HomeKohlerKohler 9EOZD

Kohler 9EOZD Generator Set

The Kohler 9EOZD is a 8.5 kW (8.5 kVA) Diesel standby generator set. It operates at 60 Hz.

8 kW
Standby
3
Document types

How to read your Kohler serial & model number →

Typical fuel consumption for 5–10 kW Diesel generators →

Compare with other 5–10 kW Diesel generators →

Specifications

FuelDiesel
Frequency60.0 Hz
Standby power8 kW
Standby kVA8
EmissionsTier 4
ControllerADC 2100

Filters & service parts

model family
ItemSpecCapacityPart #Interval
Air filterOne-side serviceability of air cleaner
Fuel filter
Oil filter
BeltBelt guard, Focused vibromounts
Coolant
OilLubricating System

Compiled from this model's family documentation — may include parts for closely-related variants. Confirm the exact part for your serial number.

Fault codes

2
CodeNameMeaningSeverityAction
CO-3Fault displayed if the CO parameter is set incorrectlyShutdown
CO-6Fault displayed if the CO parameter is set incorrectlyShutdown

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Procedures

3
Controller Configuration adjustment

⚠ Be sure to save the new settings immediately before exiting the configuration mode; changes are lost if the controller times out (about 1 minute).

  1. Hold the Select button and move the master switch to RUN to enter configuration mode.
  2. Press the down arrow key then the up arrow key 3 times to enter configuration mode (password).
  3. Set the voltage/frequency parameter Uu for the model.
  4. Set the unit configuration parameter Uc (marine, standby, mobile).
  5. Set the engine type parameter Ec.
  6. Press the up arrow at the Adnc display to enter advanced configuration mode.
  7. Set the engine data input type Ed.
  8. Set the battery voltage Bt (12 or 24 VDC).
  9. Set the communications parameter Cn.
  10. Enter save mode and save your settings before exiting.
Output Voltage and Frequency Adjustment adjustment

⚠ The generator set must be running during these adjustments.

⚠ The engine speed (frequency) adjustment menus are not accessible on models with mechanical governors.

Tools: multimeter

  1. Move the master switch to RUN; the engine starts and runtime hours display.
  2. Hold the Select button about 5 seconds until the program version number displays.
  3. Press the down arrow key then the up arrow key 3 times to enter adjustment mode.
  4. 1P: adjust voltage coarse in large increments (approximately 5-7 volts per step).
  5. 2P: adjust voltage fine in smaller increments (approximately 0.5-0.7 volts per step).
  6. Adjust voltage stability (gain) coarse and fine.
  7. 3P: set volts/Hz (00=low, 09=high).
  8. 4P: adjust engine governor speed coarse and fine.
  9. 5P: adjust engine governor stability (gain) coarse and fine.
  10. Enter SAVE mode and save settings before exiting the adjustment mode.
Controller Replacement installation

⚠ Disconnect the battery cables before working on the generator set; remove the negative lead first and reconnect it last.

Tools: multimeter, personal computer with Program Loader Software

  1. Record generator set information required for configuration: model, market, voltage, frequency, phases, battery voltage.
  2. Place the generator set master switch in the OFF position.
  3. Disconnect power to the battery charger, if equipped.
  4. Disconnect the engine starting battery(ies), negative lead first.
  5. Open the junction box; disconnect the controller at P1, J15, and J16.
  6. Models ECD/EFCD, EGD/EFGD, EGZD only: disconnect the CO sensor harness at the 4-pin connector.
  7. Remove four controller mounting screws and remove the old controller.
  8. ECD/EFCD, EGD/EFGD, EGZD only: install CO sensor module assembly GM46362 on the back of the new controller GM47982.
  9. Install the new controller and secure with the mounting screws.
  10. Reconnect the P1, J15, and J16 connectors; connect the CO sensor harness on applicable models.
  11. Models 10/13/15EG, 10/13/15ERG, 15/30RES, 15/30RYG with S/N before 2053692: cut a 1-in. section of the gray/orange lead entering pin 9 at the ECM connector.
  12. Check that the generator set master switch is in the OFF position.
  13. Reconnect the engine starting battery, negative lead last.
  14. Reconnect power to the battery charger, if equipped.
  15. Check the controller application software version and load the latest application code if necessary.

