Service parts for the 30REYG
Grouped by system, with how many of each the parts manual calls for.
Air intake
1 requiredPrices captured from merchant listings; some links are affiliate links. Confirm against your serial number before ordering.
Specifications
| Fuel | Natural Gas |
|---|---|
| Frequency | 60.0 Hz |
| Standby power | 27 kW |
| Standby kVA | 27 |
| Controller | ADC 2100, Advanced Digital (ADC 2100) |
| Oil capacity | 3.5 L |
| Alternator | 2F7 (2-pole, Class Class H insulation) |
| Coolant capacity | 11.5 L |
| Engine jacket water | 3.3 L |
Engine
| Oil capacity | 3.5 L |
|---|---|
| Coolant capacity | 11.5 L |
| Displacement | 1.6 L |
| Rated speed | 3600 rpm |
Maintenance & consumables
for the General Motors GM 1.6L OHC| Item | Spec | Capacity | Part # | Interval | |
|---|---|---|---|---|---|
| Air filter | Dry | ×1 | GM16944 | Amazon eBay $49.68 NAPA $41.18 | |
| Fuel filter | — | ||||
| Oil filter | Cartridge | ×1 | GM28351 | Amazon eBay $19.46 NAPA $9.09 | |
| Battery | 525 CCA, 12 V DC | — | |||
| Belt | — | ||||
| Coolant | 11.5 L | — | 1000 hr | ||
| Oil | 3.5 L | — | 200 hr | ||
| Spark plug | — | 1000 hr |
Fault codes
16| Code | Name | Meaning | Severity | Action |
|---|---|---|---|---|
| AF | Auxiliary fault | FMI 2, SPN 0x02BD | ||
| CC | Crank cycle | |||
| CO-3 | Fault displayed if the CO parameter is set incorrectly | Shutdown | ||
| CO-6 | Fault displayed if the CO parameter is set incorrectly | Shutdown | ||
| HB | High battery voltage | FMI 0, SPN 0x00A8 | ||
| HE | High engine temp | FMI 0, SPN 0x006E | ||
| LB | Low battery voltage | FMI 1, SPN 0x00A8 | ||
| LCL | Low coolant level | FMI 1, SPN 0x006F | ||
| LOC | Loss of coolant | FMI 1, SPN 0x006F | ||
| LOP | Low oil pressure | FMI 1, SPN 0x0064 | ||
| OC | Overcrank | FMI 0, SPN 0x068B | ||
| OF | Overfrequency | FMI 0, SPN 0x0984 | ||
| OS | Overspeed | FMI 0, SPN 0x00BE | ||
| OU | Overvoltage | FMI 0, SPN 0x0988 | ||
| UF | Underfrequency | FMI 1, SPN 0x0984 | ||
| UU | Undervoltage | FMI 1, SPN 0x0988 |
Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.
Procedures
12ADC-RES Controller Configuration (Cn setting) adjustment
⚠ The controller automatically exits configuration mode without saving changes after about 1 minute if no buttons are pressed.
- Enter the configuration mode while the engine is not running by following the Figure 26 sequence.
- Step through the parameters to the communication setting Cn parameter.
- Use the up and down arrow buttons to change the Cn setting to Cn01, if necessary.
- Press to SAVE CHANGES (YES) before exiting the configuration mode.
- Move the generator set master switch to OFF/RESET.
Controller Configuration adjustment
⚠ Be sure to save the new settings immediately before exiting the configuration mode; changes are lost if the controller times out (about 1 minute).
- Hold the Select button and move the master switch to RUN to enter configuration mode.
- Press the down arrow key then the up arrow key 3 times to enter configuration mode (password).
- Set the voltage/frequency parameter Uu for the model.
- Set the unit configuration parameter Uc (marine, standby, mobile).
- Set the engine type parameter Ec.
- Press the up arrow at the Adnc display to enter advanced configuration mode.
- Set the engine data input type Ed.
- Set the battery voltage Bt (12 or 24 VDC).
- Set the communications parameter Cn.
- Enter save mode and save your settings before exiting.
Output Voltage and Frequency Adjustment adjustment
⚠ The generator set must be running during these adjustments.
⚠ The engine speed (frequency) adjustment menus are not accessible on models with mechanical governors.
