Home›Kohler›Kohler RXT

Kohler RXT Generator Set

The Kohler RXT is a generator set. It is available at 100 V, 200 V, 300 V and 400 V, single-phase.

3
Document types

How to read your Kohler serial & model number →

Specifications

Voltage options100 V, 200 V, 300 V, 400 V
PhaseSingle phase,Three phase

Maintenance & consumables

ItemSpecCapacityPart #Interval
Air filter—
Fuel filter—
Oil filter—
Battery—
Belt—
Coolant—
Coolant filter—
Oil—
Spark plug—

Service intervals

40
ItemActionHoursMonthsNotes
Oil levelCheck8 hrEvery 8 hours of engine operation
Change oilChange100 hrYearly or 100 hours
Oil coolerClean100 hr20 kW models; Yearly or 100 hours
Air cleaner serviceClean150 hrYearly or hours shown
Replace filter (oil)Replace200 hr14 kW: Yearly or 200 hours; 20 kW: Yearly or 100 hours
Air cleaner serviceReplace300 hrYearly or hours shown; service more frequently under dusty/dirty conditions
Brushes and collector ringInspect300 hrYearly or 300 hours; authorized distributor/dealer only
Spark plugsReplace300 hr14 kW: 300; 20 kW: 150 and 300 hours
Crankcase breather hoseCheck500 hrYearly or 500 hours
Replace stepper motor coupling and bushingReplace500 hrAuthorized distributor/dealer only
Wire-cable insulation conditionTest500 hr3 Years or 500 hours
All external hardware in place, tightened, and not badly wornCheck12 moFigure 3-9 Yearly (Y)
All internal hardware in place, tightened, and not badly wornCheck12 moFigure 3-9 Yearly (Y)
Automatic control systemTest1 moMonthly automatic operation test (Sections 2.4, 5.5).
Automatic operationTest1 moMonthly; verify expected sequence of operation during a loaded exercise run or per Section 5.5.
Contactor's external operating mechanismClean12 moCheck for cleanliness; clean and relubricate if dirty. Service more frequently if the transfer switch is operated in dusty or dirty areas. Yearly (Y)
Control and power wiring connectionsAdjust12 moTighten to specifications (see Section 2.5). Yearly (Y)
Control and power wiring connections tighteningAdjust12 moTighten to specifications; Figure 3-9 Yearly (Y)
Electrical systemInspect1 moCheck for signs of overheating or loose connections: discoloration of metal, melted plastic, or a burning odor. Monthly and yearly.
Electrical system connections and contactor - signs of overheating or loose connections (discoloration of metal, melted plastic, burning odor)Check12 moYearly (Y); performed by authorized distributor/dealer
Exterior (vibration, high temperature, contamination, deterioration)Inspect1 moMonthly
External hardwareCheck1 moIn place, tightened, and not badly worn. Monthly (M)
External hardware (in place, tightened, not badly worn)Check1 moMonthly
External operating mechanism cleanlinessClean12 moClean as needed; service more frequently in dusty/dirty areas
External operating mechanism cleanliness (clean as needed)Clean1 moFigure 3-9; service more frequently in dusty/dirty areas
General InspectionInspect12 moAnnual general inspection
High contact resistance on power circuitsTest12 moMillivolt drop test; Yearly
Inside of transfer switchInspect12 moSigns of excessive vibration, leakage, high temperature, contamination, or deterioration. Yearly (Y)
Inside of transfer switch (vibration, noise, high temperature, contamination, deterioration)Inspect12 moFigure 3-9 Yearly (Y); Section 3.2.2
Interior (vibration, noise, temperature, contamination, deterioration)Inspect12 moYearly
Internal hardwareCheck12 moIn place, tightened, and not badly worn. Yearly (Y)
Internal hardware (in place, tightened, not badly worn)Check12 moYearly
LED indicators, time delays, and remote control systemsTest12 moTest for operation (Section 5.5).
LED indicators, time delays, remote control systemsTest12 moYearly
Main power switching contactsCheck12 moClean or replace the main contacts or replace the contactor assembly as necessary. Yearly (Y)
Main power switching contactsInspect1 moClean or replace the main contacts or replace the transfer switch assembly as necessary.
Main power switching contacts conditionCheck12 moClean or replace main contacts or replace transfer switch assembly as necessary; Figure 3-9 Yearly (Y)
Main power switching contacts conditionInspect12 moClean or replace contacts or transfer switch assembly as necessary
Main power switching mechanismInspect1 moCheck mechanical operation and integrity.
Main power switching mechanism mechanical operation and integrityCheck12 mo

