Home›Repair guides›Kohler›Restore the generator set to service and top off the coolant

Kohler — Restore the generator set to service and top off the coolant

Operation

From a Kohler service manual covering: 38RCL, 48RCL, 48RCLB, 60RCL, 60RCLA. Check it applies to your exact model before use.

Applies to: Kohler 38RCL, Kohler 48RCL, Kohler 48RCLB, Kohler 60RCL, Kohler 60RCLA

Before you start

  • Purge trapped air to prevent block heater element failure.

Procedure

  1. Reconnect the generator set engine starting battery, negative (--) lead last.
  2. Reconnect the utility power to the generator set.
  3. Press the RUN button on the generator set controller; the generator set will start.
  4. Test run the generator set for a few minutes to check for coolant leaks and purge air.
  5. Stop the generator set; after the engine cools, correct any leakage.
  6. Recheck the coolant level and add coolant as necessary.
  7. Connect the block heater electrical plug to the power outlet.

Full service-parts list: Kohler 38RCL →, Kohler 48RCL →, Kohler 48RCLB →, Kohler 60RCL →, Kohler 60RCLA →

Source: Kohler service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.