Tools: multimeter
- Move the master switch to RUN; the engine starts and runtime hours display.
- Hold the Select button about 5 seconds until the program version number displays.
- Press the down arrow key then the up arrow key 3 times to enter adjustment mode.
- 1P: adjust voltage coarse in large increments (approximately 5-7 volts per step).
- 2P: adjust voltage fine in smaller increments (approximately 0.5-0.7 volts per step).
- Adjust voltage stability (gain) coarse and fine.
- 3P: set volts/Hz (00=low, 09=high).
- 4P: adjust engine governor speed coarse and fine.
- 5P: adjust engine governor stability (gain) coarse and fine.
- Enter SAVE mode and save settings before exiting the adjustment mode.
Network Bridge Diagnostics diagnostic
- Check the network LEDs on the RJ45 connector for Ethernet network communication.
- Check the STAT LED; if not lit, check connections and the engine starting battery.
- Check the TX and RX LEDs for CAN data transmission and reception.
- If neither the TX nor the RX LED flashes, check bridge power, connections, and settings.
- If only one of the TX or RX LEDs flashes, check the connected devices on the generator set (CAN) side.
15/30RES and 15/30RYG Bridge Installation (GM62630-KP2) installation
- Remove the junction box panel to gain access to the inside of the junction box.
- Drill two 4.8 mm (3/16 in.) mounting holes in the top of the junction box.
- Install network bridge GM58703 inside the junction box using two screws M7985A-0410-20, washers M125A-04-80, and nuts M934-04-50.
- Proceed to Section 6, Network Bridge Connection.
15/30RESA and 15/30REYG Bridge Installation (GM62630-KP4) installation
- Remove the junction box panel to gain access to the inside of the junction box.
- Drill two 4.8 mm (3/16 in.) mounting holes in the top of the junction box.
- Install network bridge GM58703 inside the junction box using two screws M7985A-0410-20, washers M125A-04-80, and nuts M934-04-50.
- Proceed to Section 6, Network Bridge Connection.
17/18RES Bridge Installation (GM62630-KP1) installation
- Open the enclosure and remove the front panel to access the controller junction box. Cover internal components.
- Drill a hole for the customer-supplied Ethernet cable at the location shown.
- Drill a 38.1 mm (1.5 in.) hole in the bottom of the junction box. Insert bushing X-634-28.
- Route connector P21 of Y-harness GM62626 through this opening.
- Drill two 4.8 mm (3/16 in.) mounting holes in the front panel at the locations shown.
- Use two screws M7985A-04010-20, washers X-6278-8, and nuts M934-04-50 to mount network bridge GM58703.
- Proceed to Section 6, Network Bridge Connection.
8.5/12RES Bridge Installation (GM62630-KP3) installation
- Remove existing junction box panel GM60625. Save the hardware and seal for reuse.
- Mount network bridge GM58703 onto the new panel using two screws X-51-15, washers M125A-04-80, and nuts M934-04-50.
- Install new J-box panel GM66795 as shown. Use the existing hardware and seal X-6422-31.
- Affix decal GM54820 in the location shown.
- Proceed to Section 6, Network Bridge Connection.
Assign Bridge IP Address installation
Tools: DeviceInstaller software
- Launch DeviceInstaller from the Windows Start button.
- In the DeviceInstaller menu, click View then Details.
- Click the Search button on the toolbar.
- Find the device whose hardware address matches the MAC address printed on the network bridge label.
- Click the Assign IP button in the toolbar.
- If no IP address is assigned, enter the bridge's hardware (MAC) address and click Next.
- Select Assign a Specific IP Address and click Next.
- Type the bridge IP address, subnet mask, and default gateway in dotted decimal notation. Click Next.
- Click the Assign button to assign the IP settings.
- Click the Finish button to close the Wizard.
Controller Replacement installation
⚠ Disconnect the battery cables before working on the generator set; remove the negative lead first and reconnect it last.
Tools: multimeter, personal computer with Program Loader Software
- Record generator set information required for configuration: model, market, voltage, frequency, phases, battery voltage.
- Place the generator set master switch in the OFF position.
- Disconnect power to the battery charger, if equipped.
- Disconnect the engine starting battery(ies), negative lead first.
- Open the junction box; disconnect the controller at P1, J15, and J16.