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Service specifications

60
TypeItemValueUnitCondition
GapSpark plug gap0.76mm (0.030 in.)
OtherAltitude0 to 3050m (10000 ft.) without derating
OtherHumidity5 to 95% noncondensing
OtherLoad Control Contact Rating10A @ 250 VAC
OtherSpecific gravity, battery fully charged1.260electrolyte temperature 80 F (26.7 C)
OtherSpecific gravity, battery needs charging (below)1.215electrolyte temperature 80 F (26.7 C)
PressureEngine oil pressure172-241kPa (25-35 psi)
PressureFuel supply pressure, LPG1.7-2.7 (7-11)kPa (in. H2O)
PressureFuel supply pressure, natural gas1.2-2.7 (5-11)kPa (in. H2O)
ResistanceCurrent transformer burden resistor16OhmsGM83929 and GM17250, internal
ResistanceMaximum contact resistance, 100--200 Amp0.250milliohms
ResistanceMaximum contact resistance, 100-200 Amp0.250milliohms
ResistanceMaximum contact resistance, 300/400 Amp0.200milliohms
ResistanceMinimum wire insulation resistance1.24megohms
ResistanceMinimum wire insulation resistance (meggar/hi-pot)1.24megohms
ResistanceRectifier diode reverse resistanceat least 100 times the forward resistanceohmmeter R x 1 scale or diode checker
ResistanceResistance through the brushes0.1-0.2ohmswithout meter lead resistance
ResistanceRotor resistance, cold (14RCA/L 2F5/2G5)5.2ohmscold
ResistanceRotor resistance, cold (20RCA/L 2F7/2G7)5.6ohmscold
ResistanceStepper motor coil resistance per half coil38.5ohms
ResistanceTemperature sensor (OTS) resistance at 100 C (212 F)180-200ohms100 C (212 F)
ResistanceTemperature sensor (OTS) resistance at 30 C (86 F)2100-2400ohms30 C (86 F)
ResistanceWire insulation resistance (hi-pot/meggar test)>1.24megohmsmax 500 VAC, max 1 second
SpeedATS frequency sensing accuracy±2%
SpeedEngine crank disconnect speed750RPM
SpeedEngine run speed (60 Hz)3600RPM
SpeedEngine start time delay3secondstime delay after utility source is lost until engine start cycle begins
SpeedExercise time duration20minadjustment range 10-30 min, increment 1 min; factory setting
SpeedFrequency regulation, no load to full loadIsochronous
SpeedFrequency regulation, steady state±0.5%
SpeedLoad Control time delay5minutesfixed, not adjustable; allows delayed connection of selected loads
SpeedLoad control time delay (fixed)5minutesnot adjustable
SpeedRetransfer from Emergency to Normal time delay2min (120 sec)adjustment range 1 sec-10 min; factory setting
SpeedSource 1/2 Voltage Debounce Delay0.5s
SpeedTransfer from Normal to Emergency time delay3secadjustment range 1-10 sec, increment 1 sec; factory setting
SpeedTransfer, Emergency to Normal time delay2minutesafter utility source returns until transfer back to normal
SpeedTransfer, Normal to Emergency time delay3secondsafter emergency source becomes available until transfer
SpeedUndervoltage dropout time0.5secNA adjustment
TemperatureAlternator temperature rise130°CStandby
TemperatureExhaust temperature exiting the enclosure at rated kW, dry260 (500)°C (°F)Rated kW, dry
TemperatureOperating temperature-20 to 70°C (-4°F to 158°F)environmental specification
TemperatureStorage temperature-40 to 85°C (-40°F to 185°F)environmental specification
TorqueAlternate internal socket lug torque, #14 to #1060in. lb. (5 ft. lb., 6.8 Nm)
TorqueAlternate internal socket lug torque, #2 to 2/0240in. lb. (20 ft. lb., 27.1 Nm)
TorqueAlternate internal socket lug torque, #8 to #3120in. lb. (10 ft. lb., 13.6 Nm)
TorqueAlternate internal socket lug torque, 3/0 to 350MCM300in. lb. (25 ft. lb., 33.9 Nm)
TorqueAlternate internal socket lug torque, 400 to 600 MCM360in. lb. (30 ft. lb., 40.7 Nm)
TorqueAlternate internal socket lug torque, 700 to 1000 MCM480in. lb. (40 ft. lb., 54.2 Nm)
TorqueAlternator adapter bolts69Nm (51 ft. lb.)
TorqueAlternator mounting bolts14.9Nm (11 ft. lb.)
TorqueAlternator thrubolt85Nm (63 ft. lb.)
TorqueArc chute hold down screws2.8Nm25 in. lb.
TorqueArc chute holding screws2.8Nm25 in. lb.
TorqueCoil assembly M5 screws3Nm
TorqueContactor connecting bolts (T/N/E terminals)16.3Nm (12 ft. lb.)
TorqueContactor connecting bolts (load/normal/emergency terminals, 3-phase)16.3Nm12 ft. lb.
TorqueContactor connecting bolts (load/normal/emergency)16.3Nm12 ft. lb.
TorqueContactor mounting screws, 100 Amp2.4Nm21 in. lb.
TorqueContactor mounting screws, 150/200 Amp2.4Nm21 in. lb.
TorqueContactor mounting screws, 300/400 Amp6.8Nm60 in. lb.

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Recommended fluids

FluidGradeStandardAmbientCapacityNotes
Engine oilKohler Genuine oil1.8 LOil capacity with filter 1.8 L (1.9 qt.); Kohler recommends Kohler Genuine oil and filters
Engine oil5W-30 or 10W-30API Service Class SG, SH, or SJ synthetic oil1.8 L14 kW models; capacity 1.8 L (1.9 qt.)
FuelLP gas or natural gasMinimum fuel supply pressure NG: 1.2-2.7 kPa (5-11 in. H2O); LP: 1.7-2.7 kPa (7-11 in. H2O)
FuelLPGPropane 85% min; propene 5.0% max; C4 and higher 2.5% max; sulfur 25 ppm max; lower heating value 84.2 MJ/m3 (2260 Btu/ft3) minNominal fuel rating 93 MJ/m3 (2500 Btu/ft3); supply pressure 1.7-2.7 kPa (7-11 in. H2O); conversion factors 8.58 ft3 = 1 lb, 0.535 m3 = 1 kg, 36.39 ft3 = 1 gal
FuelNatural gasMethane 90% min; ethane 4.0% max; propane 1.0% max; propene 0.1% max; C4 and higher 0.3% max; sulfur 25 ppm max; lower heating value 33.2 MJ/m3 (890 Btu/ft3) minNominal fuel rating 37 MJ/m3 (1000 Btu/ft3); supply pressure 1.2-2.7 kPa (5-11 in. H2O); 1/2 NPT fuel supply inlet

