Specifications
| Fuel | Diesel |
|---|---|
| Frequency | 50.0 Hz |
| Standby power | 9 kW |
| Standby kVA | 9 |
| Controller | ADC 2100 |
Maintenance & consumables
| Item | Spec | Capacity | Part # | Interval | |
|---|---|---|---|---|---|
| Oil filter | — |
Fault codes
2| Code | Name | Meaning | Severity | Action |
|---|---|---|---|---|
| CO-3 | Fault displayed if the CO parameter is set incorrectly | Shutdown | ||
| CO-6 | Fault displayed if the CO parameter is set incorrectly | Shutdown |
Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.
Procedures
3Controller Configuration adjustment
⚠ Be sure to save the new settings immediately before exiting the configuration mode; changes are lost if the controller times out (about 1 minute).
- Hold the Select button and move the master switch to RUN to enter configuration mode.
- Press the down arrow key then the up arrow key 3 times to enter configuration mode (password).
- Set the voltage/frequency parameter Uu for the model.
- Set the unit configuration parameter Uc (marine, standby, mobile).
- Set the engine type parameter Ec.
- Press the up arrow at the Adnc display to enter advanced configuration mode.
- Set the engine data input type Ed.
- Set the battery voltage Bt (12 or 24 VDC).
- Set the communications parameter Cn.
- Enter save mode and save your settings before exiting.
Output Voltage and Frequency Adjustment adjustment
⚠ The generator set must be running during these adjustments.
⚠ The engine speed (frequency) adjustment menus are not accessible on models with mechanical governors.
Tools: multimeter
- Move the master switch to RUN; the engine starts and runtime hours display.
- Hold the Select button about 5 seconds until the program version number displays.
- Press the down arrow key then the up arrow key 3 times to enter adjustment mode.
- 1P: adjust voltage coarse in large increments (approximately 5-7 volts per step).
- 2P: adjust voltage fine in smaller increments (approximately 0.5-0.7 volts per step).
- Adjust voltage stability (gain) coarse and fine.
- 3P: set volts/Hz (00=low, 09=high).
- 4P: adjust engine governor speed coarse and fine.
- 5P: adjust engine governor stability (gain) coarse and fine.
- Enter SAVE mode and save settings before exiting the adjustment mode.
Controller Replacement installation
⚠ Disconnect the battery cables before working on the generator set; remove the negative lead first and reconnect it last.
Tools: multimeter, personal computer with Program Loader Software
- Record generator set information required for configuration: model, market, voltage, frequency, phases, battery voltage.
- Place the generator set master switch in the OFF position.
- Disconnect power to the battery charger, if equipped.
- Disconnect the engine starting battery(ies), negative lead first.
- Open the junction box; disconnect the controller at P1, J15, and J16.
- Models ECD/EFCD, EGD/EFGD, EGZD only: disconnect the CO sensor harness at the 4-pin connector.
- Remove four controller mounting screws and remove the old controller.
- ECD/EFCD, EGD/EFGD, EGZD only: install CO sensor module assembly GM46362 on the back of the new controller GM47982.
- Install the new controller and secure with the mounting screws.
- Reconnect the P1, J15, and J16 connectors; connect the CO sensor harness on applicable models.
- Models 10/13/15EG, 10/13/15ERG, 15/30RES, 15/30RYG with S/N before 2053692: cut a 1-in. section of the gray/orange lead entering pin 9 at the ECM connector.
- Check that the generator set master switch is in the OFF position.
- Reconnect the engine starting battery, negative lead last.
- Reconnect power to the battery charger, if equipped.
- Check the controller application software version and load the latest application code if necessary.
Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.
Voltage reconnection
| Voltage | Phase | Connection | Leads | Notes |
|---|---|---|---|---|
| 100 VAC | 1 | 1Ph, 2W | Uu00; 60 Hz | |
| 100 VAC | 1 | 1Ph, 3W | Uu00; 60 Hz | |
| 100/200 VAC | 1 | 1Ph, 3W | Uu08; 60 Hz | |
| 110 VAC | 1 | 1Ph, 2W | Uu05; 50 Hz | |
| 110 VAC | 1 | 1Ph, 3W | Uu05; 50 Hz | |
| 110/190 VAC | 3 | Wye | Uu17; 50 Hz | |
| 110/220 VAC | 1 | 1Ph, 3W | Uu07; 50 Hz | |
| 110/220 VAC | 1 | Dogleg | Uu07; 50 Hz | |
| 110/220 VAC | 3 | Delta | Uu15; 50 Hz | |
| 115 VAC | 1 | 1Ph, 2W | Uu05; 50 Hz | |
| 115/200 VAC | 3 | Wye | Uu23; 50 Hz | |
| 115/230 VAC | 1 | 1Ph, 3W | Uu02; 50 Hz | |
| 115/230 VAC | 1 | Dogleg | Uu06; 50 Hz | |
| 115/230 VAC | 3 | Delta | Uu14; 50 Hz | |
| 120 VAC | 1 | 1Ph, 2W | Uu00; 60 Hz | |
| 120 VAC | 1 | 1Ph, 3W | Uu00; 60 Hz | |
| 120/208 VAC | 3 | Wye | Uu11; 60 Hz | |
| 120/240 VAC | 1 | 1Ph, 3W | Uu01; 60 Hz | |
| 120/240 VAC | 1 | Dogleg | Uu01; 60 Hz | |
| 120/240 VAC | 3 | Delta | Uu10; 60 Hz | |
| 127/220 VAC | 3 | Wye | Uu16; 60 Hz | |
| 139/240 VAC | 3 | Wye | Uu10; 60 Hz | |
| 220 VAC | 1 | 1Ph, 2W | Uu12; 50 Hz | |
| 220/380 VAC | 3 | Wye | Uu19; 60 Hz | |
| 230 VAC | 1 | 1Ph, 2W | Uu02; 50 Hz | |
| 230/400 VAC | 3 | Wye | Uu03; 50 Hz | |
| 240 VAC | 1 | 1Ph, 2W | Uu13; 50 Hz | |
| 240/416 VAC | 3 | Wye | Uu20; 60 Hz | |
| 277/480 VAC | 3 | Wye | Uu04; 60 Hz |
Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.
Common questions
How many kW is the Kohler 9EFOZ?
The Kohler 9EFOZ is rated 9 kW standby (9.0 kVA).
What kind of fuel does the Kohler 9EFOZ run on?
The Kohler 9EFOZ runs on Diesel.
Parts
2| Part # | Description | Qty | System | |
|---|---|---|---|---|
| 344089 | Seawater pump | 1 | Pump | Amazon eBay |
| 344606 | Seawater pump pulley | 1 | Pump | Amazon eBay |
Service, wear & replacement parts referenced for this model and its engine — confirm the exact part for your serial number. See the full parts catalog to search and cross-reference.
Fuel consumption
| Rating | Load | L/h | gal/h |
|---|---|---|---|
| 25% | 1.3 | 0.35 | |
| 50% | 2.0 | 0.53 | |
| 75% | 2.7 | 0.72 | |
| 100% | 4.0 | 1.05 |
Available documents