HomeEnginesKohler CH1000

Kohler CH1000 Engine

The Kohler CH1000 is a 1 L 2-cylinder air-cooled, four-cycle, twin cylinder, overhead valve, with oil cooler engine rated at 3600 rpm, producing up to 23 kW. It powers generator sets from Kohler, including the 18RCAL, 20RCA, 20RES and RESA. It holds 1.9 L (0.5 gal) of oil and 2.5 L (0.7 gal) of coolant.

Also known as: Kohler CH1000

0.999 L
Displacement
2
Cylinders
3600 rpm
Rated speed
23 kW
Gross power

Engine specifications

Oil capacity1.9 L
Coolant capacity2.5 L
Displacement0.999 L
Cylinders2
Aspirationair-cooled, four-cycle, twin cylinder, overhead valve, with oil cooler
Rated speed3600 rpm
Gross power23 kW

Common problems

15
  • The generator set cranks but does not start, starts hard, lacks power, or operates erratically.
    Cause: Air cleaner clogged.
    Fix: Clean and/or replace the air cleaner.
  • No AC output.
    Cause: Line circuit breaker in the OFF position.
    Fix: Place the circuit breaker in the ON position.
  • Auxiliary winding circuit breaker tripped.
    Fix: Reset the auxiliary winding circuit breaker. Contact an authorized dealer for service if breaker trips repeatedly.
  • Generator thermostat tripped.
    Fix: Check for obstructed air inlets and outlets. Reset the thermostat.
  • Generator set stops suddenly.
    Cause: Low oil pressure shutdown.
    Fix: Check for oil leaks. Check the oil level and add oil if necessary.
  • Remote stop command received from a remote switch, ATS, or OnCuerPlus.
    Fix: Check the remote switch position. Check OnCuerPlus.
  • Low oil pressure shutdown.
    Fix: Check for oil leaks. Check the oil level and add oil if necessary.
  • Line circuit breaker tripping because of short circuit.
    Fix: Contact an authorized distributor/dealer for service.
  • Line circuit breaker tripping because of overload.
    Fix: Reduce the load on the generator set by unplugging non-essential appliances.
  • Generator set in the OFF mode.
    Fix: Press the RUN button to start the engine or press AUTO to allow remote starting.
  • Fuel pressure insufficient.
    Fix: Check the fuel supply and valves.
  • Engine malfunction.
    Fix: Contact an authorized distributor/dealer.
  • The generator set does not crank.
    Cause: Battery weak or dead.
    Fix: Recharge or replace the battery. Make sure that the AC power to the generator set controller is backed up by the generator set.
  • Low output or excessive drop in voltage.
    Cause: Generator set overloaded.
    Fix: Reduce the load by unplugging non-essential appliances.
  • Controller display is off.
    Cause: Low or no battery voltage.
    Fix: Check connections. Check generator set battery. See the Service Views section.

Compiled from service & troubleshooting documentation across every generator set that uses the Kohler CH1000.

Maintenance schedule

ItemSpecCapacityPart #Interval
Air filter300 hr
Fuel filterKohler Fuel Filter200 hr
Oil filterCartridge type52 050 02-S200 hr Amazon $22.70 eBay
BatteryGroup 27200 hr
BeltKohler V-Belt200 hr
CoolantKohler Coolant2.5 L200 hr
OilKohler SAE 10W-30500.0 L200 hr
Spark plug300 hr

Pooled from every document that names this exact engine — confirm the interval and part number against your unit's serial number.

