminal blocks on the paralleling boxes.
  3. Tighten the connections to 0.5 Nm (4.4 in. lbs.).
Paralleling System Setup installation

⚠ Generator management must be disabled manually at each generator set controller.

Tools: Personal computer with SiteTech software

  1. Check that the voltage selector switch and/or alternator wiring matches the building voltage configuration for all generator sets.
  2. Set the digital output to Contactor (SiteTech Programmable Digital Output 116).
  3. Set reactive droop to 0.5-2% (default 1%), using the same reactive droop setting on all generators.
  4. Set the target voltage on all paralleled generators to the same value.
  5. Set engine speed adjustment to 50 on all generators (default 50; range 40-60).
  6. Verify metering; if voltage is incorrect, use the calibration procedure.
  7. Set Sync Mode in AUTO to ACTIVE and Sync Mode in Run to CHECK on all generators.
  8. Set Generator Management Enabled to OFF at each generator unless generator management is requested.
  9. Set up load management (load shed priorities) for non-critical loads.
  10. Stop all generators by pressing the OFF button on each controller.
Source Connections installation

⚠ Hazardous voltage. This equipment must be installed and serviced by qualified electrical personnel. Do not connect or disconnect cables under load.

  1. Remove the camlock security guard from one row of connectors for each generator and store the guard.
  2. Generator 2 connects to the upper set of camlocks; generator 1 connects to the lower set.
  3. Connect the source side ground (green) camlock cables to the paralleling box first and then to each generator.
  4. Connect the source side neutral (white) camlock cables to the paralleling box first and then to each generator.
  5. Connect the source side L1 (black), L2 (red), and L3 (blue) camlock cables to the paralleling box first and then to each generator.
Storage Procedure maintenance

⚠ Do not open the electrical compartment on the opposite side of the enclosure; that compartment should be opened only by Kohler authorized distributors or dealers.

  1. Store control harnesses on the storage rack inside the box when not in use.
  2. Lock the cabinet door with the key provided and store the key in a secure location.
  3. Use the guards to cover the camlock connectors.
  4. Attach padlocks to the electrical panel cover and the camlock guards to prevent unauthorized access.
Disable the Generator Sets operation

⚠ Accidental starting can cause severe injury or death. Remove the negative (-) lead first when disconnecting the battery; reconnect it last.

  1. Press the generator set master control OFF/RESET button.
  2. Disconnect the power to the battery charger, if equipped.
  3. Disconnect the generator set engine starting battery(ies), negative (-) lead first.
Re-enable the Generator Sets operation

⚠ Reconnect the battery correctly, positive to positive and negative to negative, to avoid electrical shock and damage.

  1. Check that the generator set is OFF.
  2. Reconnect the generator set engine starting battery, negative (-) lead last.
  3. Reconnect power to the battery charger, if equipped.

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Common questions

How many kW is the Kohler 70REZGT?

The Kohler 70REZGT is rated 62 kW standby (77.0 kVA).

What engine is in the Kohler 70REZGT?

The Kohler 70REZGT is powered by the General Motors Industrial Powertrain Vortec 5.7 L engine.

What fuel type does the Kohler 70REZGT take?

The Kohler 70REZGT runs on LP/NG.

What's the oil capacity on a Kohler 70REZGT?

The General Motors Industrial Powertrain Vortec 5.7 L engine in the Kohler 70REZGT has an oil capacity of 6.2 liters.

What air filter fits the Kohler 70REZGT?

The Kohler 70REZGT uses air filter part number GM90280.

