Kohler — Network Bridge Connection, 15RES/15RYG/30RES/30RYG
Installation · Network bridge to controller harness
From a Kohler service manual covering: 12RES, 15RES, 15REYG, 15RYG, 17RES, 18RES, 30 RYG, 30RES, 30REYG, 8.5RES. Check it applies to your exact model before use.
Applies to: Kohler 12RES, Kohler 15RES, Kohler 15REYG, Kohler 15RYG, Kohler 17RES, Kohler 18RES, Kohler 30 RYG, Kohler 30RES, Kohler 30REYG, Kohler 8.5RES
Procedure
- Disconnect the existing harness at the 12-pin customer interface connector on the junction box.
- Connect Y-harness GM65797 to the disconnected plug and to the customer interface connector.
- Connect the 12-pin connector of network bridge harness GM62627 to the third plug of Y-harness GM65797.
- Connect harness GM62627 to P36 on the bridge.
- Connect leads 3 and 4 to the remote start/stop switch or ATS engine start contacts, if applicable.
- Proceed to the instructions for All Models.
Specs & values
- Do not exceed 36 m (120 ft.) of cable length
Full service-parts list: Kohler 12RES →, Kohler 15RES →, Kohler 15REYG →, Kohler 15RYG →, Kohler 17RES →, Kohler 18RES →, Kohler 30 RYG →, Kohler 30RES →, Kohler 30REYG →, Kohler 8.5RES →
Source: Kohler service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.