Kohler 70REZGT Troubleshooting

Kohler 70REZGT troubleshooting: 129 symptom-cause-remedy entries from the manufacturer's own service documentation.

Kohler 70REZGT — full specs, parts & maintenance.

All Kohler fault codes →

Troubleshooting

129

Symptoms & remedies

SymptomCauseRemedy
Does not crankController and Emergency Stop Switch
Cranks but does not startController and Emergency Stop Switch
Does not crankController circuit board(s) inoperativeReplace the controller.
Cranks but does not startController circuit board(s) inoperativeReplace the controller.
Does not crankController circuit board(s) wiring faultCheck the wiring.
Does not crankController faultTroubleshoot the controller.
Cranks but does not startController faultTroubleshoot the controller.
Starts hardController faultTroubleshoot the controller.
Does not crankController internal fuse blownCheck for battery power to the circuit board. If fuse does not auto-reset troubleshoot the controller and wiring.
Cranks but does not startController internal fuse blownCheck for battery power to the circuit board. If fuse does not auto-reset troubleshoot the controller and wiring.
Displays error message/locks upController master control buttons inoperativeReplace the controller master control button circuit board.
Does not crankController master control button in the OFF/RESET modePress the controller master control RUN or AUTO button.
Does not crankEngine start circuit openPress the controller master control RUN button to test the generator set. Troubleshoot the auto start circuit and time delays.
Cranks but does not startEngine start circuit openPress the controller master control RUN button to test the generator set. Troubleshoot the auto start circuit and time delays.
Does not crankEmergency stop switch activated, if equippedReset the emergency stop switch.
Cranks but does not startEmergency stop switch activated, if equippedReset the emergency stop switch.
No or low output voltageVoltage regulation inoperativeReplace the junction box sensing fuses. If the fuse blows again, troubleshoot the controller.
Displays error message/locks upController firmware errorReview the controller display troubleshooting chart.
Displays error message/locks upController communication errorVerify that RS-485 cable “shield” wire is connected on only one end.
No or low output voltageAC output circuit breaker openReset the breaker and check for AC voltage at the generator set side of the circuit breaker.
Does not crankTransfer switch test switch in the OFF positionMove the transfer switch test switch to the AUTO position.
Does not crankTransfer switch fails to transfer loadMove the ATS test switch to the AUTO position. Troubleshoot the transfer circuit and time delays.
No or low output voltageWiring, terminals, or pin in the exciter field openCheck for continuity.
No or low output voltageMain field (rotor) inoperative (open or grounded)Test and/or replace the rotor.
No or low output voltageStator inoperative (open or grounded)Test and/or replace the stator.
Excessive or abnormal noiseVibration excessiveTighten loose components.
No or low output voltageVibration excessiveTighten loose components.
No or low output voltageVoltage regulator settings incorrectAdjust the voltage regulator.
Does not crankBattery connections loose, corroded, or incorrectVerify that the battery connections are correct, clean, and tight.
Cranks but does not startBattery connections loose, corroded, or incorrectVerify that the battery connections are correct, clean, and tight.
Does not crankBattery weak or deadRecharge or replace the battery. The spec sheet provides recommended battery CCA rating.
Cranks but does not startBattery weak or deadRecharge or replace the battery. The spec sheet provides recommended battery CCA rating.
Does not crankStarter/starter solenoid inoperativeReplace the starter or starter solenoid.
Cranks but does not startStarter/starter solenoid inoperativeReplace the starter or starter solenoid.
Does not crankEngine harness connector(s) not locked tightDisconnect the engine harness connector(s) then reconnect it to the controller.
Cranks but does not startEngine harness connector(s) not locked tightDisconnect the engine harness connector(s) then reconnect it to the controller.
Does not crankFault shutdownReset the fault switches and troubleshoot the controller.
Cranks but does not startFault shutdownReset the fault switches and troubleshoot the controller.
Does not crankAir cleaner cloggedClean or replace the filter element.
Cranks but does not startAir cleaner cloggedClean or replace the filter element.
Starts hardAir cleaner cloggedClean or replace the filter element.
Lacks powerAir cleaner cloggedClean or replace the filter element.
Does not crankCompression weakCheck the compression.
Cranks but does not startCompression weakCheck the compression.
Starts hardCompression weakCheck the compression.
Lacks powerCompression weakCheck the compression.
High fuel consumptionCompression weakCheck the compression.
Stops suddenlyEngine overloadReduce the electrical load. See the generator set spec sheet for wattage specifications.
