Service parts for the 13ERG
Grouped by system, with how many of each the parts manual calls for.
Air intake
1 requiredFuel system
1 requiredOil system
1 requiredBelts
1 requiredPrices captured from merchant listings; some links are affiliate links. Confirm against your serial number before ordering.
Specifications
| Fuel | LP gas or gasoline |
|---|---|
| Frequency | 60.0 Hz |
| Standby power | 13 kW |
| Standby kVA | 13 |
| Controller | ADC 2100 |
Filters & service parts
model family| Item | Spec | Capacity | Part # | Interval | |
|---|---|---|---|---|---|
| Air filter | Cover, Spring clip(s), Housing, Pressure tap, Element, Dust ejector | A-226955 | 100 hr | Amazon eBay | |
| Fuel filter | GM34570 | 100 hr | Amazon eBay $34.05 | ||
| Oil filter | 358337 | 200 hr | Amazon eBay $45.17 NAPA $65.06 | ||
| Battery | — | ||||
| Belt | GM28353 | 1000 hr | Amazon eBay | ||
| Coolant | — | 800 hr | |||
| Coolant filter | — | ||||
| Oil | 3.5 L | — | 100 hr | ||
| Spark plug | GM35826 | 2000 hr | Amazon eBay $13.00 NAPA $2.64 |
Compiled from this model's family documentation — may include parts for closely-related variants. Confirm the exact part for your serial number.
Service intervals
8| Item | Action | Hours | Months | Notes |
|---|---|---|---|---|
| Lube oil filter element | Replace | 200 hr | ||
| Mounting bolts/vibromounts | Check | 200 hr | Check tightness | |
| Oil in the crankcase | Replace | 200 hr | ||
| Coolant protection and hose clamps | Check | 400 hr | Check coolant protection and tighten hose clamps | |
| Gasoline fuel filter | Replace | 400 hr | ||
| Cooling system | Other | 800 hr | Flush the cooling system | |
| Spark plugs | Replace | 800 hr | ||
| Slip rings and brushes | Clean | 1000 hr | Clean slip rings and inspect brushes |
Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.
Service specifications
18| Type | Item | Value | Unit | Condition |
|---|---|---|---|---|
| Clearance | Alternator/fan belt deflection | 0.5 | in. | finger pressure |
| Clearance | Alternator/fan belt deflection | 12.7 | mm | finger pressure |
| Gap | Spark plug gap | 0.031-0.035 | in. | |
| Gap | Spark plug gap | 0.8-0.9 | mm | |
| Pressure | LP vapor gas fuel system test pressure | 6-8 | oz./in.2 | 10-14 inches water column |
| Pressure | Pressure cap rating | 14 | psi | |
| Pressure | Pressure cap rating | 96.5 | kPa | |
| Speed | Overfrequency shutdown | 110% | % of frequency setpoint | more than 5 seconds |
| Speed | Overspeed shutdown | 115% | % of normal running speed | more than 0.3 seconds |
| Speed | Underfrequency shutdown | 90% | % of frequency setpoint | more than 5 seconds |
| Temperature | Thermostat rating | 195 | F | |
| Temperature | Thermostat rating | 91 | C | |
| Torque | Spark plug | 18 | ft. lbs. | |
| Torque | Spark plug | 25 | Nm | |
| Voltage | High battery voltage warning threshold, 12 VDC system | 16 | VDC | engine not running, more than 2 seconds |
| Voltage | High battery voltage warning threshold, 24 VDC system | 30 | VDC | engine not running, more than 2 seconds |
| Voltage | Low battery voltage warning threshold, 12 VDC system | 9.5 | VDC | engine not running, more than 2 seconds |
| Voltage | Low battery voltage warning threshold, 24 VDC system | 16 | VDC | engine not running, more than 2 seconds |
Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.
