Kohler 14RCA / 20RCA — 12-Lead Generator Reconnection Procedure

Installation · Stator leads / alternator

For the Kohler 14RCA / 20RCA, from the Kohler service manual.

Applies to: Kohler 14RCA, Kohler 20RCA, Kohler CH740 (14 kW models); CH1000 (20 kW models) engine, Kohler CH 740 engine, Kohler CH1000 engine

Before you start

  • Hazardous voltage. Disconnect all power sources before opening the enclosure.

Procedure

  1. Press the OFF button on the RDC2 controller.
  2. Disconnect the engine starting battery, negative lead first.
  3. Disconnect utility power to the generator set.
  4. Remove the circuit breaker cover and the controller panel to access the alternator leads and CTs.
  5. Replace the circuit breaker with the correct part for the new voltage rating.
  6. Select the desired voltage connection and connect the leads per the diagram.
  7. Reconnect the engine starting battery, negative lead last.
  8. Check system voltage, frequency, and phase settings and change them if necessary.
  9. Connect a digital multimeter (DVM) to the generator set output.
  10. Press RUN to start the generator set.
  11. Use a voltmeter to check for the correct voltage output; calibrate the RDC2 voltage if necessary.
  12. Press OFF to stop the generator set.
  13. Reconnect utility power to the generator set.
  14. Press AUTO to place the generator set in automatic mode.

Tools required

Tool links are Amazon searches (affiliate links); manufacturer special tools may only be available from a dealer.

Specs & values

  • Replace the line circuit breaker when changing the voltage configuration
  • Affix voltage reconnection decal 246242 Amazon eBay $9.67 after reconnecting

Full service-parts list: Kohler 14RCA →, Kohler 20RCA →

Source: Kohler service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.

More Kohler repair guides →