Lacks powerEngine overloadReduce the electrical load. See the generator set spec sheet for wattage specifications.
Excessive or abnormal noiseExhaust system leakInspect the exhaust system. Replace the inoperative exhaust system components.
Excessive or abnormal noiseExhaust system not securely installedInspect the exhaust system. Tighten the loose exhaust system components.
Starts hardGovernor inoperativeAdjust the governor.
Lacks powerGovernor inoperativeAdjust the governor.
OverheatsGovernor inoperativeAdjust the governor.
Excessive or abnormal noiseGovernor inoperativeAdjust the governor.
Starts hardValve clearance incorrectAdjust the valves.
Lacks powerValve clearance incorrectAdjust the valves.
Does not crankEngine ECM and/or sensorsTroubleshoot the engine ECM and/or sensors.
Cranks but does not startEngine ECM and/or sensorsTroubleshoot the engine ECM and/or sensors.
Starts hardEngine ECM and/or sensorsTroubleshoot the engine ECM and/or sensors.
Lacks powerEngine ECM and/or sensorsTroubleshoot the engine ECM and/or sensors.
High fuel consumptionEngine ECM and/or sensorsTroubleshoot the engine ECM and/or sensors.
OverheatsAir openings cloggedClean the air openings.
OverheatsCoolant level lowRestore the coolant to normal operating level.
OverheatsCooling water pump inoperativeTighten or replace the belt. Replace the water pump.
OverheatsHigh temperature shutdownAllow the engine to cool down. Then troubleshoot the cooling system.
OverheatsLow coolant level shutdown, if equippedRestore the coolant to normal operating level.
OverheatsThermostat inoperativeReplace the thermostat.
Cranks but does not startFuel tank empty or fuel valve shut offAdd fuel and move the fuel valve to the ON position.
Starts hardFuel tank empty or fuel valve shut offAdd fuel and move the fuel valve to the ON position.
Stops suddenlyFuel tank empty or fuel valve shut offAdd fuel and move the fuel valve to the ON position.
Lacks powerFuel tank empty or fuel valve shut offAdd fuel and move the fuel valve to the ON position.
Cranks but does not startFuel filter restrictionClean or replace the fuel filter.
Starts hardFuel filter restrictionClean or replace the fuel filter.
Stops suddenlyFuel filter restrictionClean or replace the fuel filter.
Lacks powerFuel filter restrictionClean or replace the fuel filter.
Cranks but does not startFuel solenoid inoperativeTroubleshoot the fuel solenoid.
Stops suddenlyOil level lowRestore the oil level. Inspect the generator set for oil leaks.
Low oil pressureOil level lowRestore the oil level. Inspect the generator set for oil leaks.
Excessive or abnormal noiseOil level lowRestore the oil level. Inspect the generator set for oil leaks.
Stops suddenlyLow oil pressure shutdownCheck the oil level.
Starts hardCrankcase oil type incorrect for ambient temperatureChange the oil. Use oil with a viscosity suitable for the operating climate.
Lacks powerCrankcase oil type incorrect for ambient temperatureChange the oil. Use oil with a viscosity suitable for the operating climate.
OverheatsCrankcase oil type incorrect for ambient temperatureChange the oil. Use oil with a viscosity suitable for the operating climate.
High fuel consumptionCrankcase oil type incorrect for ambient temperatureChange the oil. Use oil with a viscosity suitable for the operating climate.
Display is blackNo/low battery chargeRecharge/replace battery
Display shows single segmentLow battery voltageRecharge battery
Display shows an error messageController firmware or pushbutton/rotary selector dial entry errorReview the System Fault Shutdown Lamp With Digital Displays section
Display locks upNo/low battery chargeRecharge/replace battery
Output voltage rampsDefective exciter windingTroubleshoot alternator components
Output voltage unstableVoltage regulation calibration incorrectReadjust voltage regulation
Unable to change voltage and current calibrationsCalibration not enabledEnable calibration in Generator Metering section 2.6.3 Calibration Submenu
Unable to find volt select menuVolt select not enabledEnable volt select in SiteTech
Trailer is unstable or noisy during towing.Tire(s) worn or damagedCheck tire condition. Repair or replace.
Trailer is unstable or noisy during towing.Tire pressure lowCheck tire pressure and inflate as necessary.
Trailer is unstable or noisy during towing.Wheel lug nuts looseTorque wheel lug nuts.
Trailer is unstable or noisy during towing.Tire/wheels mismatched on same axleCheck compatibility of wheels and tires on each end of axle.
Trailer is unstable or noisy during towing.Trailer not level horizontally (side to side)Check compatibility of wheels and tires of each axle. Check trailer weight distribution and cargo.
Trailer is unstable or noisy during towing.Trailer not level horizontally (front to back)Check and adjust trailer hitch height.
Trailer is unstable or noisy during towing.Generator set not secured to trailerCheck mounting hardware.
Trailer is unstable or noisy during towing.Trailer suspension noisyLubricate suspension contact points.
Trailer is unstable or noisy during towing.Trailer suspension worn or damagedCheck components and replace as necessary.