Recommended fluids
| Fluid | Grade | Standard | Ambient | Capacity | Notes |
|---|---|---|---|---|---|
| Coolant | 50% ethylene glycol and 50% clean, softened water | 7.6 L | 50% ethylene glycol provides freezing protection to -37 C (-34 F) and overheating protection to 129 C (265 F). Consult engine manufacturer's operation manual for engine coolant specifications. | ||
| Engine oil | 5W-30 | API Starburst certification mark for gasoline engines | below -18°C | 3.5 L | Recommended below -18 C (0 F) |
| Engine oil | 10W-30 | API Starburst certification mark for gasoline engines | above -18°C | 3.5 L | Recommended for -18 C (0 F) or above |
| Fuel | Clean, good-quality unleaded gasoline, octane number 87 or 89 | Use fresh gasoline; never mix oil with fuel |
Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.
Fault codes
14| Code | Name | Meaning | Severity | Action |
|---|---|---|---|---|
| AF | Auxiliary fault input shutdown | Input from a customer-supplied switch that closes when the fault is active. Shutdown occurs 0.3 seconds after the fault is detected and will not start when the fault is active (input is grounded). Protection becomes active 3 seconds after crank disconnect. | Shutdown | Check the cause of the auxiliary fault. |
| CO-3 | Fault displayed if the CO parameter is set incorrectly | Shutdown | ||
| CO-6 | Fault displayed if the CO parameter is set incorrectly | Shutdown | ||
| HB | High battery voltage warning | Fault code is displayed if the engine starting battery voltage rises above 16 VDC for a 12 VDC system or above 30 VDC for a 24 VDC system for more than 2 seconds when the engine is not running. Does not inhibit engine starting. Clears when battery voltage returns within limits for more than 2 seconds. | Warning | Check the battery rating and condition. |
| HE | High engine temperature shutdown | Shutdown occurs if the engine coolant temperature exceeds the maximum temperature for more than 5 seconds. Protection becomes active after the engine reaches crank disconnect speed. Functions only when the coolant level is in the operating range. | Shutdown | Check for a low engine coolant level. |
| LB | Low battery voltage warning | Fault code is displayed if the engine starting battery voltage falls below 9.5 VDC for a 12 VDC system or below 16 VDC for a 24 VDC system for more than 2 seconds when the engine is not running. Does not inhibit engine starting. Clears when battery voltage returns within limits for more than 2 seconds. | Warning | Check the battery rating and condition. Charge or replace the battery. |
| LOP | Low oil pressure shutdown | Shutdown occurs if a low oil pressure condition exists for more than 5 seconds. Protection becomes active 30 seconds after the engine has reached crank disconnect speed (30 second inhibit). | Shutdown | Check for leaks in the lubrication system. Check the oil level and add oil if the level is low. |
| OC | Overcrank shutdown | Shutdown occurs after 3 unsuccessful starting attempts. The crank cycle is set for three starting attempts. | Shutdown | Check the fuel supply and battery. If there is no output voltage, check the line circuit breaker. Also check for loose connections. Contact an authorized distributor/dealer if problem continues. |
| OF | Overfrequency shutdown | Shutdown occurs when the governed frequency exceeds 110% of the system's frequency setpoint for more than 5 seconds. Protection becomes active 10 seconds after engine start (10 second inhibit). | Shutdown | Contact an authorized distributor/dealer for service if problem continues. |
| OS | Overspeed shutdown | Shutdown occurs if the engine speed exceeds 115% of the normal running speed for more than 0.3 seconds. | Shutdown | Contact an authorized distributor/dealer for service if problem continues. |
| OU | Overvoltage shutdown | Shutdown occurs if the voltage exceeds 120% of the voltage regulator setpoint for more than 2 seconds. | Shutdown | Contact an authorized distributor/dealer for service if problem continues. |
| SCF0 | Controller error | Indicates a software or communication problem within the ADC 2100. | Shutdown | Contact an authorized distributor/dealer for service if problem continues. |
| UF | Underfrequency shutdown | Shutdown occurs when the governed frequency falls below 90% of the system's frequency setpoint for more than 5 seconds. Protection becomes active 10 seconds after engine start (10-second inhibit). | Shutdown | Reduce the load and restart the generator set. Contact an authorized distributor/dealer for service if problem continues. |
| UU | Undervoltage shutdown | Shutdown occurs if the voltage falls below 80% of the voltage regulator setpoint for more than 10 seconds. | Shutdown | Reduce the load and restart the generator set. Contact an authorized distributor/dealer for service if problem continues. |
Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.