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Fault codes

31
CodeNameMeaningSeverityAction
AC Sens Loss ShutdwnLoss of AC sensing shutdownController shut down the generator because there was less than 5% of rated voltage measured on Phase A for 3 seconds, only in AUTO.ShutdownCheck for loose wiring and connections. Check all AC leads. Troubleshoot alternator.
AC Sens Loss WarningLoss of AC sensing warningController measured less than 5% of rated voltage on Phase A for 1 second, 10 seconds after crank disconnect.WarningCheck for loose wiring and connections. Check all AC leads. Troubleshoot alternator.
ATS ComError WarningATS communication errorThe controller has lost communications with the RXT ATS that had previously been communicating properly.WarningCheck connections from ATS interface module to generator set; check the power LED on the interface board.
ATS Fail Xfr WarningATS fail to transferThe RXT ATS has reported a fail to transfer, the digital output for ATS Fail To Transfer (PIM) is active (contacts closed).WarningSee the troubleshooting charts in Section 4.6 and Section 4.7.
Aux Input ShutdwnAuxiliary input shutdownDigital input for a custom shutdown (AuxiliaryInputShutdown - PIM) was activated (low).ShutdownCheck customer equipment connected to the PIM module.
Battery CRLow WarningBattery cranking low warningBattery voltage dropped to 11 VDC or less for 30 seconds or more.WarningCheck engine starting battery. Check battery charger DC output voltage from RDC2.
Battery High WarningBattery high warningBattery voltage above the high warning setting for 10 seconds or more.WarningCheck engine starting battery.
Battery Low WarningBattery low warningBattery voltage below the low warning setting for 90 seconds or more.WarningCheck engine starting battery. Check battery charger DC output voltage from RDC2.
Emerg Pwr OnEmergency Power System Supplying LoadThe digital output for EPS Supplying Load (PIM) is active (contacts closed), indicating current output (>5%) from the alternator, only if CTs are installed.InfoNotice; not a fault.
Emerg Stop ShutdwnEmergency stop shutdownOptional emergency stop button pressed or emergency stop leads ESS and/or ESN are not connected.ShutdownReset the emergency stop button and clear the fault; check ESS and ESN connections; if no E-stop, connect ESS and ESN together.
Engine M/N Invalid ShutdwnEngine model number invalid shutdownGenerator model number has not been entered.ShutdownEnter the generator set model number from the RDC2 keypad, or use SiteTech to select the genset model number.
Engine Speed High ShutdwnEngine speed high shutdownEngine speed, calculated from AC frequency, was above the high speed setting for 0.3 seconds or more.ShutdownTroubleshoot engine operation per the engine service manual.
Engine Speed Low ShutdwnEngine speed low shutdownEngine speed below the low speed setting for 3 seconds or more after crank disconnect; enclosure thermostat may have tripped.ShutdownTroubleshoot engine per engine service manual. Check for high enclosure temperatures and reset the thermostat.
Frequency High ShutdwnFrequency high shutdownFrequency measured on Phase A exceeded the high frequency setting for 10 seconds, 10 seconds or more after crank disconnect.ShutdownTroubleshoot engine operation per the engine service manual.
Frequency Low ShutdwnFrequency low shutdownFrequency on Phase A was less than the low limit for 10 seconds, or 10 Hz or more less than rated for 60 seconds or more.ShutdownTroubleshoot engine per engine service manual. Check for high enclosure temperatures and reset the thermostat.
High Lube Oil Temperature ShutdownHigh lube oil temperature shutdownOil temperature higher than 325 F (163 C).ShutdownSee Overheats in the troubleshooting charts in Section 5.14.
High Lube Oil Temperature WarningHigh lube oil temperature warningOil temperature higher than 300 F (149 C).WarningSee Overheats in the troubleshooting charts in Section 5.14.
Lo Crank Vlt WarningLow cranking voltage warningDuring cranking, battery voltage measured less than 60% (7.2V or 14.4V) for 6 seconds or more.WarningCheck cranking battery.
Locked Rotor ShutdwnLocked rotor shutdownNo rotation of the engine or alternator was detected for 3 seconds or more during cranking.ShutdownCheck cranking circuit. Troubleshoot the engine and alternator. Check alternator connections to controller and auxiliary winding circuit breaker.
MainPwrOverL ShutdwnMain power overload shutdownInternal current limit circuit tripped, indicating an overcurrent condition on the DC power supply circuit.ShutdownCheck crank, run, and flash relay circuits for short circuits.
NormSrcUnavlNormal source unavailable (RXT required)The normal power source (source 1) is disconnected, unavailable, or unacceptable.InfoCheck for utility source power outage. Check wiring and connections to the ATS.
NormSrcUnavl (RXT required)Normal source unavailableThe normal power source (source 1) is disconnected, unavailable or unacceptable.InfoCheck for utility source power outage. Check wiring and connections to the ATS.
Not In Auto WarningNot in auto warningThe RDC2 controller is not in AUTO; generator will not start from an ATS or remote device.WarningPress the Auto button to ensure automatic system operation.
Oil Pressure Low ShutdwnLow oil pressure shutdownThe low oil pressure switch was closed for 5 seconds or more; inhibited until 30 seconds after crank disconnect.ShutdownCheck for oil leaks; check oil level and add oil if low; check oil pressure sensor.
Oil Pressure OpenCR WarningOil pressure open circuit warningOil pressure switch closure has not been detected after shutdown.WarningCheck the oil pressure switch connection. Test the LOP switch.
Over Crank ShutdwnOvercrank shutdownThe engine did not start during the crank cycle (15 second time delay).ShutdownCheck the alternator, fuel supply, cranking circuit, cranking battery; troubleshoot engine.
RBUS ComError WarningRBUS communication error warningThe controller has lost communication with an RBUS device that had previously been communicating properly.WarningCheck connection to the RBUS device.
Rmt StartCmdRemote Start Command IssuedThe controller has received a remote start signal while the controller is in AUTO, and will go to normal running.InfoVerify remote start signal.
Spd Sens Flt ShutdwnSpeed sensor fault shutdownThe speed signal was lost; also occurs if the engine stalls.ShutdownCheck leads 55, 66, F+, and F- between the alternator and the controller; check the engine.
Volts L1-L2 (AB) High ShutdwnVoltage L1-L2 high shutdownVoltage from Phase A to Phase B exceeded the high limit for longer than the 2 second delay setting.ShutdownTroubleshoot alternator.
Volts L1-L2 (AB) Low ShutdwnVoltage L1-L2 low shutdownVoltage from Phase A to Phase B was greater than 5% of rated but less than the low voltage setting for longer than the 10 second delay; enclosure thermostat may have tripped.ShutdownTroubleshoot alternator. Check for high enclosure temperatures and reset the thermostat.

