Advanced Digital (ADC 2100) Controller

The Advanced Digital (ADC 2100) is a generator-set controller. It is used on generator sets from Kohler, including the 12 RES, 15REYG, 30REYG and 8.5 RES.

5
Generator sets
Kohler
Brand
7–27 kW
Power range
Bi-Fuel (NG/LP)
Fuel

Generator sets using this controller

5

Also fitted to: Kohler 10/13/15ERG.

Engines paired with this controller

3

Troubleshooting

60

Fault codes

CodeMeaningCauseRemedy
AFIndicates a shutdown initiated by pushing the emergency stop switch.Not used on RES models.Check the position of the emergency stop button. (TRES models only)
AFInput from a customer-supplied switch that closes when the fault is active. The generator set shuts down and will not start when the fault is active (input is grounded).Check the cause of the auxiliary fault.
EnpowerGeneratorVoltHighTrip OR EnpowerGeneratorVoltLowTrip OR EnpowerGeneratorFreqHighTrip OR EnpowerGeneratorFreqLowTripGenerator voltage and/or frequency out of spec while in generator mode and generator is connectedThe generator gets disconnected
GenTHDHighHigh Total Harmonic Distortion (THD) Measured THD is above 25%Generator power output is not stable and having high THD (THD means total harmonic distortion, which is a metric to measure the power quality. If the THD is high, the performance of your electronics will be affected; for example, you may see flickering lights).
GeneratorStartFailedGenerator not startingThe generator does not start as selected in user preferences.Check if the generator 2-wire start/stop wiring to IQ System Controller is loose. Check whether the generator breaker at the unit was tripped (if so turn the breaker off and then on. Also switch the controller to the auto position), whether the generator is out of fuel, or the starting battery of the generator was dead. Contact your installer or Enphase customer support if the problem persists.
GeneratorStopFailedGenerator not stoppingGenerator continues to run even though user preferences indicate it should have stopped.Check if the generator 2-wire start/stop wiring to IQ System Controller is loose. Turn off the generator manually and contact installer or Enphase customer support.
GeneratorVoltageImbalance OR GeneratorComBusPhaseDifferenceOORGenerator was overloaded.Generator breaker in IQ System Controller tripped, and the generator is disconnected.The system will try to reconnect the generator in 5 minutes. You should: • Open IQ System Controller door, turn off the generator breaker and turn it on again. (When you open IQ System Controller, the generator breaker lever will not be in ON position) • Ensure you do not overload the system while the generator is running.
HBFault code is displayed if the engine starting battery voltage rises above 16 VDC for a 12 VDC system or above 30 VDC for a 24 VDC system for more than 10 seconds when the engine is not running. This fault condition does not inhibit engine starting.Check the battery rating and condition. Check the battery charger operation.
HBHigh battery voltage warningFault code is displayed if the engine starting battery voltage rises above 16 VDC for more than 30 seconds when the engine is running. Not operative during the engine crank cycle, this fault condition does not inhibit engine starting.Check the battery rating and condition. Check the battery charger operation.
HEHigh engine temperature shutdownShutdown occurs if the engine coolant temperature exceeds the maximum temperature for more than 5 seconds. This function becomes active after the engine reaches the crank disconnect speed.Check for blocked air inlets and exhaust outlets.
HEShutdown occurs if the engine coolant temperature exceeds the maximum temperature for more than 5 seconds. This protective becomes active after the engine reaches the crank disconnect speed.Check for blocked air inlets and exhaust outlets.
LBFault code is displayed if the engine starting battery voltage falls below 8 VDC for a 12 VDC system or below 16 VDC for a 24 VDC system for more than 10 seconds when the engine is not running. This fault condition does not inhibit engine starting.Check the battery rating and condition. Check the battery charger operation.Charge or replace the battery.
