Home›Repair guides›Kohler›Source Connections

Kohler — Source Connections

Installation · Paralleling box source camlock connectors

From a Kohler service manual covering: 125REZGT, 145REOZT4, 175REOZT4, 30REZG, 35 REOZT4, 45 REOZT4, 50REZG, 55REOZT4, 70REZGT, GM88594-KP1-QS, REOZT4. Check it applies to your exact model before use.

Applies to: Kohler 125REZGT, Kohler 145REOZT4, Kohler 175REOZT4, Kohler 30REZG, Kohler 35 REOZT4, Kohler 45 REOZT4, Kohler 50REZG, Kohler 55REOZT4, Kohler 70REZGT

Before you start

  • Hazardous voltage. This equipment must be installed and serviced by qualified electrical personnel. Do not connect or disconnect cables under load.

Procedure

  1. Remove the camlock security guard from one row of connectors for each generator and store the guard.
  2. Generator 2 connects to the upper set of camlocks; generator 1 connects to the lower set.
  3. Connect the source side ground (green) camlock cables to the paralleling box first and then to each generator.
  4. Connect the source side neutral (white) camlock cables to the paralleling box first and then to each generator.
  5. Connect the source side L1 (black), L2 (red), and L3 (blue) camlock cables to the paralleling box first and then to each generator.

Specs & values

  • Maximum current allowed for each camlock cable is 400 amps

Full service-parts list: Kohler 125REZGT →, Kohler 145REOZT4 →, Kohler 175REOZT4 →, Kohler 30REZG →, Kohler 35 REOZT4 →, Kohler 45 REOZT4 →, Kohler 50REZG →, Kohler 55REOZT4 →, Kohler 70REZGT →

Source: Kohler service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.