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Voltage reconnection

VoltagePhaseConnectionLeadsNotes
100 VAC11Ph, 2WUu00; 60 Hz
100 VAC11Ph, 3WUu00; 60 Hz
100/200 VAC11Ph, 3WUu08; 60 Hz
110 VAC11Ph, 2WUu05; 50 Hz
110 VAC11Ph, 3WUu05; 50 Hz
110/190 VAC3WyeUu17; 50 Hz
110/220 VAC11Ph, 3WUu07; 50 Hz
110/220 VAC1DoglegUu07; 50 Hz
110/220 VAC3DeltaUu15; 50 Hz
115 VAC11Ph, 2WUu05; 50 Hz
115/200 VAC3WyeUu23; 50 Hz
115/230 VAC11Ph, 3WUu02; 50 Hz
115/230 VAC1DoglegUu06; 50 Hz
115/230 VAC3DeltaUu14; 50 Hz
120 VAC11Ph, 2WUu00; 60 Hz
120 VAC11Ph, 3WUu00; 60 Hz
120/208 VAC3WyeUu11; 60 Hz
120/240 VAC11Ph, 3WUu01; 60 Hz
120/240 VAC1DoglegUu01; 60 Hz
120/240 VAC3DeltaUu10; 60 Hz
127/220 VAC3WyeUu16; 60 Hz
139/240 VAC3WyeUu10; 60 Hz
220 VAC11Ph, 2WUu12; 50 Hz
220/380 VAC3WyeUu19; 60 Hz
230 VAC11Ph, 2WUu02; 50 Hz
230/400 VAC3WyeUu03; 50 Hz
240 VAC11Ph, 2WUu13; 50 Hz
240/416 VAC3WyeUu20; 60 Hz
277/480 VAC3WyeUu04; 60 Hz

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Common questions

What is the power rating of the Kohler 9EOZD?

The Kohler 9EOZD is rated 8 kW standby (8.5 kVA).

What fuel does the Kohler 9EOZD use?

The Kohler 9EOZD runs on Diesel.

Parts

15model family
Part #DescriptionQtySystem
GM32112-KA1Oil pressure sender kit (also -KP1)Sensor buy
GM35299-KA1Sender kit (also -KP1)Sensor buy
GM45891-KA1OP and WT sender kitSensor buy
GM46362CO sensor module assembly1Sensor buy
GM50552-KA1Oil pressure sender kitSensor buy
GM28483SCR moduleService part / kit FridayParts $258.90
GM28707Controller Assy ADC 21001Service part / kit buy
GM32337-KP1Remote Digital Gauge for MarineService part / kit buy
GM32337-KP2Remote Digital Gauge for Mobile and Residential/CommercialService part / kit buy
GM42037Controller Assy ADC 21001Service part / kit buy
GM46035-KP1Three-Inch Digital GaugeService part / kit buy
GM46308-KP1Electronic governor kitService part / kit buy
GM47164-KP1Electronic governor kitService part / kit buy
GM47982Controller Assy ADC 21001Service part / kit buy
GM50822-KP1Two-Inch Digital GaugeService part / kit buy

Compiled from this model's family documentation — may include parts for closely-related variants. Confirm the exact part for your serial number. See the full parts catalog to search and cross-reference.

Fuel consumption

RatingLoadL/hgal/h
25%1.30.35
50%1.80.47
75%2.50.65
100%3.30.86

Available documents

Spec sheet (Kohler)Spec sheet — 9EOZD (Kohler)Reference (Kohler)Reference — G18095 (Kohler)Service manual — tt1364 (Kohler)