Kohler — Resetting the Controller after a Fault Shutdown

Testing & diagnosis · ADC 2100 controller

From a Kohler operator's manual covering: 10/13/15ERG, 10ERG, 13ERG, 15ERG, TP-6334. Check it applies to your exact model before use.

Applies to: Kohler 10ERG, Kohler 13ERG, Kohler 15ERG

Before you start

  • Always identify and correct the cause of a fault shutdown before resetting the controller.

Procedure

  1. Move the generator set master switch to the OFF/RESET position.
  2. Disconnect the generator set from the load using the line circuit breaker or ATS.
  3. Identify and correct the cause of the fault shutdown. Refer to Troubleshooting.
  4. Start the generator set by moving the master switch to RUN. Test operate to verify the cause is corrected.
  5. Shut the generator off by moving the master switch to the OFF/RESET position.
  6. Reconnect the generator set to the load using the line circuit breaker or ATS.
  7. Move the master switch to the AUTO position for startup by remote transfer switch, remote start/stop switch, or remote digital gauge.