Before you start

  • Hazardous voltage. Disconnect all power sources before opening the enclosure.

Procedure

  1. Prevent all connected generator sets from starting (master switch OFF, disconnect battery charger, disconnect starting battery negative lead first).
  2. Disconnect power to the transfer switch, open the enclosure, and verify zero volts across each phase.
  3. Note the location of the fast-on connectors to the microswitch terminals.
  4. Disconnect the fast-on connectors.
  5. Remove the holding screws and remove the suspect microswitch (remove end plate for four-microswitch SN/SE assemblies).
  6. Install the new microswitch and install the holding screws, tightening to 0.3 Nm (3 in. lb.).
  7. Connect the fast-on connections as noted in step 3.
  8. Close the enclosure, connect power, and enable the generator set.
  9. Move the generator set master switch to AUTO and test the transfer switch operation.

Tools required

  • Basic electrician's hand tools
  • Rubber insulating gloves class 0 Amazon
  • Safety glasses Amazon
  • Electrical hazard safety shoes Amazon

Tool links are Amazon searches (affiliate links); manufacturer special tools may only be available from a dealer.

Specs & values

  • Microswitch holding screws torque 0.3 Nm (3 in. lb.)

Source: Kohler service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.