- Models ECD/EFCD, EGD/EFGD, EGZD only: disconnect the CO sensor harness at the 4-pin connector.
- Remove four controller mounting screws and remove the old controller.
- ECD/EFCD, EGD/EFGD, EGZD only: install CO sensor module assembly GM46362 on the back of the new controller GM47982.
- Install the new controller and secure with the mounting screws.
- Reconnect the P1, J15, and J16 connectors; connect the CO sensor harness on applicable models.
- Models 10/13/15EG, 10/13/15ERG, 15/30RES, 15/30RYG with S/N before 2053692: cut a 1-in. section of the gray/orange lead entering pin 9 at the ECM connector.
- Check that the generator set master switch is in the OFF position.
- Reconnect the engine starting battery, negative lead last.
- Reconnect power to the battery charger, if equipped.
- Check the controller application software version and load the latest application code if necessary.
DeviceInstaller Software Installation Procedure installation
Tools: OnCue software CD-ROM
- Insert the OnCue software CD-ROM into your PC's CD drive and wait for the opening window.
- Click on DeviceInstaller Software. A new window will open.
- Click on the Installer.msi file. The DeviceInstaller Setup Wizard will start.
- Read the information on the screen and click Next.
- Choose the installation directory, normally C:\Program Files. Click Next.
- Choose Everyone or Just me for multiple PC users. Click Next.
- Continue to follow the on-screen instructions to install DeviceInstaller software.
Installation Procedure installation
⚠ Accidental starting can cause severe injury or death. Disconnect the battery cables, negative lead first.
⚠ Hazardous voltage. Disconnect all power sources before opening the enclosure.
- Place the generator set master switch in the OFF position.
- Disconnect the power to the battery charger, if equipped.
- Disconnect the generator set engine starting battery(ies), negative lead first.
- Determine whether the network bridge will be mounted inside the enclosure or in a remote location.
- For a remote location, find a protected location; do not install the bridge outdoors.
- Maximum cable length between the network bridge and the controller is 36.6 m (120 ft.).
- Proceed to the bridge mounting instructions for your generator set model (Figure 8).
Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.
Voltage reconnection
| Voltage | Phase | Connection | Leads | Notes |
|---|---|---|---|---|
| 100 VAC | 1 | 1Ph, 2W | Uu00; 60 Hz | |
| 100 VAC | 1 | 1Ph, 3W | Uu00; 60 Hz | |
| 100/200 VAC | 1 | 1Ph, 3W | Uu08; 60 Hz | |
| 110 VAC | 1 | 1Ph, 2W | Uu05; 50 Hz | |
| 110 VAC | 1 | 1Ph, 3W | Uu05; 50 Hz | |
| 110/190 VAC | 3 | Wye | Uu17; 50 Hz | |
| 110/220 VAC | 1 | 1Ph, 3W | Uu07; 50 Hz | |
| 110/220 VAC | 1 | Dogleg | Uu07; 50 Hz | |
| 110/220 VAC | 3 | Delta | Uu15; 50 Hz | |
| 115 VAC | 1 | 1Ph, 2W | Uu05; 50 Hz | |
| 115/200 VAC | 3 | Wye | Uu23; 50 Hz | |
| 115/230 VAC | 1 | 1Ph, 3W | Uu02; 50 Hz | |
| 115/230 VAC | 1 | Dogleg | Uu06; 50 Hz | |
| 115/230 VAC | 3 | Delta | Uu14; 50 Hz | |
| 120 VAC | 1 | 1Ph, 2W | Uu00; 60 Hz | |
| 120 VAC | 1 | 1Ph, 3W | Uu00; 60 Hz | |
| 120/208 VAC | 3 | Wye | Uu11; 60 Hz | |
| 120/240 VAC | 1 | 1Ph, 3W | Uu01; 60 Hz | |
| 120/240 VAC | 1 | Dogleg | Uu01; 60 Hz | |
| 120/240 VAC | 3 | Delta | Uu10; 60 Hz | |
| 127/220 VAC | 3 | Wye | Uu16; 60 Hz | |
| 139/240 VAC | 3 | Wye | Uu10; 60 Hz | |
| 220 VAC | 1 | 1Ph, 2W | Uu12; 50 Hz | |
| 220/380 VAC | 3 | Wye | Uu19; 60 Hz | |
| 230 VAC | 1 | 1Ph, 2W | Uu02; 50 Hz | |
| 230/400 VAC | 3 | Wye | Uu03; 50 Hz | |
| 240 VAC | 1 | 1Ph, 2W | Uu13; 50 Hz | |
| 240/416 VAC | 3 | Wye | Uu20; 60 Hz | |
| 277/480 VAC | 3 | Wye | Uu04; 60 Hz |
Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.