Procedures
12Belt Tensioning Procedure adjustment
⚠ Also check the fan belt for cracks or tears and replace the belt if necessary.
- Disconnect the battery, negative lead first.
- Loosen the pivot and adjusting screws.
- While prying the battery charging alternator outward, tighten the adjusting screw.
- Tighten the pivot screw.
- Recheck and adjust as necessary.
- Reconnect the battery, negative lead last.
Controller Configuration adjustment
⚠ Be sure to save the new settings immediately before exiting the configuration mode; changes are lost if the controller times out (about 1 minute).
- Hold the Select button and move the master switch to RUN to enter configuration mode.
- Press the down arrow key then the up arrow key 3 times to enter configuration mode (password).
- Set the voltage/frequency parameter Uu for the model.
- Set the unit configuration parameter Uc (marine, standby, mobile).
- Set the engine type parameter Ec.
- Press the up arrow at the Adnc display to enter advanced configuration mode.
- Set the engine data input type Ed.
- Set the battery voltage Bt (12 or 24 VDC).
- Set the communications parameter Cn.
- Enter save mode and save your settings before exiting.
Output Voltage and Frequency Adjustment adjustment
⚠ The generator set must be running during these adjustments.
⚠ The engine speed (frequency) adjustment menus are not accessible on models with mechanical governors.
Tools: multimeter
- Move the master switch to RUN; the engine starts and runtime hours display.
- Hold the Select button about 5 seconds until the program version number displays.
- Press the down arrow key then the up arrow key 3 times to enter adjustment mode.
- 1P: adjust voltage coarse in large increments (approximately 5-7 volts per step).
- 2P: adjust voltage fine in smaller increments (approximately 0.5-0.7 volts per step).
- Adjust voltage stability (gain) coarse and fine.
- 3P: set volts/Hz (00=low, 09=high).
- 4P: adjust engine governor speed coarse and fine.
- 5P: adjust engine governor stability (gain) coarse and fine.
- Enter SAVE mode and save settings before exiting the adjustment mode.
Resetting the Controller after a Fault Shutdown diagnostic
⚠ Always identify and correct the cause of a fault shutdown before resetting the controller.
- Move the generator set master switch to the OFF/RESET position.
- Disconnect the generator set from the load using the line circuit breaker or ATS.
- Identify and correct the cause of the fault shutdown. Refer to Troubleshooting.
- Start the generator set by moving the master switch to RUN. Test operate to verify the cause is corrected.
- Shut the generator off by moving the master switch to the OFF/RESET position.
- Reconnect the generator set to the load using the line circuit breaker or ATS.
- Move the master switch to the AUTO position for startup by remote transfer switch, remote start/stop switch, or remote digital gauge.
Controller Replacement installation
⚠ Disconnect the battery cables before working on the generator set; remove the negative lead first and reconnect it last.
Tools: multimeter, personal computer with Program Loader Software
- Record generator set information required for configuration: model, market, voltage, frequency, phases, battery voltage.
- Place the generator set master switch in the OFF position.
- Disconnect power to the battery charger, if equipped.
- Disconnect the engine starting battery(ies), negative lead first.
- Open the junction box; disconnect the controller at P1, J15, and J16.
- Models ECD/EFCD, EGD/EFGD, EGZD only: disconnect the CO sensor harness at the 4-pin connector.
- Remove four controller mounting screws and remove the old controller.
- ECD/EFCD, EGD/EFGD, EGZD only: install CO sensor module assembly GM46362 on the back of the new controller GM47982.
- Install the new controller and secure with the mounting screws.
- Reconnect the P1, J15, and J16 connectors; connect the CO sensor harness on applicable models.
- Models 10/13/15EG, 10/13/15ERG, 15/30RES, 15/30RYG with S/N before 2053692: cut a 1-in. section of the gray/orange lead entering pin 9 at the ECM connector.