Trailer is unstable or noisy during towing.Tow vehicle suspension worn or damagedCheck tow vehicle suspension and replace as necessary.
Trailer is unstable or noisy during towing.Trailer hitch worn or damaged or incorrectly attachedReconnect trailer to tow vehicle. Replace worn or damaged components as necessary.
Trailer is unstable or noisy during towing.Wheel bearings underlubricatedDisassemble, clean or replace, and repack.
Trailer is unstable or noisy during towing.Axle shaft or spindle bentCheck components and replace as necessary.
Trailer is unstable or noisy during towing.Bearings wornCheck components and replace as necessary.
Trailer is unstable or noisy during towing.Trailer overloadedCheck trailer weight capacity and cargo.
Tow vehicle and trailer are unstable or noisy during brakingTow vehicle brakes wornCheck brake fluid level. Add fluid as necessary.
Tow vehicle and trailer are unstable or noisy during brakingBrake components wornCheck component and replace as necessary.
Tow vehicle and trailer are unstable or noisy during brakingBrake linings/drums greasy or oilyClean or replace.
Tow vehicle and trailer are unstable or noisy during brakingRotors/drums out of roundMachine or replace.
Main circuit breaker(s) tripped or trips when resetCircuit breaker overloadedReduce circuit load. Reset circuit breaker.
Main circuit breaker(s) tripped or trips when resetElectrical circuit shortedCheck electrical circuit wiring and load connections.
Main circuit breaker(s) tripped or trips when resetCircuit breaker inoperativeContact an authorized service distributor/dealer or licensed electrician.
Duplex circuit breaker(s) tripped or trips when resetCircuit breaker overloadedReduce circuit load. Reset duplex circuit breaker(s).
Duplex circuit breaker(s) tripped or trips when resetElectrical circuit shortedCheck electrical circuit wiring and load connections.
Duplex circuit breaker(s) tripped or trips when resetCircuit breaker inoperativeContact an authorized service distributor/dealer or licensed electrician.
Duplex circuit breaker(s) tripped or trips when resetGFCI outlet trippedCheck ground circuit of GFCI outlet.
Duplex receptacles have no powerGenerator set not runningPower to duplex receptacles is from the generator set—not shore power.
Duplex receptacles have no powerDuplex circuit breaker(s) trippedReduce circuit load. Reset duplex circuit breaker(s).
Duplex receptacles have no powerVoltage selector switch is in the 480-volt position (high wye). (Voltage selector switch not used on all models)Duplex receptacles are not functional when the voltage selector switch is in the 480 volt (high wye) position. The voltage selector switch must be in the single-phase or low wye position in order for the duplex receptacles to have power.
Voltage selector switch position does not match load voltage.Unit not set up for applicationContact onsite electrician or rental distributor. See Section 3, Electrical Connections and Requirements, for more information.
Voltage selector switch knob does not rotate.Padlock installed on lockout featureContact onsite electrician or rental distributor.
Voltage selector switch knob does not rotate.Lockout button inoperativePress lockout button and rotate (do not move the voltage selector switch while generator set is running). See Section 3, Electrical Connections and Requirements, for more information.
Voltage selector switch knob does not rotate.Voltage selector switch inoperative (Voltage selector switch not used on all models)Contact an authorized service distributor/dealer or licensed electrician.
User-supplied wiring between customer connection panel and load devices feels hot or has burning odorWiring undersized for applicationContact onsite electrician or rental distributor.
User-supplied wiring between customer connection panel and load devices feels hot or has burning odorTerminal connections loose and/or corrodedClean, if required, and tighten terminal connections. Torque customer connection panel load lugs to specifications.
Battery charger and/or block heater not functioningDevices not connected to receptaclePlug devices into respective receptacles

Fault codes and symptom→remedy steps extracted from this model’s service/owner documentation; verify against the official manual before servicing.

Cross-brand guides for these symptoms

Common questions

Kohler 70REZGT: Does not crank — what causes it?

Documented causes: Controller and Emergency Stop Switch; Controller circuit board(s) inoperative; Controller circuit board(s) wiring fault; Controller fault. See the table for the matching fixes.

Kohler 70REZGT: Cranks but does not start — what causes it?

Documented causes: Controller and Emergency Stop Switch; Controller circuit board(s) inoperative; Controller fault; Controller internal fuse blown. See the table for the matching fixes.

Kohler 70REZGT: Trailer is unstable or noisy during towing — what causes it?

Documented causes: Tire(s) worn or damaged; Tire pressure low; Wheel lug nuts loose; Tire/wheels mismatched on same axle. See the table for the matching fixes.