Service intervals

40
ItemActionHoursMonthsNotes
Oil levelCheck8 hrEvery 8 hours of engine operation
Oil level, 14 kW modelsCheck8 hrEvery 8 hours of engine operation
Oil level, 18/20 kW modelsCheck8 hrEvery 8 hours of engine operation
Oil level, 20 kW modelsCheck8 hr
Oil level, 26 kW modelsCheck24 hr
Change oil (14 kW models)Change100 hr12 moYearly or 100 hours
Engine oilChange100 hr12 mo14 kW models: 100 hours; 20 kW models: 150 hours
Oil (14 kW)Change100 hr12 mo
Air cleanerReplace150 hr300 hours shown; service more frequently under dusty/dirty conditions
Change oil (20 kW models)Change150 hr12 moYearly or 150 hours
Oil (20 kW)Change150 hr12 mo
Oil cooler (20RCA/RCAL only)Clean150 hr12 moYearly or 150 hours; inspect and clean, must be kept free of debris
Oil filter (20 kW)Replace150 hr12 mo
Replace oil filter (20 kW models)Replace150 hr12 moYearly or 150 hours
Oil filterReplace200 hr12 mo14 kW models: 200 hours; 20 kW models: 150 hours
Oil filter (14 kW)Replace200 hr12 mo
Replace oil filter (14 kW models)Replace200 hr12 moYearly or 200 hours
Air cleaner serviceClean300 hr12 moYearly or 150/300 hours depending on model; more often under dusty/dirty conditions
Brushes and collector ringInspect300 hr12 moYearly or 300 hours; authorized distributor/dealer only
Generator brushes and collector ringReplace300 hr12 moAuthorized distributor only
Spark plugsReplace300 hr12 mo150-300 hours shown
Crankcase breather hoseInspect500 hr12 moYearly or 500 hours
Crankcase breather hoseReplace500 hr12 moYearly or 500 hours
Replace stepper motor coupling and bushingReplace500 hrAuthorized distributor/dealer only
Wire-cable insulation conditionInspect500 hr36 mo3 years or 500 hours
Wire-cable insulation conditionTest500 hr36 mo3 years or 500 hours
AC electrical system visible wear or damageInspect3 moQuarterly
Air ducts and louversClean12 mo
Air ducts, louversClean12 moYearly; visually inspect and clean
BatteryCheck1 moCheck charger operation, charge rate
Battery and rack corrosionClean12 moYearly
Battery charger operation, charge rateCheck1 moMonthly
Battery electrolyte level and specific gravityCheck12 moYearly; not necessary for maintenance-free batteries
Battery terminals and bootsClean12 moYearly
Clean and tighten battery terminals and inspect bootsClean12 moYearly
Control and power wiring connectionsCheck12 moTighten; Yearly
Exhaust insulation, fire hazardsInspect12 moYearly
Flexible fuel lines and connectionsInspect3 moReplace as necessary; Quarterly
Fuel flexible lines and connectionsInspect3 moVisually inspect; replace as necessary; quarterly
Fuel pipingInspect12 moYearly

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Service specifications

49
TypeItemValueUnitCondition
GapSpark plug0.03in.
GapSpark plug0.76mm
GapSpark plug gap0.51mm (0.02 in.)
GapSpark plug gap0.7--0.8mm (0.028--0.030 in.)
GapSpark plug gap0.76mm (0.030 in.)
GapSpark plug gap0.8--0.9mm (0.03--0.04 in.)
GapSpark plug gap0.89mm (0.035 in.)
GapSpark plug gap0.9--1.0mm (0.036--0.04 in.)
OtherBattery wrap length1067 (42)mm (in.)
OtherBattery wrap length864 (34)mm (in.)
OtherEngine cooldown time delay5minutes
OtherEngine start crank cycle3 attempts, 15 sec crank / 15 sec off
OtherGoverned frequency high shutdown110% of frequency setpoint for >10 sec10 sec inhibit after engine start
OtherGoverned frequency low shutdown90% of frequency setpoint for >10 sec, or 1 Hz below setpoint for >60 sec10 sec inhibit after engine start
OtherHeater wrap rating50Watts
OtherHeater wrap rating65Watts
OtherPlug cord length75 (3)mm (in.)
OtherPower cord length1677 (66)mm (in.)
OtherPower cord length1830 (72)mm (in.)
OtherPower cord length483 (19)mm (in.)
PressureLPG fuel supply1.7-2.7kPa
PressureNatural gas fuel supply0.9-2.7kPa
SpeedEngine overspeed shutdown115% of normal running speed for >0.3 sec
SpeedEngine speed high shutdown115% of normal running speed for >0.3 sec
SpeedEngine speed low shutdown85% of normal running speed for >3 sec
SpeedEngine underspeed shutdown85% of normal running speed for >3 sec
TemperatureCarburetor heater thermostat OFF16 ± 3C (60 ± 5F)
TemperatureCarburetor heater thermostat ON4 ± 4C (40 ± 7F)
TemperatureExhaust temperature260Cat rated kW
TemperatureThermostat OFF16 ± 3°CThermostat OFF (60 ± 5°F)
TemperatureThermostat ON4 ± 4°CThermostat ON (40 ± 7°F)
TemperatureThermostat off temperature27C (80 F)
TemperatureThermostat on temperature16C (60 F)
TorqueSpark plug18ft. lb.
TorqueSpark plug22ft. lb.
TorqueSpark plug24.4Nm
TorqueSpark plug24.4-29.8Nm (18-22 ft. lb.)
TorqueSpark plug29.8Nm
TorqueSpark plug torque15Nm (11 ft. lb.)
TorqueSpark plug torque18Nm (13.3 ft. lb.)
TorqueSpark plug torque24.4--29.8Nm (18--22 ft. lb.)
TorqueSpark plug torque25Nm (18 ft. lb.)
VoltageBattery charger output13.4 ±2%VDC, max 2.5 A
VoltageBattery specific gravity, fully charged1.260specific gravitycorrected to 80°F (26.7°C)
VoltageBattery specific gravity, needs chargingbelow 1.215specific gravitycorrected to 80°F (26.7°C)
VoltageEngine starting electrical system12VDC, negative ground
VoltageGenerator output voltage high shutdown120% of nominal system voltage for >2 sec
VoltageGenerator output voltage low shutdown80% of nominal system voltage for >10 sec
VoltageVoltage regulation1.0%no-load to full-load RMS