LBLow battery voltage warningFault code is displayed if the engine starting battery voltage falls below 11 VDC for more than 30 seconds when the engine is not running. Not operative during the engine crank cycle, this fault condition does not inhibit engine starting.
LOPLow oil pressure shutdownShutdown occurs if a low oil pressure condition exists for more than 5 seconds. This function becomes active 30 seconds after the engine has reached crank disconnect speed (30 second inhibit). Note: The low oil pressure shutdown does not protect against low oil level. Check the oil level at the engine.Check for leaks in the lubrication system. Check the oil level and add oil if the level is low.
LOPShutdown occurs if a low oil pressure condition exists 7 seconds after the engine has reached crank disconnect speed.Note: The low oil pressure shutdown does not protect against low oil level. Check the oil level at the engine. Check for leaks in the lubrication system.Check the oil level and add oil if the level is low.
Locked rotorThe generator set also shuts down on OC if no engine rotation is sensed during cranking. Shuts down 3 seconds after the fault is detected.
OCOvercrank shutdownShutdown occurs after 3 unsuccessful starting attempts. The crank cycle is set for three starting attempts of 15 seconds cranking and 15 seconds rest.Check the fuel supply, spark plug, and battery. Check for loose connections. Contact an authorized distributor/dealer for service if problem continues.
OCShutdown occurs after 3 unsuccessful starting attempts. The crank cycle is set for three starting attempts of 15 seconds cranking and 15 seconds rest. The generator set also shuts down after 1 crank attempt if no speed signal is sensed. Shuts down 1 second after the fault is detected.Check the fuel supply, spark plug, and battery. Check for loose connections.Contact an authorized distributor/dealer for service if problem continues.
OFOverfrequency shutdownShutdown occurs when the governed frequency exceeds 110% of the system’s frequency setpoint for more than 5 seconds. This function becomes active 10 seconds after engine start (10 second inhibit).Contact an authorized distributor/dealer for service if problem continues.
OFShutdown occurs when the governed frequency exceeds 110% of the system’s frequency setpoint for more than 1 second. This protective becomes active 30 seconds after engine start.Contact an authorized distributor/dealer for service if problem continues.
OSOverspeed shutdownShutdown occurs if the engine speed exceeds 110% of the normal running speed for more than 0.3 seconds.Contact an authorized distributor/dealer for service if problem continues.
OSShutdown occurs if the engine speed exceeds 115% of the normal running speed for more than 1 second.Contact an authorized distributor/dealer for service if problem continues.
OUOvervoltage shutdownShutdown occurs if the voltage exceeds 120% of the system nominal voltage for more than 2 seconds.Contact an authorized distributor/dealer for service if problem continues.
OUShutdown occurs if the voltage exceeds 120% of the voltage regulator setpoint for more than 1 second.Contact an authorized distributor/dealer for service if problem continues.
UFShutdown occurs when the governed frequency falls 1 Hz below the system’s frequency setpoint for more than 1 second.Reduce the load and restart the generator set. Contact an authorized distributor/dealer for service if problem continues.
UFUnderfrequency shutdownShutdown occurs if the governed frequency falls below 54 Hz for more than 5 seconds. Shutdown also occurs if the governed frequency falls below 56.5 Hz for more than 60 seconds. This function becomes active 10 seconds after engine start. (10 second inhibit).Reduce the load and restart the generator set. Contact an authorized distributor/dealer for service if problem continues.
UUShutdown occurs if the voltage falls below 80% of the voltage regulator setpoint for more than 1 second. This protective becomes active 30 seconds after engine start.Reduce the load and restart the generator set. Contact an authorized distributor/dealer for service if problem continues.
UUUndervoltage shutdownShutdown occurs if the voltage falls below 80% of the nominal system voltage for more than 10 seconds.Reduce the load and restart the generator set. Contact an authorized distributor/dealer for service if problem continues.