Common questions
How many kW is the Kohler 30REYG?
The Kohler 30REYG is rated 27 kW standby (27.0 kVA).
What engine is in the Kohler 30REYG?
The Kohler 30REYG is powered by the General Motors GM 1.6L OHC engine.
What kind of fuel does the Kohler 30REYG run on?
The Kohler 30REYG runs on Natural Gas.
What is the oil capacity of the Kohler 30REYG?
The General Motors GM 1.6L OHC engine in the Kohler 30REYG has an oil capacity of 3.5 liters.
How much coolant does the Kohler 30REYG hold?
The Kohler 30REYG cooling system holds 11.5 liters (3.0 US gallons) for the radiator system including the engine, per the manufacturer specification sheet.
What alternator comes on the Kohler 30REYG?
The Kohler 30REYG uses a 2F7 alternator. It has 2 poles. Insulation class Class H.
What oil filter fits the Kohler 30REYG?
The Kohler 30REYG uses oil filter part number GM28351.
What air filter does the Kohler 30REYG use?
The Kohler 30REYG uses air filter part number GM16944.
Troubleshooting
50Fault codes
| Code | Meaning | Remedy |
|---|---|---|
| HB | High battery voltage warning — Fault code is displayed if the engine starting battery voltage rises above 16 VDC for a 12 VDC system or above 30 VDC for a 24 VDC system for more than 10 seconds when the engine is not running. This fault condition does not inhibit engine starting. The fault condition clears when the battery voltage returns to a voltage within the limits for more than 10 seconds. | Check the battery rating and condition. |
| LB | Low battery voltage warning — Fault code is displayed if the engine starting battery voltage falls below 9.5 VDC for a 12 VDC system or below 16 VDC for a 24 VDC system for more than 10 seconds when the engine is not running. This fault condition does not inhibit engine starting. The fault condition clears when the battery voltage returns to a voltage within the limits for more than 10 seconds. | Check the battery rating and condition. Charge or replace the battery. |
| AF | Auxiliary fault input shutdown — Input from a customer-supplied switch that closes when the fault is active. The generator set shuts down 0.3 seconds after the fault is detected and will not start when the fault is active (input is grounded). This protection becomes active 3 seconds after crank disconnect. | Check the cause of the auxiliary fault. |
| HE | High engine temperature shutdown — Shutdown occurs if the engine coolant temperature exceeds the maximum temperature for more than 5 seconds. This protective becomes active after the engine reaches the crank disconnect speed. | Check for blocked air inlets and exhaust outlets. |
| LCL | Low coolant level | |
| LOC | Loss of coolant | |
| LOP | Low oil pressure shutdown — Shutdown occurs if a low oil pressure condition exists for more than 5 seconds. This protective becomes active 30 seconds after the engine has reached crank disconnect speed (30 second inhibit). | Check for leaks in the lubrication system. Check the oil level and add oil if the level is low. |
| OC | Overcrank shutdown — Shutdown occurs after 3 unsuccessful starting attempts. The crank cycle is set for three starting attempts of 15 seconds cranking and 15 seconds rest. The generator set also shuts down if no engine rotation is sensed during cranking. Shuts down 1 second after the fault is detected. | Check the fuel supply, spark plug, and battery. Check for loose connections. Contact an authorized distributor/dealer for service if problem continues. |
| OF | Overfrequency shutdown — Shutdown occurs when the governed frequency exceeds 110% of the system’s frequency setpoint for more than 5 seconds. This protective becomes active 10 seconds after engine start (10 second inhibit). | Contact an authorized distributor/dealer for service if problem continues. |
| OS | Overspeed shutdown — Shutdown occurs if the engine speed exceeds 115% of the normal running speed for more than 0.3 seconds. | Contact an authorized distributor/dealer for service if problem continues. |
| OU | Overvoltage shutdown — Shutdown occurs if the voltage exceeds 120% of the system nominal voltage for more than 2 seconds. | Contact an authorized distributor/dealer for service if problem continues. |
