ADC 2100 Controller

The ADC 2100 is a generator-set controller. It is used on generator sets from Kohler, including the 10EOZ, 10ERG, 11.5EFOZD and 11EFOZD.

108
Generator sets
Kohler
Brand
7–40 kW
Power range
5
Fuel types

Troubleshooting

60

Fault codes

CodeMeaningCauseRemedy
AFAuxiliary fault input shutdownIndicates a shutdown initiated by pushing the emergency stop switch. (TRES models only)Check the position of the emergency stop button. (TRES models only)
AFIndicates a shutdown initiated by pushing the emergency stop switch.Not used on RES models.Check the position of the emergency stop button. (TRES models only)
AFInput from a customer-supplied switch that closes when the fault is active. The generator set shuts down and will not start when the fault is active (input is grounded).Check the cause of the auxiliary fault.
Auxiliary faultAuxiliary fault
Auxiliary faultUnspecified auxiliary issue
HBFault code is displayed if the engine starting battery voltage rises above 16 VDC for a 12 VDC system or above 30 VDC for a 24 VDC system for more than 10 seconds when the engine is not running. This fault condition does not inhibit engine starting.Check the battery rating and condition. Check the battery charger operation.
HBHigh battery voltage warningFault code is displayed if the engine starting battery voltage rises above 16 VDC for more than 30 seconds when the engine is running. Not operative during the engine crank cycle, this fault condition does not inhibit engine starting.Check the battery rating and condition. Check the battery charger operation.
HEHigh engine temperature shutdownShutdown occurs if the engine coolant temperature exceeds the maximum temperature for more than 5 seconds. This function becomes active after the engine reaches the crank disconnect speed.Check for blocked air inlets and exhaust outlets.
HEShutdown occurs if the engine coolant temperature exceeds the maximum temperature for more than 5 seconds. This protective becomes active after the engine reaches the crank disconnect speed.Check for blocked air inlets and exhaust outlets.
High battery voltageBattery voltage exceeds normal range
High battery voltageHigh battery voltage
High engine temperatureEngine overheating
High engine temperatureEngine runtime, hours
High engine temperatureHigh engine temperature
High engine temperatureHigh engine temperature shutdown
LBFault code is displayed if the engine starting battery voltage falls below 8 VDC for a 12 VDC system or below 16 VDC for a 24 VDC system for more than 10 seconds when the engine is not running. This fault condition does not inhibit engine starting.Check the battery rating and condition. Check the battery charger operation.Charge or replace the battery.
LBLow battery voltage warningFault code is displayed if the engine starting battery voltage falls below 11 VDC for more than 30 seconds when the engine is not running. Not operative during the engine crank cycle, this fault condition does not inhibit engine starting.
LOPLow oil pressure shutdownShutdown occurs if a low oil pressure condition exists for more than 5 seconds. This function becomes active 30 seconds after the engine has reached crank disconnect speed (30 second inhibit). Note: The low oil pressure shutdown does not protect against low oil level. Check the oil level at the engine.Check for leaks in the lubrication system. Check the oil level and add oil if the level is low.
LOPShutdown occurs if a low oil pressure condition exists 7 seconds after the engine has reached crank disconnect speed.Note: The low oil pressure shutdown does not protect against low oil level. Check the oil level at the engine. Check for leaks in the lubrication system.Check the oil level and add oil if the level is low.
Locked rotorThe generator set also shuts down on OC if no engine rotation is sensed during cranking. Shuts down 3 seconds after the fault is detected.
Loss of coolantLoss of coolant
Loss of coolantSeawater pump impeller failure shutdown
Low battery voltageBattery voltage is below normal
Low battery voltageCrank cycle status
Low battery voltageLow battery voltage
Low oil pressureLow oil pressure
Low oil pressureLow oil pressure shutdown
Low oil pressureOil pressure is too low
OCOvercrank shutdownShutdown occurs after 3 unsuccessful starting attempts. The crank cycle is set for three starting attempts of 15 seconds cranking and 15 seconds rest.Check the fuel supply, spark plug, and battery. Check for loose connections. Contact an authorized distributor/dealer for service if problem continues.
OCShutdown occurs after 3 unsuccessful starting attempts. The crank cycle is set for three starting attempts of 15 seconds cranking and 15 seconds rest. The generator set also shuts down after 1 crank attempt if no speed signal is sensed. Shuts down 1 second after the fault is detected.Check the fuel supply, spark plug, and battery. Check for loose connections.Contact an authorized distributor/dealer for service if problem continues.
OFOverfrequency shutdownShutdown occurs when the governed frequency exceeds 110% of the system’s frequency setpoint for more than 5 seconds. This function becomes active 10 seconds after engine start (10 second inhibit).Contact an authorized distributor/dealer for service if problem continues.
OFShutdown occurs when the governed frequency exceeds 110% of the system’s frequency setpoint for more than 1 second. This protective becomes active 30 seconds after engine start.Contact an authorized distributor/dealer for service if problem continues.
OSOverspeed shutdownShutdown occurs if the engine speed exceeds 110% of the normal running speed for more than 0.3 seconds.Contact an authorized distributor/dealer for service if problem continues.
OSShutdown occurs if the engine speed exceeds 115% of the normal running speed for more than 1 second.Contact an authorized distributor/dealer for service if problem continues.
OUOvervoltage shutdownShutdown occurs if the voltage exceeds 120% of the system nominal voltage for more than 2 seconds.Contact an authorized distributor/dealer for service if problem continues.
OUShutdown occurs if the voltage exceeds 120% of the voltage regulator setpoint for more than 1 second.Contact an authorized distributor/dealer for service if problem continues.
Over/under frequencyFrequency deviates from nominal value
Over/under frequencyOver/under frequency
Over/under voltageOver/under voltage
Over/under voltageVoltage is outside the normal range
OvercrankRemote two-wire start/stop capability
Overcrank safetyExcessive cranking duration
Overcrank safetyOvercrank safety
Overcrank safetyOverspeed
OverfrequencyDigital voltage regulation: ±1.5% RMS no-load to full-load
OverspeedAutomatic start for programmed cranking cycle
OverspeedEngine speed exceeds safe limits
UFShutdown occurs when the governed frequency falls 1 Hz below the system’s frequency setpoint for more than 1 second.Reduce the load and restart the generator set. Contact an authorized distributor/dealer for service if problem continues.
UFUnderfrequency shutdownShutdown occurs if the governed frequency falls below 54 Hz for more than 5 seconds. Shutdown also occurs if the governed frequency falls below 56.5 Hz for more than 60 seconds. This function becomes active 10 seconds after engine start. (10 second inhibit).Reduce the load and restart the generator set. Contact an authorized distributor/dealer for service if problem continues.
UUShutdown occurs if the voltage falls below 80% of the voltage regulator setpoint for more than 1 second. This protective becomes active 30 seconds after engine start.Reduce the load and restart the generator set. Contact an authorized distributor/dealer for service if problem continues.
UUUndervoltage shutdownShutdown occurs if the voltage falls below 80% of the nominal system voltage for more than 10 seconds.Reduce the load and restart the generator set. Contact an authorized distributor/dealer for service if problem continues.
UnderfrequencyMaster control switch mounted on the junction box: Run/Off-Reset/Auto
UndervoltageUpgradeable application software

