HomeKohlerKohler 15ERG

Kohler 15ERG Generator Set

The Kohler 15ERG is a 14 kW (14 kVA) Gasoline standby generator set. It operates at 60 Hz.

14 kW
Standby
3
Document types

How to read your Kohler serial & model number →

Specifications

FuelGasoline
Frequency60.0 Hz
Standby power14 kW
Standby kVA14
ControllerADC 2100

Filters & service parts

model family
ItemSpecCapacityPart #Interval
Air filterCover, Spring clip(s), Housing, Pressure tap, Element, Dust ejectorA-226955100 hr Amazon eBay $2.28 PartsGeek
Fuel filterGM34570100 hr Amazon eBay $23.36 PartsGeek
Oil filter358337200 hr PartsGeek
BeltGM283531000 hr Amazon eBay PartsGeek
Coolant800 hr
Coolant filter find
Oil3.5 L100 hr

Compiled from this model's family documentation — may include parts for closely-related variants. Confirm the exact part for your serial number.

Common questions

What is the power rating of the Kohler 15ERG?

The Kohler 15ERG is rated 14 kW standby (14.0 kVA).

What fuel does the Kohler 15ERG use?

The Kohler 15ERG runs on Gasoline.

Troubleshooting

32

Fault codes

CodeMeaningCauseRemedy
HBHigh battery voltage warningEngine starting battery voltage rises above 16 VDC for a 12 VDC system or above 30 VDC for a 24 VDC system for more than 2 seconds when the engine is not running.Check the battery rating and condition.
LBLow battery voltage warningEngine starting battery voltage falls below 9.5 VDC for a 12 VDC system or below 16 VDC for a 24 VDC system for more than 2 seconds when the engine is not running.Check the battery rating and condition. Charge or replace the battery.

Symptoms & remedies

SymptomCauseRemedy
The generator set is not running.Block heater damage; the block heater will fail if the energized heater element is not immersed in coolant. Fill the cooling system before turning on the block heater. Run the engine until it is warm and refill the radiator to purge the air from the system before energizing the block heater.
Hot engine and exhaust system.Do not work on the generator set until it cools.
Does not crankGenerator set master switch in the OFF positionMove the generator set master switch to the correct position (RUN or AUTO).
Crank but does not startController fuse (F3) blownReplace the blown controller fuse. If the fuse blows again, troubleshoot the controller.
Starts hardRelay interface board fuse (F2) blownReplace the blown relay interface board fuse. If the fuse blows again, troubleshoot the controller.
No or low output voltageAuxiliary winding fuse (F1) blownReplace the blown auxiliary winding fuse. If the fuse blows again, troubleshoot the controller.
Stops suddenlyController circuit breaker trippedReset the controller circuit breaker.
Lacks powerController master or start/stop switch inoperativeReplace the controller master or start/stop switch.
OverheatsCooling System: Air openings cloggedClean the air openings.
Fault shutdownReset the controller.Section 2
Starter/starter solenoid inoperativeReplace the starter or starter solenoid. Eng. S/M
Faulty ground connectionClean and retighten the connection. —
Air cleaner/backfire flame arrestor cloggedClean or replace the filter element. Section 2
Compression weakCheck the compression. Eng. S/M
Engine overloadReduce the electrical load. See the generator set installation manual for wattage specifications. I/M
Exhaust system leakInspect the exhaust system. Replace the inoperative exhaust system components. Section 3, I/M
Exhaust system not securely installedInspect the exhaust system. Tighten the loose exhaust system components. Section 3, I/M
Overspeed shutdownReset the controller. If the overspeed fault occurs again, contact the distributor/dealer. Section 2
Valve clearance incorrectAdjust the valves. Eng. S/M
Vibration excessiveTighten all loose hardware. —
Ignition system inoperative (gas/gasoline only)Check the ignition system (ignition module, spark plugs, spark plug wires, etc.). Eng. O/M
AC output circuit breaker openReset the breaker and check for AC voltage at the generator side of the circuit breaker. —
Overcrank shutdownReset the controller. If the overcrank fault occurs again, contact the distributor/dealer. —
Transfer switch test switch in the OFF positionMove the transfer switch test switch to the AUTO position. ATS O/M
Wiring, terminals, or pin in the exciter field openCheck for continuity. Gen. S/M, W/D
Main field (rotor) inoperative (open or grounded)Test and/or replace the rotor. Gen. S/M
Stator inoperative (open or grounded)Test and/or replace the stator. Gen. S/M
Shutdown occurs when the governed frequency falls below 90% of the system’s frequency setpoint for more than 5 seconds.Reduce the load and restart the generator set. Contact an authorized distributor/dealer for service if problem continues.
Shutdown occurs if the voltage falls below 80% of the voltage regulator setpoint for more than 10 seconds.Reduce the load and restart the generator set. Contact an authorized distributor/dealer for service if problem continues.
Controller errorIndicates a software or communication problem within the ADC 2100.Contact an authorized distributor/dealer for service if problem continues.

Fault codes and symptom→remedy steps extracted from this model’s service/owner documentation; verify against the official manual before servicing.

Parts

1
Part #DescriptionQtySystem
G-585Unacceptable Nut/Bolt Clearance2Service part / kit PartsGeek

Service, wear & replacement parts referenced for this model and its engine — confirm the exact part for your serial number. See the full parts catalog to search and cross-reference.

Fuel consumption

RatingLoadL/hgal/h
25%3.370.89
50%4.921.3
75%6.621.75
100%7.952.1
Prime
Standby

Available documents

Spec sheet (Kohler)Installation manual — tt1364 (Kohler)Reference — TP-6337 Kohler 10,13,15ERG Service Parts (Kohler)Service manual — TP-6334, 10,13,15ERG Operators Manual (Kohler)Service manual — TP-6335 15ERG, 13ERG, 10ERG 95342 Installation Manual (Kohler)