Kohler — Multiple Paralleling Boxes (PGEN Connections)

Installation · PGEN terminal block

From a Kohler service manual covering: 125REZGT, 145REOZT4, 175REOZT4, 30REZG, 35 REOZT4, 45 REOZT4, 50REZG, 55REOZT4, 70REZGT, GM88594-KP1-QS, REOZT4. Check it applies to your exact model before use.

Applies to: Kohler 125REZGT, Kohler 145REOZT4, Kohler 175REOZT4, Kohler 30REZG, Kohler 35 REOZT4, Kohler 45 REOZT4, Kohler 50REZG, Kohler 55REOZT4, Kohler 70REZGT

Procedure

  1. Connect one or two generators to each paralleling box.
  2. Use Belden cable #9841 (or equivalent) shielded twisted-pair communication cable to connect the PGEN terminal blocks on the paralleling boxes.
  3. Tighten the connections to 0.5 Nm (4.4 in. lbs.).

Specs & values

  • Tighten PGEN connections to 0.5 Nm (4.4 in. lbs.)
  • Up to four paralleling boxes with eight generator sets can be connected together

Full service-parts list: Kohler 125REZGT →, Kohler 145REOZT4 →, Kohler 175REOZT4 →, Kohler 30REZG →, Kohler 35 REOZT4 →, Kohler 45 REOZT4 →, Kohler 50REZG →, Kohler 55REOZT4 →, Kohler 70REZGT →

Source: Kohler service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.