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Procedures

12
Voltage Calibration Using SiteTech adjustment

Tools: Personal computer with Kohler SiteTech software, Digital voltmeter, USB cable

  1. Measure the voltage across transfer switch lugs NL1 and NL2.
  2. Check the voltage displayed for Source 1 Voltage L1-L2 in the Source 1 Metering group; compare to the voltmeter.
  3. If they differ, calculate the new calibration factor: (Vmeter / Vcontrol) x Fold = Fnew.
  4. In the Source 1 Calibration group, type the new value for Source 1 Calibration Factor Voltage L1-L2 and click Apply Changes.
  5. Allow a few seconds and compare the voltmeter reading with the controller display.
  6. For three-phase models, repeat for L2-L3 and L3-L1.
  7. Start the generator set and repeat for Source 2 using Source 2 Metering and Calibration groups.
Voltage Calibration using RDC2 Menus adjustment

⚠ Hazardous voltage. Only authorized personnel should open the enclosure.

Tools: Digital voltmeter (DVM) with electrically insulated probes

  1. On the RDC2 controller navigate to the ATS Status menu; press Select and use the down arrow to the Normal Voltage display.
  2. Measure the voltage across lugs NL1 and NL2 with a digital voltmeter.
  3. If the controller display does not match, press Select (voltage flashes), use Up/Down to match the voltmeter reading, and press Select to save.
  4. For 3-phase models, repeat for NL2-NL3 and NL3-NL1.
  5. Start the generator set.
  6. Navigate to the Emergency Voltage display and measure across EL1 and EL2; calibrate as in step 3.
  7. For 3-phase models, repeat for EL2-EL3 and EL3-EL1.
  8. Press the down arrow to move to the next menu and stop the generator set.
Initial Normal Source Sensing Test diagnostic

⚠ Hazardous voltage. Only authorized personnel should open the enclosure.

Tools: Voltmeter with minimum accuracy of +/-1%

  1. Connect the normal source and verify that the Normal Source Available LED lights; if not, proceed.
  2. Check for nominal voltage at the ATS contactor lugs (single-phase across NL1-NL2; three-phase across NL1-NL2, NL2-NL3, NL3-NL1).
  3. If voltage is present at the lugs, check the interface board LEDs and check for voltage at the interface board connectors (single-phase P13-1 and P13-5; three-phase P1-12 to P1-11, P1-11 to P1-4, P1-4
  4. If no voltage at the interface board connectors, check the wiring from the contactor to the interface board and repair or replace as needed.
  5. If the voltage exceeds the pickup voltage, the Utility Available LED on the RDC2 controller should light; if not, check communications wiring.
  6. For the optional ATS status indicator, verify the Utility Available LED and check the status indicator connection to P12.
  7. Disconnect the normal source and verify the Utility Available LED turns off within a few seconds.
Millivolt Drop Test Procedure diagnostic

⚠ Testing live electrical circuits. Hazardous voltage or current will cause severe injury or death. Only authorized personnel should open the enclosure.

Tools: Voltmeter, Ammeter

  1. Apply a balanced load of at least 10% of the switch rating (10 amps or greater gives more accurate results).
  2. Measure the voltage on both sources from the source lug to the load lug; take several readings.
  3. Use an ammeter to measure the current flow through the circuit.
  4. Calculate contact resistance using R = V divided by I (V in millivolts, I in amps, R in milliohms).
  5. Compare calculated resistance to the table; if significantly higher (2 times or more), disconnect power, check connections and lug torques, and repeat.
  6. If the second measurement is also too high, replace the contactor.
Separate Excitation Procedure diagnostic

⚠ Hazardous voltage. Operate the generator set only when all guards and electrical enclosures are in place.

