Kohler — Resetting the Controller after a Fault Shutdown
Testing & diagnosis · ADC 2100 controller
From a Kohler operator's manual covering: 10/13/15ERG, 10ERG, 13ERG, 15ERG, TP-6334. Check it applies to your exact model before use.
Applies to: Kohler 10ERG, Kohler 13ERG, Kohler 15ERG
Before you start
- Always identify and correct the cause of a fault shutdown before resetting the controller.
Procedure
- Move the generator set master switch to the OFF/RESET position.
- Disconnect the generator set from the load using the line circuit breaker or ATS.
- Identify and correct the cause of the fault shutdown. Refer to Troubleshooting.
- Start the generator set by moving the master switch to RUN. Test operate to verify the cause is corrected.
- Shut the generator off by moving the master switch to the OFF/RESET position.
- Reconnect the generator set to the load using the line circuit breaker or ATS.
- Move the master switch to the AUTO position for startup by remote transfer switch, remote start/stop switch, or remote digital gauge.
Full service-parts list: Kohler 10ERG →, Kohler 13ERG →, Kohler 15ERG →
Source: Kohler operator's manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.