Symptoms & remedies

SymptomRemedy
AC output circuit breaker openReset the breaker and check for AC voltage at the generator side of the circuit breaker. —
Accidental startingDisconnect the battery cables before working on the generator set. Remove the negative (--) lead first when disconnecting the battery. Reconnect the negative (--) lead last when reconnecting the battery.
Air cleaner/backfire flame arrestor cloggedClean or replace the filter element. Section 2
Alternator or control system problemPerform separate excitation procedure to isolate the problem to the alternator or the control system. Then troubleshoot the alternator or control system components as follows.
Auxiliary winding fuse (F1) blownReplace the fuse. Contact an authorized distributor/dealer for service if fuse blows repeatedly.
Battery acid is electrically conductive and corrosive.Add 500 g (1 lb.) of bicarbonate of soda (baking soda) to a container with 4 L (1 gal.) of water and mix the neutralizing solution. Pour the neutralizing solution on the spilled battery acid and continue to add the neutralizing solution to the spilled battery acid until all evidence of a chemical reaction (foaming) has ceased. Flush the resulting liquid with water and dry the area.
Battery short circuitDisconnect the battery before generator set installation or maintenance. Remove all jewelry before servicing the equipment. Use tools with insulated handles. Remove the negative (--) lead first when disconnecting the battery. Reconnect the negative (--) lead last when reconnecting the battery. Never connect the negative (--) battery cable to the positive (+) connection terminal of the starter solenoid. Do not test the battery condition by shorting the terminals together.

Fault codes and symptom→remedy steps extracted from this controller’s service/owner documentation; verify against the official manual before servicing. Aggregated from the service documentation of generator sets built on this controller.