| UF | Underfrequency shutdown — Shutdown occurs when the governed frequency falls below 90% of the nominal system frequency for more than 5 seconds or below 59 Hz for more than 60 seconds. This protective becomes active 10 seconds after engine start. (10 second inhibit). | Reduce the load and restart the generator set. Contact an authorized distributor/dealer for service if problem continues. |
| UU | Undervoltage shutdown — Shutdown occurs if the voltage falls below 80% of the nominal system voltage for more than 10 seconds. | Reduce the load and restart the generator set. Contact an authorized distributor/dealer for service if problem continues. |
| SCF0 | Software Communication Fault 0 — Indicates a software or communication problem within the ADC 2100 | Replace the controller. |
| F1 | Auxiliary Winding Fuse — A replaceable 10-amp fuse protects the alternator. | |
| F2 | Relay Fuse — A replaceable 10-amp fuse protects the engine relays. If the generator set does not crank, check the battery and battery connections and then check the relay fuse. | |
| F3 | Controller Fuse — A replaceable 10-amp fuse protects the controller circuitry. If the controller display is dark, check the battery and battery connections and then check the controller fuse. |
Symptoms & remedies
| Symptom | Cause | Remedy |
|---|---|---|
| The generator set does not crank | Battery weak or dead | Recharge or replace the battery. |
| The generator set does not crank | Battery connections reversed or poor | Check the connections. |
| The generator set does not crank | Controller fuse (F3) blown | Replace the fuse. Contact an authorized distributor/dealer for service if fuse blows repeatedly. |
| The generator set does not crank | Relay interface board fuse (F2) blown; Engine fuse blown. | |
| The generator set does not crank | Generator set master switch in the OFF position | Move the master switch to the RUN position. |
| The generator set cranks but does not start, starts hard, lacks power, or operates erratically | Air cleaner clogged | Clean and/or replace the air cleaner. |
| The generator set cranks but does not start, starts hard, lacks power, or operates erratically | Battery weak or dead | Recharge or replace the battery. |
| The generator set cranks but does not start, starts hard, lacks power, or operates erratically | Battery connection poor | Clean and tighten the battery connections. |
| The generator set cranks but does not start, starts hard, lacks power, or operates erratically | Spark plug wire connection loose | Check the spark plug wires. |
| The generator set cranks but does not start, starts hard, lacks power, or operates erratically | Low oil pressure shutdown | Check the oil level. |
| The generator set cranks but does not start, starts hard, lacks power, or operates erratically | Fuel pressure insufficient | Check the fuel supply and valves. |
| The generator set cranks but does not start, starts hard, lacks power, or operates erratically | Engine fuse blown. | Replace the fuse. Contact an authorized distributor/dealer for service if fuse blows repeatedly. |
| The generator set cranks but does not start, starts hard, lacks power, or operates erratically | Engine malfunction | Contact the distributor/dealer. |
| No AC output | AC circuit breaker in the OFF position | Place the circuit breaker in the ON position. |
| No AC output | AC circuit breaker tripping because of overload | Reduce the load on the generator set. |
| No AC output | AC circuit breaker tripping because of short circuit | Contact an authorized distributor/dealer for service. |
| No AC output | Auxiliary winding fuse (F1) blown | Replace the fuse. Contact an authorized distributor/dealer for service if fuse blows repeatedly. |
| No AC output | Engine fuse blown. | |
| Low output or excessive drop in voltage | Generator set overloaded | Reduce the load. |
| Generator set stops suddenly | Low oil pressure shutdown | Check the oil level. |
| Generator set stops suddenly | Out of fuel | Check fuel supply. |
| Generator set stops suddenly | Overcrank shutdown | Reset the controller. If the overcrank fault occurs again, contact the distributor/dealer. |