Tools: DC ammeter, 10-amp fuse, 12-volt automotive battery

  1. Disconnect the black FN and FP leads from the alternator at the brush holder terminals.
  2. Connect a DC ammeter, 10-amp fuse, and a 12-volt automotive battery to the FP and FN brush leads.
  3. Note and record the ammeter reading.
  4. Start the engine and check that the ammeter reading remains stable.
  5. An increasing reading indicates a shorted rotor; a decreasing reading suggests a running open.
  6. Check for AC output across the stator leads and compare to Section 1 specifications.
  7. If rotor and stator are good, check the wiring, fuses, and controller settings and connections.
Source Voltage and Frequency Check Procedure diagnostic

⚠ Hazardous voltage. Only authorized personnel should open the enclosure.

⚠ Do not connect or disconnect the controller wiring harness when the power is connected.

Tools: Digital voltmeter (DVM) with electrically insulated probes

  1. Press the OFF button on the generator set controller and verify the OFF LED.
  2. Disconnect both power sources from the transfer switch.
  3. Disconnect the transfer switch contactor wiring harness from P13 (single-phase) or P1 (3-phase) interface board.
  4. Manually operate the transfer switch to position E.
  5. Close the utility source circuit breaker and check the utility source voltage to the transfer switch across NL1-NL2, NL1-neutral, and NL2-neutral.
  6. For three-phase systems, repeat the checks across NL1-NL3 and NL3-NL1.
  7. Disconnect Source N and manually operate the switch to position N.
  8. Press RUN to start the generator set and check generator source voltage and frequency at EL1 and EL2.
  9. If generator output voltage/frequency do not match the nameplate, adjust the generator set.
  10. Stop the generator set, disconnect both sources, reconnect the wiring harness, close the door, and reconnect both sources.
  11. Press the AUTO button on the generator set controller.
Wire Insulation Breakdown Test Procedure diagnostic

⚠ Testing live electrical circuits. Hazardous voltage or current will cause severe injury or death.

Tools: Hi-pot tester or meggar

  1. Disconnect all power sources and the load; disconnect the transfer switch wiring harness from the controller at connector P1.
  2. Use a hi-pot tester or meggar to check insulation resistance phase-to-phase, phase-to-neutral, and phase-to-ground if isolated.
  3. For a hi-pot tester, maximum potential is 500 VAC and maximum test time is 1 second.
  4. Verify that measured insulation resistance exceeds 1.24 megohms.
  5. If breakdown is indicated or resistance is less than 1.24 megohms, isolate the leakage current and replace faulty components.
12-Lead Generator Reconnection Procedure installation

⚠ Hazardous voltage. Disconnect all power sources before opening the enclosure.

Tools: digital multimeter, voltmeter

  1. Press the OFF button on the RDC2 controller.
  2. Disconnect the engine starting battery, negative lead first.
  3. Disconnect utility power to the generator set.
  4. Remove the circuit breaker cover and the controller panel to access the alternator leads and CTs.
  5. Replace the circuit breaker with the correct part for the new voltage rating.
  6. Select the desired voltage connection and connect the leads per the diagram.
  7. Reconnect the engine starting battery, negative lead last.
  8. Check system voltage, frequency, and phase settings and change them if necessary.
  9. Connect a digital multimeter (DVM) to the generator set output.
  10. Press RUN to start the generator set.
  11. Use a voltmeter to check for the correct voltage output; calibrate the RDC2 voltage if necessary.
  12. Press OFF to stop the generator set.
  13. Reconnect utility power to the generator set.
  14. Press AUTO to place the generator set in automatic mode.
Fuel Conversion from Natural Gas to LPG, 14RCA/RCAL installation

⚠ Explosive fuel vapors. Use extreme care when handling, storing, and using fuels.

Tools: straight-blade screwdriver, gas leak detector

  1. Press the OFF button on the generator set controller.
  2. Disconnect the utility power to the generator.
  3. Disconnect the engine starting battery, negative lead first.
  4. Turn off and disconnect the fuel supply.
  5. Remove the fuel hose from the hose fitting on the top of the regulator.
  6. Use a straight-blade screwdriver to remove the NG orifice from the hose fitting.
  7. Insert the LPG orifice into the hose fitting and tighten until snug.
  8. Slide the hose onto the fitting and secure with the clamp.
  9. Disconnect ignition timing leads 65 and N3 for LPG.
  10. Connect and turn on the new fuel supply.
  11. Reconnect the engine starting battery leads, negative lead last.
  12. Reconnect the utility power to the generator.
  13. Start the generator set by pressing RUN.
  14. Check for leaks with a gas leak detector, run to check operation, and press OFF.
Installation installation

⚠ Do not use compressed air to clean the switch; it can cause debris to lodge in the components and damage the switch.

⚠ Hazardous voltage: disconnect all power sources before opening the enclosure.

Tools: Shims, Vacuum cleaner

  1. Check the system voltage and frequency against the transfer switch nameplate before installing.
  2. Plan the installation using the enclosure dimension (ADV) drawings in Section 6.
  3. Select a mounting site that complies with local electrical code restrictions for the enclosure type.
  4. Mount the transfer switch as close to the load and power sources as possible.
  5. NEMA 3R enclosures: support the front panel while removing the screws, then pull the bottom out and down.
  6. Wall mounting: mount to a wall or other rigid vertical structure, using shims to plumb the enclosure.
  7. Cover or remove internal components to protect them from drill chips or debris during installation.
  8. Tighten the mounting screws to 2.9 Nm (26 in. lb.) when reinstalling the components.
Procedure to Connect an LCM if the Combined Board is Used on the RXT installation

⚠ Hazardous voltage. Disconnect all power sources before opening the enclosure.

