Home›Repair guides›Kohler›Extended Storage (Lubricating System)

Kohler — Extended Storage (Lubricating System)

Maintenance · Engine lubricating system

From a Kohler operator's manual covering: 125REZGT, 30--125REZGT, 30REZG, 30REZGT, 50REZG, 70REZGT. Check it applies to your exact model before use.

Applies to: Kohler 125REZGT, Kohler 30REZG, Kohler 30REZGT, Kohler 50REZG, Kohler 70REZGT

Before you start

  • Hot engine and exhaust system. Do not work on the generator set until it cools.

Procedure

  1. Run the generator set for a minimum of 30 minutes to bring it to normal operating temperature.
  2. Stop the generator set.
  3. With the engine still warm, drain the oil from the crankcase.
  4. Remove and replace the oil filter.
  5. Refill the crankcase with oil suited to the climate.
  6. Run the generator set for two minutes to distribute the clean oil.
  7. Stop the generator set.
  8. Check the oil level and adjust, if needed.

Specs & values

  • Perform before taking out of service for three months or longer

Full service-parts list: Kohler 125REZGT →, Kohler 30REZG →, Kohler 30REZGT →, Kohler 50REZG →, Kohler 70REZGT →

Source: Kohler operator's manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.