| Generator set stops suddenly | Controller fuse (F3) blown | Replace the fuse. If the fuse blows again, contact the distributor/dealer. |
| Generator set stops suddenly | Overspeed shutdown | Reset the controller. If the overspeed fault occurs again, contact the distributor/dealer. |
| Generator set stops suddenly | Generator set master switch in the OFF/RESET position | Move the switch to the correct position (RUN or AUTO). |
| Generator set stops suddenly | Remote stop command received from a remote switch, remote digital gauge, or ATS | Check the remote switch position. |
| Generator set stops suddenly | Engine malfunction | Contact the distributor/dealer. |
| Generator set stops suddenly | Engine fuse blown. | Replace the fuse. Contact an authorized distributor/dealer for service if fuse blows repeatedly. |
| Generator set stops suddenly | Auxiliary winding fuse (F1) blown | Replace the fuse. Contact an authorized distributor/dealer for service if fuse blows repeatedly. |
| Controller LED display is off | Controller may power down if the generator set has not run in the last hour of 48 hours, depending on the controller’s Cn parameter setting. See Section 2.3.6, Controller Power Down. | Controller display will automatically activate when a remote start command is received or the generator set master switch is moved to the RUN position. |
| Controller LED display is off | Controller fuse (F3) is blown. | Replace the fuse. If the fuse blows again, contact the distributor/dealer. |
| Controller LED display is off | Low or no battery voltage. | Check connections. Check generator set battery. See Figure 4-2. |
| Controller LED display is off | Generator set master switch is in the OFF/RESET position. | Move generator set master switch to the AUTO or RUN position. |
Fault codes and symptom→remedy steps extracted from this model’s service/owner documentation; verify against the official manual before servicing.
Repair guides
18- 15/30RES and 15/30RYG Bridge Installation (GM62630-KP2)
- 15/30RESA and 15/30REYG Bridge Installation (GM62630-KP4)
- 17/18RES Bridge Installation (GM62630-KP1)
- 8.5/12RES Bridge Installation (GM62630-KP3)
- ADC-RES Controller Application Code Upgrade
- ADC-RES Controller Configuration (Cn setting)
- Assign Bridge IP Address
- DeviceInstaller Software Installation Procedure
- Installation Procedure
- Network Bridge Connection, 15RES/15RYG/30RES/30RYG
- Network Bridge Connection, 15RESA/15REYG/30RESA/30REYG
- Network Bridge Connection, 8.5RES/12RES/17/18RES
- Network Bridge Connection, All Models
- Network Bridge Diagnostics
- Password Reset
- Select Bridge IP Address
- Set Up Dynamic Domain Name System (DDNS)
- Set Up Port Forwarding
Step-by-step procedures compiled from the Kohler service manual for this model.
Parts
12| Part # | Description | Qty | System | |
|---|---|---|---|---|
| 359422 | Washer, sealing (30.1 mm OD) | 1 | Seal | Amazon eBay |
| 364345 | Switch, assembly pressure | 1 | Sensor | Amazon eBay |
| 365499 | O-ring, ISO 6149 (11.3 mm ID) | 2 | Seal | Amazon eBay |
| X-386-109 | Fuel line, flexible | 1 | Hose | Amazon eBay |
| X-422-15 | Fuel line, flexible | 1 | Hose | Amazon eBay |
| X-422-35 | Fuel line, flexible | 1 | Hose | Amazon eBay |
| X-422-38 | Line, flexible | 1 | Hose | Amazon eBay |
| GM36247 | Exhaust pipe | 1 | Service part / kit | Amazon eBay |
| GM58703 | Assy, J1939/ModBus/Ethernet Converter (network bridge) | 1 | Service part / kit | eBay |
| GM66054 | Decal reminder to check oil level | 1 | Service part / kit | Amazon eBay |
| GM66559 | Lead, oil pressure switch | 1 | Service part / kit | Amazon eBay |
| GM75873 | AIR INTAKE RESONATOR KIT | 1 | Service part / kit | Amazon eBay |
Service, wear & replacement parts referenced for this model and its engine — confirm the exact part for your serial number. See the full parts catalog to search and cross-reference.
Fuel consumption
| Rating | Load | L/h | gal/h |
|---|---|---|---|
| Standby | 25% | 181.2 | 47.87 |
| Standby | 50% | 240.7 | 63.59 |
| Standby | 75% | 300.5 | 79.38 |
| Standby | 100% | 359.6 | 95.0 |
Available documents
This page was generated from the 10 manufacturer documents above by automated extraction; every figure shown is copied from one of them. How the data is compiled.