⚠ DO NOT connect power relays, HVAC relays, or current transformer to the combined board.

Tools: Basic electrician's hand tools

  1. Press the OFF button on the generator set controller.
  2. Disconnect the utility power to the generator set.
  3. Disconnect the generator set engine starting battery(ies), negative (-) lead first.
  4. Disconnect power to the transfer switch.
  5. Remove the ATS enclosure cover and find the combined interface/load management board.
  6. Move the P11 jumper from terminals 2 and 3 to terminals 1 and 2 to disable load management on the combined board.
  7. Connect the RBUS communication cable to A, B, PWR, and COM on terminal block P10 on the interface/load management board.
  8. Follow TT-1574 to connect the LCM: connect LCM RBUS to the combined interface board or generator controller; connect the current transformer (CT) to the LCM (not the combined board); connect power rel
  9. Install the ATS enclosure cover, check the generator set is OFF, and reconnect utility power to the transfer switch.
  10. Reconnect the generator set engine starting battery, negative (-) lead last, and reconnect utility power to the generator set.
Air Cleaner Service maintenance

⚠ Do not operate the generator set with the air cleaner removed; a sudden backfire can cause severe injury or death.

  1. Press the OFF button on the generator set controller.
  2. Disconnect the utility power to the generator set.
  3. Disconnect the generator set engine starting battery, negative lead first.
  4. Loosen the cover retaining knob(s) and remove the cover.
  5. Remove the element cover nut, element cover, and the paper element.
  6. Do not wash the paper element or clean it with pressurized air.
  7. Replace the element if it is dirty, bent, or damaged.
  8. Check the air cleaner base and element cover; replace damaged components.
  9. Reinstall the paper element, element cover, nut, and cover; secure the cover.
  10. Reconnect the utility power to the generator set.
  11. Reconnect the engine starting battery, negative lead last.

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Voltage reconnection

VoltagePhaseConnectionLeadsNotes
P10 (RBUS communication) on controller interface boardP10-1 A Communication Line; P10-2 B Communication Line; P10-3 PWR 12 VDC; P10-4 COM 12 VDC20 AWG shielded twisted-pair, Belden 9402 or equivalent; 12--14 AWG wire for PWR and COM for long runs.
P10-1ACommunication Line; 20 AWG shielded twisted-pair, Belden 9402 or equivalent
P10-1 (A)20 AWG shielded twisted-pair, Belden 9402, 8723, or equivalentCommunication Line, ATS interface board to RDC2/DC2 generator set controller
P10-2BCommunication Line; 20 AWG shielded twisted-pair, Belden 9402 or equivalent
P10-2 (B)20 AWG shielded twisted-pair, Belden 9402, 8723, or equivalentCommunication Line
P10-3PWR12 VDC; 20 AWG shielded twisted-pair Belden 9402 or 12-14 AWG wire
P10-3 (PWR)20 AWG shielded twisted-pair Belden 9402, or 12-14 AWG wire12 VDC
P10-4COM12 VDC; 20 AWG shielded twisted-pair Belden 9402 or 12-14 AWG wire
P10-4 (COM)20 AWG shielded twisted-pair Belden 9402, or 12-14 AWG wire12 VDC
P11 (Load control) on standard interface board onlyP11-1 / P11-2 LOAD Load ControlContact rating 10 A @ 250 VAC; wire size #12--18 AWG. Not present on combined interface/load management board.
P11-1ALoad Control connection on standard interface board only; contact rating 10 A @ 250 VAC; wire size #12-18 AWG
P11-1 (LC1)#12-18 AWGLoad Control Output, 10 A @ 250 VAC, 1 A @ 30 VDC
P11-2BLoad Control connection on standard interface board only; contact rating 10 A @ 250 VAC; wire size #12-18 AWG
P11-2 (LC2)#12-18 AWGLoad Control Output
RBUS module connections to generator set terminal block TB1A, B, PWR, COMConnect one end of each cable shield to GROUND at the generator set; leave the end of each cable shield disconnected at the last device.
1Single-phase leads 1-2, 3-41, 2, 3, 44-lead generator sets are not reconnectable
1Standard (100A)(1) #14 - 1/0 AWGNormal and Emergency Load
1Standard (200A)(1) #6 AWG - 250 MCMNormal and Emergency Load
1Standard (400A)(2) #6 - 250 MCMNormal and Emergency Load (Emerg: (2) #6 - 250 MCM)
3Standard (200A)(1) #6 AWG - 250 MCMNormal and Emergency Load
3Standard (400A)(1) #6 AWG - 250 MCMNormal and Emergency Load
3Three-phase leads 1-4, 2-5, 3-6, 7-10, 8-11, 9-121-1212-lead generator sets are reconnectable to voltages shown on the generator set specification sheet
single-phaseEmergency source voltage sensing (single-phase)P13-3 and P13-7Interface board connector P13
single-phaseNormal source voltage sensing (single-phase)P13-1 and P13-5Interface board connector; check nominal voltage and LED1 normal source available
three-phaseEmergency source voltage sensing (three-phase)P1-7 and P1-18, P1-6 and P1-7, P1-6 and P1-18Interface board connector P1
three-phaseNormal source voltage sensing (three-phase)P1-12 to P1-11, P1-11 to P1-4, P1-4 to P1-12Interface board connector P1
120/2083WyeVoltage configuration (Figure 4-12)
120/24012-pole, 3-wire, solid neutral#14 - 1/0 AWG100 amp standard model
120/2401SingleVoltage configuration (Figure 4-12)
120/2403DeltaVoltage configuration (Figure 4-12)

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Common questions

What voltage does the Kohler RXT produce?