- Check that the generator set master switch is in the OFF position.
- Reconnect the engine starting battery, negative lead last.
- Reconnect power to the battery charger, if equipped.
- Check the controller application software version and load the latest application code if necessary.
Air Cleaner Service Procedure maintenance
⚠ Do not clean the element in any liquid or use compressed air as these will damage the filter element.
⚠ Do not operate the generator set with the air cleaner removed; a sudden backfire can cause severe injury or death.
- Release the spring clips to open the housing and remove the air silencer element.
- Tap the element lightly against a flat surface to dislodge loose surface dirt.
- Examine the element and housing for damage. Replace the element or housing if necessary.
- Wipe the cover and base with a clean rag. Make sure sealing surfaces fit correctly and reattach the spring clips.
Draining the Cooling System maintenance
⚠ Pay special attention to the coolant level.
- Remove the radiator's pressure cap to allow the entire system to drain and prevent air pockets.
- Open the radiator's coolant drain valve to drain the cooling system.
- After the coolant drains, allow time for complete refill of the engine water jacket and check the coolant level.
Filling the Cooling System maintenance
⚠ Do not add coolant to a hot engine; it can crack the cylinder block or cylinder head.
⚠ A coolant solution of 50% ethylene glycol provides freezing protection to -37 C (-34 F) and overheating protection to 129 C (265 F). Do not use alcohol or methanol antifreeze.
- Close the radiator's coolant drain valve and tighten the hose clamps.
- Fill the radiator with the recommended coolant mixture of 50% ethylene glycol and 50% clean, softened water.
- Replace the radiator's pressure cap.
- Operate the engine until the thermostat opens and the radiator upper hose becomes hot.
- Stop the engine and allow it to cool.
- Remove the radiator's pressure cap.
- Add coolant to the radiator to just below the overflow tube on the filler neck.
- Replace the radiator's pressure cap.
- Maintain the coolant level in the coolant overflow bottle between the High and Low markings.
Flushing and Cleaning Procedure maintenance
⚠ Before removing the pressure cap, stop the generator set and allow it to cool. Then loosen the pressure cap to relieve pressure.
- Remove the pressure cap, open the radiator's coolant drain valve and let the system drain completely.
- Drain, clean, and flush the coolant overflow bottle.
- Flush the system with clean water.
- Close the radiator's coolant drain valve.
- Fill the system with the recommended coolant.
- Replace the pressure cap.
Generator Storage Procedure maintenance
⚠ Run the generator set once a month whenever possible.
- Start and run the generator set until it reaches operating temperature or about 15 minutes.
- Stop the generator set.
- Change the oil and oil filter.
- Drain the fuel completely from the fuel tank.
- Check the engine coolant protection; use antifreeze capable of withstanding the lowest possible temperatures.
- Keep spark plugs in their holes or seal spark plug holes with suitable threaded metal plugs.
- Clean the exterior and spread a light film of oil or silicon spray over exposed surfaces.
- Seal the air inlet, exhaust pipe, and fuel tank cap with tape.
- Disconnect and remove the battery; store in a warm, dry location. Recharge the battery once a month.
- Select a well-ventilated (not humid or dusty) location to store the generator.
- Cover the entire unit with a dust cover.
Oil Change Procedure maintenance
⚠ Too high an oil level causes high oil consumption and engine carbonizing. Too low a level damages the engine.
⚠ Do not pollute the environment. Dispose of used engine oil in a safe, approved manner.
- Stop the generator set.
- To drain the oil, open the oil-drain valve.
- Drain the oil into a suitable container.
- Allow ample time for all oil to drain.
- Close the oil-drain valve.
- Remove the oil-fill cap.
- Replace the engine oil filter per the service schedule and Section 3.3.5.
- Fill crankcase with oil; replace the oil-fill cap.
- Start the generator set and check for oil leaks.
- Stop the generator set. Check the oil level. Add oil to bring the level to the Full mark.
Oil Filter Change Procedure maintenance
⚠ Wash hands after any contact with engine oil.
