Home› Troubleshooting›Kohler 13ERG

Kohler 13ERG Troubleshooting

Kohler 13ERG troubleshooting: 30 fault codes and symptom-cause-remedy entries from the manufacturer's own service documentation.

Kohler 13ERG — full specs, parts & maintenance.

All Kohler fault codes →

Troubleshooting

30

Fault codes

CodeMeaningCauseRemedy
HBHigh battery voltage warningEngine starting battery voltage rises above 16 VDC for a 12 VDC system or above 30 VDC for a 24 VDC system for more than 2 seconds when the engine is not running.Check the battery rating and condition.
LBLow battery voltage warningEngine starting battery voltage falls below 9.5 VDC for a 12 VDC system or below 16 VDC for a 24 VDC system for more than 2 seconds when the engine is not running.Check the battery rating and condition. Charge or replace the battery.

Symptoms & remedies

SymptomCauseRemedy
Does not crankGenerator set master switch in the OFF positionMove the generator set master switch to the correct position (RUN or AUTO).
Crank but does not startController fuse (F3) blownReplace the blown controller fuse. If the fuse blows again, troubleshoot the controller.
Starts hardRelay interface board fuse (F2) blownReplace the blown relay interface board fuse. If the fuse blows again, troubleshoot the controller.
No or low output voltageAuxiliary winding fuse (F1) blownReplace the blown auxiliary winding fuse. If the fuse blows again, troubleshoot the controller.
Stops suddenlyController circuit breaker trippedReset the controller circuit breaker.
Lacks powerController master or start/stop switch inoperativeReplace the controller master or start/stop switch.
OverheatsCooling System: Air openings cloggedClean the air openings.
Fault shutdownReset the controller.Section 2
Starter/starter solenoid inoperativeReplace the starter or starter solenoid. Eng. S/M
Faulty ground connectionClean and retighten the connection. —
Air cleaner/backfire flame arrestor cloggedClean or replace the filter element. Section 2
Compression weakCheck the compression. Eng. S/M
Engine overloadReduce the electrical load. See the generator set installation manual for wattage specifications. I/M
Exhaust system leakInspect the exhaust system. Replace the inoperative exhaust system components. Section 3, I/M
Exhaust system not securely installedInspect the exhaust system. Tighten the loose exhaust system components. Section 3, I/M
Overspeed shutdownReset the controller. If the overspeed fault occurs again, contact the distributor/dealer. Section 2
Valve clearance incorrectAdjust the valves. Eng. S/M
Vibration excessiveTighten all loose hardware. —
Ignition system inoperative (gas/gasoline only)Check the ignition system (ignition module, spark plugs, spark plug wires, etc.). Eng. O/M
AC output circuit breaker openReset the breaker and check for AC voltage at the generator side of the circuit breaker. —
Overcrank shutdownReset the controller. If the overcrank fault occurs again, contact the distributor/dealer. —
Transfer switch test switch in the OFF positionMove the transfer switch test switch to the AUTO position. ATS O/M
Wiring, terminals, or pin in the exciter field openCheck for continuity. Gen. S/M, W/D
Main field (rotor) inoperative (open or grounded)Test and/or replace the rotor. Gen. S/M
Stator inoperative (open or grounded)Test and/or replace the stator. Gen. S/M
Shutdown occurs when the governed frequency falls below 90% of the system’s frequency setpoint for more than 5 seconds.Reduce the load and restart the generator set. Contact an authorized distributor/dealer for service if problem continues.
Shutdown occurs if the voltage falls below 80% of the voltage regulator setpoint for more than 10 seconds.Reduce the load and restart the generator set. Contact an authorized distributor/dealer for service if problem continues.
Controller errorIndicates a software or communication problem within the ADC 2100.Contact an authorized distributor/dealer for service if problem continues.

Fault codes and symptom→remedy steps extracted from this model’s service/owner documentation; verify against the official manual before servicing.

Common questions

Kohler 13ERG: Does not crank — what causes it?

Documented causes: Generator set master switch in the OFF position. See the table for the matching fixes.

Kohler 13ERG: Crank but does not start — what causes it?

Documented causes: Controller fuse (F3) blown. See the table for the matching fixes.

Kohler 13ERG: Starts hard — what causes it?

Documented causes: Relay interface board fuse (F2) blown. See the table for the matching fixes.