Symptoms & remedies

SymptomCauseRemedy
AC output circuit breaker openReset the breaker and check for AC voltage at the generator side of the circuit breaker. —
Accidental startingDisconnect the battery cables before working on the generator set. Remove the negative (--) lead first when disconnecting the battery. Reconnect the negative (--) lead last when reconnecting the battery.
Air cleaner/backfire flame arrestor cloggedClean or replace the filter element. Section 2
Alternator or control system problemPerform separate excitation procedure to isolate the problem to the alternator or the control system. Then troubleshoot the alternator or control system components as follows.
Battery short circuitsDisconnect the battery before generator set installation or maintenance. Remove all jewelry before servicing the equipment. Use tools with insulated handles. Remove the negative (--) lead first when disconnecting the battery. Reconnect the negative (--) lead last when reconnecting the battery. Never connect the negative (--) battery cable to the positive (+) connection terminal of the starter solenoid. Do not test the battery condition by shorting the terminals together.
Battery short circuits.Disconnect the battery before generator set installation or maintenance. Remove all jewelry before servicing the equipment. Use tools with insulated handles. Remove the negative (--) lead first when disconnecting the battery. Reconnect the negative (--) lead last when reconnecting the battery. Never connect the negative (--) battery cable to the positive (+) connection terminal of the starter solenoid. Do not test the battery condition by shorting the terminals together.
Broken or damaged vibromount(s)Check and replace as necessary.
Brushes problemInspect brushes and replace if worn. Check for brushes sticking in brush holder or broken brush spring.
Compression weakCheck the compression. Eng. S/M
Controller errorIndicates a software or communication problem within the ADC 2100.Contact an authorized distributor/dealer for service if problem continues.
Crank but does not startController fuse (F3) blownReplace the blown controller fuse. If the fuse blows again, troubleshoot the controller.
Does not crankGenerator set master switch in the OFF positionMove the generator set master switch to the correct position (RUN or AUTO).
Engine fails to reach operating temperatureCooling system issueCheck coolant level, flush and clean cooling system if necessary
Engine not running at rated rpmCheck controller settings for unit configuration (UC) and engine type (EC). Adjust governor speed.
Engine not running smoothlySee “Generator set operates erratically,” this table
Engine overheatedCheck air intake, fuel adjustment, oil level, air inlet/outlet.
Engine overloadReduce the electrical load. See the generator set installation manual for wattage specifications. I/M
Engine overloadedReduce electrical load.
Engine power lossRefer to the Engine Service Manual for troubleshooting and repair instructions.
Excessive engine/generator vibrationCheck, rotor, crankshaft, bearing, etc. (disassembly of engine and/or alternator may be required).
Exhaust piping or air inlets/outlets not securely installedInspect for loose parts and secure if necessary.
Exhaust system leakInspect the exhaust system. Replace the inoperative exhaust system components. Section 3, I/M
Exhaust system not securely installedInspect the exhaust system. Tighten the loose exhaust system components. Section 3, I/M
Fault shutdownReset the controller.Section 2
Faulty ground connectionClean and retighten the connection. —
Fuel valve/fuel regulatorCheck regulator/valve operation.
Fuse blows repeatedlyReplace Auxiliary winding fuse (F1). Contact an authorized distributor/dealer if the fuse blows again.
Gas fuel leaks can cause an explosion.Check the LPG vapor or natural gas fuel system for leakage by using a soap and water solution with the fuel system test pressurized to 6--8 ounces per square inch (10--14 inches water column). Do not use a soap solution containing either ammonia or chlorine because both prevent bubble formation. A successful test depends on the ability of the solution to bubble.
Generator Set does not startFault Warning or ShutdownCheck the fault warning and reset the controller if necessary
Generator overloadedReduce load.
Generator produces insufficient powerAir filter cloggedClean or replace air filter
Generator set cranks but does not startNo fuelOpen (turn on) manual fuel valve. Check fuel supply tank (LP).

Fault codes and symptom→remedy steps extracted from this controller’s service/owner documentation; verify against the official manual before servicing. Aggregated from the service documentation of generator sets built on this controller.