⚠ If also performing an oil change, skip steps 4 and 5 and go back to the oil change procedure.
- Loosen the oil filter by turning it counterclockwise. Remove the oil filter and clean up spilled oil.
- Clean the contact surface of the oil filter adapter.
- Lightly lubricate the gasket surface of the new filter with fresh engine oil. Thread on until the gasket contacts, then hand-tighten an additional one-half turn.
- Start the generator set and check for oil leaks.
- Stop the generator set. Check oil level. Add oil as necessary to bring level to the Full mark.
Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.
Voltage reconnection
| Voltage | Phase | Connection | Leads | Notes |
|---|---|---|---|---|
| 100 VAC | 1 | 1Ph, 2W | Uu00; 60 Hz | |
| 100 VAC | 1 | 1Ph, 3W | Uu00; 60 Hz | |
| 100/200 VAC | 1 | 1Ph, 3W | Uu08; 60 Hz | |
| 110 VAC | 1 | 1Ph, 2W | Uu05; 50 Hz | |
| 110 VAC | 1 | 1Ph, 3W | Uu05; 50 Hz | |
| 110/190 VAC | 3 | Wye | Uu17; 50 Hz | |
| 110/220 VAC | 1 | 1Ph, 3W | Uu07; 50 Hz | |
| 110/220 VAC | 1 | Dogleg | Uu07; 50 Hz | |
| 110/220 VAC | 3 | Delta | Uu15; 50 Hz | |
| 115 VAC | 1 | 1Ph, 2W | Uu05; 50 Hz | |
| 115/200 VAC | 3 | Wye | Uu23; 50 Hz | |
| 115/230 VAC | 1 | 1Ph, 3W | Uu02; 50 Hz | |
| 115/230 VAC | 1 | Dogleg | Uu06; 50 Hz | |
| 115/230 VAC | 3 | Delta | Uu14; 50 Hz | |
| 120 VAC | 1 | 1Ph, 2W | Uu00; 60 Hz | |
| 120 VAC | 1 | 1Ph, 3W | Uu00; 60 Hz | |
| 120/208 VAC | 3 | Wye | Uu11; 60 Hz | |
| 120/240 VAC | 1 | 1Ph, 3W | Uu01; 60 Hz | |
| 120/240 VAC | 1 | Dogleg | Uu01; 60 Hz | |
| 120/240 VAC | 3 | Delta | Uu10; 60 Hz | |
| 127/220 VAC | 3 | Wye | Uu16; 60 Hz | |
| 139/240 VAC | 3 | Wye | Uu10; 60 Hz | |
| 220 VAC | 1 | 1Ph, 2W | Uu12; 50 Hz | |
| 220/380 VAC | 3 | Wye | Uu19; 60 Hz | |
| 230 VAC | 1 | 1Ph, 2W | Uu02; 50 Hz | |
| 230/400 VAC | 3 | Wye | Uu03; 50 Hz | |
| 240 VAC | 1 | 1Ph, 2W | Uu13; 50 Hz | |
| 240/416 VAC | 3 | Wye | Uu20; 60 Hz | |
| 277/480 VAC | 3 | Wye | Uu04; 60 Hz |
Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.
Common questions
What size generator is the Kohler 13ERG?
The Kohler 13ERG is rated 13 kW standby (13.0 kVA).
What fuel does the Kohler 13ERG use?
The Kohler 13ERG runs on LP gas or gasoline.
What oil filter fits the Kohler 13ERG?
The Kohler 13ERG uses oil filter part number 358337.
What fuel filter does the Kohler 13ERG use?
The Kohler 13ERG uses fuel filter part number GM34570.
What air filter does the Kohler 13ERG use?
The Kohler 13ERG uses air filter part number A-226955.