The Kohler RXT is offered in 100 V, 200 V, 300 V, 400 V, Single phase,Three phase-phase.

Troubleshooting

6

Symptoms & remedies

SymptomCauseRemedy
ATS ComError Warning (ATS communication error) — WarningThe controller has lost communications with the RXT ATS that had previously been communicating properly.Check connections from ATS interface module to generator set; Check the power LED on the interface board; See Section 5.1.
ATS Fail Xfr Warning (ATS fail to transfer) — WarningThe RXT ATS has reported a fail to transfer, the digital output for ATS Fail To Transfer (PIM) is active (contacts closed).See the troubleshooting charts in Section 4.6; Also see Section 4.7.
Emerg Pwr On (Emergency Power System Supplying Load) — NoticeThe digital output for EPS Supplying Load (PIM) is active (contacts closed), indicating there is current output (>5%) from the alternator, only if CTs are installed.
NormSrcUnavl (RXT required) — NoticeThe normal power source (source1) is disconnected, unavailable or unacceptable.Check for utility source power outage; Check wiring and connections to the ATS.
Rmt StartCmd (Remote Start Command Issued) — NoticeThe controller has received a remote start signal while the controller is in AUTO, and will go to normal running.Verify remote start signal.
RXT not respondingPower LED not steady ON; Online LED not steady ON; Online LED blinking faster than once/second; RXT not shown on SiteTech/OnCue; Number of errors and timeouts not steady; RXT ID changes over timeCheck ATS status in the RDC2 controller menu; Verify that only one RXT is connected; Check communication A & B connections at the RXT interface board and genset connection terminal block; Verify correct version of PC software is installed; Ensure the cable runs from genset to RXT are within specifications (cable size and length); If problems persist, contact the Kohler Generator Service Department.

Fault codes and symptom→remedy steps extracted from this model’s service/owner documentation; verify against the official manual before servicing. Full Kohler RXT troubleshooting guide (115 entries) →