Parts

74
Part #DescriptionQtySystem
359249Hose, 45 deg. elbow (3.00 in. ID)1Air filter Amazon eBay
GM103656Hose, coolant SAE J20R2--DI 5/8 in. ID1Hose eBay $23.00
GM16132Belt, fan standard1Belt Amazon eBay $86.00
GM16133Gasket, intake manifold1Gasket eBay
GM16140Cap, Bypass 5/8” (includes cap, connector, hose, clamps)1Hose eBay
GM16180Alternator, 70 amp1Alternator eBay
GM16199Gasket, manifold exhaust2Gasket eBay
GM16202Gasket, intake manifold1Gasket eBay
GM16348Gasket, valve rocker arm cover2Gasket eBay
GM16353Gasket, cylinder head (60 kw)2Gasket eBay
GM16360Gasket, distributor1Gasket Amazon eBay
GM16362Gasket, oil pan1Gasket eBay
GM16366Seal, crankshaft front oil1Seal Amazon eBay
GM16385Seal, intake valve stem oil6Seal Amazon eBay
GM16474Seal, crankshaft rear oil1Seal eBay
GM16482Pump, oil, .742 dia. tube (incl. items 38--43)1Pump Amazon eBay
GM16483Gasket, water pump cover1Gasket Amazon eBay
GM16496Seal, exhaust valve stem oil6Seal Amazon eBay
GM16536Gasket, thermostat cover2Gasket Amazon eBay
GM16582Gasket, water pump (part of item 31)1Gasket Amazon eBay
GM16703Filter, oil1Oil filter Amazon $9.06 eBay $58.00
GM22171Spark plug8Oil filter Amazon eBay
GM38981Gasket, crankshaft rear oil seal housing1Gasket eBay
GM39227Sensor, 1 bar TMAP1Sensor eBay
GM39601Sensor, coolant1Sensor eBay
GM42579Hose, fuel 3/8 in. 14.5 in.1Hose eBay
GM60238Gasket, man. adapter Venturi1Gasket Amazon eBay
GM69504O-ring1Seal eBay
GM72292Sensor, O21Sensor Amazon eBay
GM72303Sender, oil pressure1Sensor Amazon eBay
GM75023Seal, crankshaft pos. sensor1Seal Amazon eBay
GM75083Sensor, crishf posn1Sensor eBay
GM75088Seal, oil pan drn plug(o ring)1Seal eBay
GM75133Hose, WP to Int Man1Hose eBay
GM75159Wires, Spark Plug1Spark plug eBay
GM75237Pump kit, wat (incls plug, seal, cover, gasket)1Pump eBay
GM79585-SThermostat, Service Kit (includes gasket)1Thermostat Amazon eBay eBay
GM85017Belt, Alt1Belt Amazon eBay $52.00
GM88993-GR1Mount, Air Cleaner (6.76”ID)1Air filter Amazon eBay
GM89979Air Filter, Oil, qts. 5.7L GM899791Air filter eBay
GM90280Air Cleaner Assy1Air filter Amazon eBay
GM90281Element, Air Cleaner1Air filter Amazon $35.66 eBay KuduParts $43.00
GM90538Camshaft Position Sensor (part of item 1)1Sensor Amazon eBay $154.89
GM90969-KP1-QS3" Concrete Mounting Pad (only comes in quantities of 5)Physical Amazon eBay
GM90969-KP2-QS4" Concrete Mounting Pad (only comes in quantities of 5)Physical Amazon eBay
GM92228-KP1-QS3" Concrete Mounting Pad (only comes in quantities of 5)Physical Amazon eBay
GM92228-KP2-QS4" Concrete Mounting Pad (only comes in quantities of 5)Physical Amazon eBay
X-312-47Hose (0.63 in. ID x 36 in.)1Hose eBay
X-391-19Connector, 90 degrees (5/8 in. ID hose)1Hose eBay $30.00
X-582-1Connector, hose (5/8 in. x 1/2 in. MIP brass)1Hose Amazon eBay
X-6014-137Hose, Wire Insert 3 in. ID1Hose Amazon eBay
100ERESDKOHLER 100ERESD generatorService part / kit eBay
352945Block heater (kit GM78529-KP1-QS)1Service part / kit eBay FridayParts $69.99
352946Block heater (kit GM78529-KP2)1Service part / kit eBay
60RCLKOHLER 60RCL generatorService part / kit Amazon eBay
GM1018238.8L breather retrofit kit with oil cooler1Service part / kit Amazon eBay
GM16159Valve, PCV1Service part / kit Amazon eBay
GM17809Shield, heat (32 mm ID x 152 mm)1Service part / kit eBay
GM23718Shield, heat (32 mm ID x 455 mm)1Service part / kit eBay
GM29586Valve, throttle, 60 mm1Service part / kit Amazon eBay
GM62348-SKP1-QSMaintenance Kit1Service part / kit Amazon eBay
GM69500Mixer1Service part / kit eBay
GM71622-MA1X-612-141Service part / kit Amazon eBay
GM75155Distributor HVS (includes item 10)1Service part / kit eBay
GM75164Coil, Ignition1Service part / kit eBay
GM83718-SKP1-QSMaintenance Kit1Service part / kit Amazon eBay
GM86771-SKP1-QSMaintenance Kit1Service part / kit Amazon eBay
GM87989updated distributor capService part / kit Amazon eBay
GM87990rotor with the properly coated contactService part / kit Amazon eBay
GM89979-SKP1-QSMaintenance Kit1Service part / kit Amazon eBay
GM93396-SKP1-QSMaintenance Kit1Service part / kit Amazon eBay
GM93491EPR assembly (60RCL)1Service part / kit eBay
M6923-08-80Nut, Hex 8MM2Service part / kit Amazon eBay
M933-08016-60Screw2Service part / kit Amazon eBay

Service, wear & replacement parts referenced for this model and its engine — confirm the exact part for your serial number. See the full parts catalog to search and cross-reference.

Fuel consumption

RatingLoadL/hgal/h
Prime50%10.22.7
Prime75%13.23.5

Available documents

Spec sheet — Towable Mobile Generators Brochure (Kohler)Reference — Kohler-Gas Generators Brochure (Kohler)Reference — Mobile Rental Generators (Kohler)Owner's manual — tp6935 (Kohler)Parts manual — tp6937 (Kohler)Service manual — tp6936 (Kohler)Service manual — tt1672 (Kohler)