Troubleshooting
6Symptoms & remedies
| Symptom | Cause | Remedy |
|---|---|---|
| Does not crank | Generator set master switch in the OFF position | Move the generator set master switch to the correct position (RUN or AUTO). |
| Crank but does not start | Controller fuse (F3) blown | Replace the blown controller fuse. If the fuse blows again, troubleshoot the controller. |
| Starts hard | Relay interface board fuse (F2) blown | Replace the blown relay interface board fuse. If the fuse blows again, troubleshoot the controller. |
| No or low output voltage | Auxiliary winding fuse (F1) blown | Replace the blown auxiliary winding fuse. If the fuse blows again, troubleshoot the controller. |
| Stops suddenly | Controller circuit breaker tripped | Reset the controller circuit breaker. |
| Lacks power | Controller master or start/stop switch inoperative | Replace the controller master or start/stop switch. |
Fault codes and symptom→remedy steps extracted from this model’s service/owner documentation; verify against the official manual before servicing. Full Kohler 13ERG troubleshooting guide (30 entries) →
Repair guides
9- Belt Tensioning Procedure
- Draining the Cooling System
- Filling the Cooling System
- Flushing and Cleaning Procedure
- Generator Storage Procedure
- Oil Filter Change Procedure
- Resetting the Controller after a Fault Shutdown
- Spark Plug Service Procedure
- Starting the Generator Set (Local and Auto)
Step-by-step procedures compiled from the Kohler service manual for this model.
Parts
24model family| Part # | Description | Qty | System | |
|---|---|---|---|---|
| A-226955 | Air cleaner assembly | 1 | Air filter | Amazon eBay |
| ADV6846A-A | Schematic Diagram (Sheet 1 of 2) | Schematic diagram | Amazon eBay | |
| GM16944 | Element, air cleaner | 1 | Air filter | Amazon eBay $49.68 NAPA $41.18 |
| GM28351 | Filter, oil | 1 | Oil filter | Amazon eBay $19.46 NAPA $9.09 |
| GM28353 | Belt, Poly-6V (40.75 in.) | 1 | Belt | Amazon eBay |
| GM32112-KA1 | Oil pressure sender kit (also -KP1) | Sensor | buy | |
| GM34570 | FILTER, SECONDARY FUEL | 1 | Fuel filter | Amazon eBay $34.05 |
| GM35299-KA1 | Sender kit (also -KP1) | Sensor | buy | |
| GM35826 | Spark plug | 4 | Spark plug | Amazon eBay $13.00 NAPA $2.64 |
| GM45891-KA1 | OP and WT sender kit | Sensor | buy | |
| GM46362 | CO sensor module assembly | 1 | Sensor | buy |
| GM50552-KA1 | Oil pressure sender kit | Sensor | buy | |
| 223316 | Fuse, 10 A, 250 V | 1 | Service part / kit | Amazon eBay $31.37 |
| 358337 | Fuse: Auxiliary Winding (F1) 10 Amp | 1 | Service part / kit | Amazon eBay $45.17 NAPA $65.06 |
| GM28483 | SCR module | Service part / kit | FridayParts $258.90 | |
| GM28707 | Controller Assy ADC 2100 | 1 | Service part / kit | buy |
| GM32337-KP1 | Remote Digital Gauge for Marine | Service part / kit | buy | |
| GM32337-KP2 | Remote Digital Gauge for Mobile and Residential/Commercial | Service part / kit | buy | |
| GM42037 | Controller Assy ADC 2100 | 1 | Service part / kit | buy |
| GM46035-KP1 | Three-Inch Digital Gauge | Service part / kit | buy | |
| GM46308-KP1 | Electronic governor kit | Service part / kit | buy | |
| GM47164-KP1 | Electronic governor kit | Service part / kit | buy | |
| GM47982 | Controller Assy ADC 2100 | 1 | Service part / kit | buy |
| GM50822-KP1 | Two-Inch Digital Gauge | Service part / kit | buy |
Compiled from this model's family documentation — may include parts for closely-related variants. Confirm the exact part for your serial number. See the full parts catalog to search and cross-reference.
Fuel consumption
| Rating | Load | L/h | gal/h |
|---|---|---|---|
| Standby | 25% | 2.91 | 0.77 |
| Standby | 50% | 4.24 | 1.12 |
| Standby | 75% | 5.75 | 1.52 |
| Standby | 100% | 6.89 | 1.82 |
Available documents