Parts

86
Part #DescriptionQtySystem
GM20990Gasket4Gasket Amazon eBay
P10-4BrushesBrushes Amazon Amazon eBay eBay
082S270538-3Lamp/LED bulb - INSTRUMENT CLUSTER: GAUGE BACK LIGHT1Service part / kit Amazon eBay
082S272109-2Lamp/LED bulb - INSTRUMENT CLUSTER: LEFT TURN SIGNAL LED (GREEN)1Service part / kit Amazon eBay
082S272109-3Lamp/LED bulb - INSTRUMENT CLUSTER: GAUGE WARNING LED (RED)1Service part / kit Amazon eBay
082S272109-4Lamp/LED bulb - INSTRUMENT CLUSTER: RANGE INHIBIT LED (YELLOW)1Service part / kit Amazon eBay
082S272109-5Lamp/LED bulb - INSTRUMENT CLUSTER: HIGH BEAM ICON LED (BLUE)1Service part / kit Amazon eBay
297712Lug, Terminal3Service part / kit Amazon eBay
362081Contacts, auxiliary1Service part / kit eBay $59.99
362084Arc Chutes1Service part / kit eBay
362087Solenoid1Service part / kit eBay $350.00
362090Solenoid1Service part / kit eBay
362135Solenoid1Service part / kit eBay
G11-123Status indicator kit with LED indicators1Service part / kit eBay
G11-124Load shed kit with HVAC relays and pilot relays1Service part / kit eBay
GE1156Lamp/LED bulb - BACK-UP LIGHTS (32 candlepower)1Service part / kit Amazon eBay
GE168Lamp/LED bulb - COURTESY LIGHT (3 candlepower)1Service part / kit Amazon eBay
GE193Lamp/LED bulb - CLEARANCE & IDENTIFICATION (3 candlepower)1Service part / kit Amazon eBay
GE561Lamp/LED bulb - DOME LIGHTS (12 candlepower)1Service part / kit Amazon eBay
GE9007Lamp/LED bulb - HEAD LIGHTS: LOW BEAMS (65 watts)1Service part / kit Amazon eBay
GM102261Assy, Solenoid - 200A/240V (Motor)1Service part / kit eBay
GM102262Contact, Auxiliary2Service part / kit eBay
GM102263Lug Kit - 100A (3/Kit)2Service part / kit eBay
GM102264Lug Kit - 200A (3/Kit)2Service part / kit eBay
GM102266Harness - 240V1Service part / kit eBay
GM102267Cover - 100A1Service part / kit eBay
GM102268Cover - 200A1Service part / kit eBay
GM102288Lug Kit - 200A, SE Bus (2/Kit)1Service part / kit eBay
GM102299Assy, Solenoid - 100A/240V (Motor)1Service part / kit eBay
GM25434Switch, coil cutout / Contacts, auxiliary1Service part / kit eBay
GM28412Lug, terminal6Service part / kit eBay
GM29867Limit Switch2Service part / kit eBay
GM31593Terminal, ATS lug sensing4Service part / kit eBay
GM32387Plunger and link, solenoid1Service part / kit eBay
GM32388Rectifier1Service part / kit eBay
GM32390Solenoid1Service part / kit eBay
GM32392Solenoid1Service part / kit eBay
GM39145Arc chute assembly1Service part / kit eBay
GM41995Contactor harness1Service part / kit eBay
GM51138Lugs, cable connection1Service part / kit eBay
GM77077Power Terminal Cover1Service part / kit eBay
GM77176Relay4Service part / kit Amazon eBay
GM77177-1Decal, CSA1Service part / kit Amazon eBay
GM77178Cover w/ Decals, Load Shed1Service part / kit Amazon eBay
GM78649Membrane Status Indicator1Service part / kit Amazon eBay
GM79580PCB Assy, RXT 1-Phase ATS Interface1Service part / kit eBay $350.00
GM80079PCB Assy, RXT 3-Phase ATS Interface1Service part / kit eBay $750.00
GM80139Contactor Assembly, 400 Amp 2-poleService part / kit Amazon eBay
GM80140Contactor Assembly, 400 Amp 3-pole 240VService part / kit eBay
GM80547Contactor Assembly, 100 Amp 2-poleService part / kit eBay $599.95
GM80549Contactor Assembly, 150/200 Amp 2-poleService part / kit eBay $340.00
GM80551Contactor Assembly, 300/400 Amp 2-pole ASEService part / kit eBay $330.00
GM80778-SContactor Harness1Service part / kit eBay
GM80779Contactor Harness1Service part / kit eBay
GM80780Contactor Harness1Service part / kit eBay
GM80879Decal, Wiring Diagram1Service part / kit Amazon eBay
GM80950Decal, Warning2Service part / kit Amazon eBay
GM81111Contactor Assembly, 400 Amp 3-pole 208VService part / kit eBay $2500.00
GM81372-1PCB Assy, RDC2 Load Control1Service part / kit Amazon eBay $225.00
GM83720Rectifier1Service part / kit eBay
GM83929Transformer, Current (CT)1Service part / kit Amazon eBay
GM84872Solenoid Coil (240V)1Service part / kit eBay
GM84873Solenoid Coil (240V)1Service part / kit eBay
GM84874Solenoid Coil (240V)1Service part / kit eBay
GM84875Solenoid Coil (240V)1Service part / kit eBay
GM84876Solenoid Coil (240V)1Service part / kit eBay $119.00
GM84877Solenoid Coil (240V)1Service part / kit eBay
GM84878Solenoid Coil (240V)1Service part / kit eBay
GM84880Solenoid1Service part / kit eBay
GM84881Solenoid Coil1Service part / kit eBay
GM84882Solenoid Coil1Service part / kit eBay
GM84883Handle, Manual1Service part / kit eBay
GM84884Arc Chutes1Service part / kit eBay
GM84885Handle1Service part / kit eBay
GM84886Harness, wiring1Service part / kit eBay
GM85087-2Neutral, 100-200A (Sub-Assembled)1Service part / kit eBay
GM85087-3Neutral, 100-200A SE (Sub-Assembled)1Service part / kit eBay
GM88281-1Load Control, ATS1Service part / kit Amazon eBay
GM88557Harness, CommunicationsService part / kit eBay
GM90763Membrane, Switch/LED, RXT/LCM Combo1Service part / kit Amazon eBay
GM90773PCB Assy, RXT/LCM Combo1Service part / kit eBay $395.00
GM93969-KP1-QSRXT Interface/Load Shed PCBAService part / kit eBay
P10-1Voltage Regulator PowerBoost™ VService part / kit Amazon Amazon eBay eBay FridayParts $117.99
P10-2StatorService part / kit Amazon Amazon eBay eBay
P10-3communication cable connectorService part / kit Amazon Amazon Amazon eBay eBay eBay KuduParts $29.00
VH550Lamp/LED bulb - FOG LIGHTS (55 candlepower)1Service part / kit Amazon eBay

Service, wear & replacement parts referenced for this model and its engine — confirm the exact part for your serial number. See the full parts catalog to search and cross-reference.

Fuel consumption

RatingLoadL/hgal/h
Prime100%1.759.0
Standby100%3.9136.0

Available documents

Spec sheet — kohler-egd-14rcal-200sels-kit-specification-sheets (Kohler)Reference (Kohler)Reference — TP-6753 0914D (Kohler)Reference — adv8487 (Kohler)Reference — adv8736 (Kohler)Reference — adv9755 (Kohler)Reference — g11152 (Kohler)Reference — tp6753 (Kohler)Reference — tt1585 (Kohler)Service manual (Kohler)Service manual — 2a9cc7 (Kohler)Service manual — 50adb3b2-603c-4040-9f0d-b6f22f56a9fd (Kohler)Service manual — TP-6808 1218C (Kohler)Service manual — TP-7091 (Kohler)Service manual — adv9187 (Kohler)Service manual — gm80666 (Kohler)Service manual — gm80676 (Kohler)Service manual — tp6807 (Kohler)Service manual — tp6807fr (Kohler)Service manual — tp6808 (Kohler)Service manual — tp6984 (Kohler)Service manual — tt1609 (Kohler)Service manual — tt1646 (Kohler)

This page was generated from the 23 manufacturer documents above by automated extraction; every figure shown is copied from one of them. How the data is compiled.