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Recommended fluids

FluidGradeStandardAmbientCapacityNotes
Engine oil10W-50 extended-life synthetic1.9 L (qt.)Premium oil option, 26 kW models, requires fewer oil changes
Engine oil5W-30 or 10W-30API (American Petroleum Institute) Service Class SG, SH, or SJ synthetic oil1.8 L (1.9 qt.) - 14 kW models20 kW models: 1.9 L (2.0 qt.)
Engine oil5W-30 or 10W-30 API Service Class SG, SH, or SJ syntheticAPI SG/SH/SJ1.8 L (qt.)14 kW models
Engine oilSynthetic, API Service Class SG or higherAPI SG or higherCheck oil level at or near, not over, full mark on dipstick before operation
FuelNatural gas or propaneCertified for emergency standby use only
FuelNatural Gas or LPGNatural gas: 90% min methane. LPG: 85% min propane. Fuel supply pressure: Natural gas 0.9-2.7 kPa, LPG 1.7-2.7 kPa
FuelNatural gas or LPGGenerator set is certified for emergency standby operation only

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Fault codes

30
CodeNameMeaningSeverityAction
AC Sens LossAC Sensing LostIn Auto mode, generator output AC sensing is lost. Detection begins 10 seconds after crank disconnect.WarningContact authorized distributor/dealer for service
ATS ComErrorATS Communication ErrorWarning is displayed if ATS interface connection is lostWarningCheck communication wiring between transfer switch interface board and generator set.
ATS PhaseRotATS PhaseRotTransfer switch phase rotation does not match; ATS will not transferWarningCorrect the ATS connection. Refer to the ATS Installation manual, wiring diagrams, and labels on the transfer switch.
Accy PwrOverAccessory Power OverloadAn over current fault (short circuit) on the accessory controller power outputWarningContact authorized distributor/dealer for service
Accy PwrOver WarningAccy PwrOver WarningAn over current fault (short circuit) on the accessory controller power output.WarningContact an authorized distributor/dealer for service
Advanced DiagnosticAdvanced DiagnosticShutdown during the reduced speed portion of an exercise. Event history shows Advanced Diagnostic Active. Engine restarts, runs at full speed for 2 minutes, and stops. Controller returns to AUTO mode.ShutdownIf the generator set does not restart and return to AUTO, check for other faults that prevent generator set operation.
Aux InputAuxiliary InputOptional customer-connected input (from PIM) is closedShutdownCheck customer-supplied equipment.
Batt Chg FltBattery Charger FaultInput to PIM from an external battery charger (not the built-in battery charger).WarningCheck external battery charger.
Battery CrLoBattery Crank LowEngine starting battery voltage falls below 11 VDC for more than 10 secondsWarningClears when battery voltage returns to acceptable level
Battery CrLo WarningLow Cranking Battery Voltage WarningEngine starting battery voltage falls below 11 VDC for more than 10 seconds. Inhibited during crank cycle. Clears when battery voltage returns to acceptable level.WarningCheck the battery rating and condition. Check the battery charger operation. Charge or replace the battery.
Battery HighBattery HighEngine starting battery voltage rises above 16 VDC for more than 10 seconds (inhibited during crank)WarningCheck battery rating/condition and charger operation
Battery Voltage HighBattery Voltage HighEngine starting battery voltage rises above 16 VDC for more than 10 seconds. Inhibited during crank cycle. Clears when voltage returns to acceptable level.WarningCheck the battery rating and condition. Check the battery charger operation.
Battery Voltage LowBattery Voltage LowEngine starting battery voltage falls below 12.5 VDC for more than 90 seconds when engine not running. Not operative during crank cycle. Clears when voltage returns to acceptable level.WarningCheck the battery rating and condition. Check the battery charger operation. Charge or replace the battery.
Eng Speed HighEng Speed HighEngine speed exceeds 115% of normal running speed for more than 0.3 secondsShutdownContact an authorized distributor/dealer for service
Eng Speed LowEng Speed LowEngine speed drops below 85% of normal running speed for more than 3 secondsShutdownReduce the load; on 20RCA/RCAL check enclosure thermostat; contact dealer if it persists
Engine Speed HighEngine Speed HighEngine speed exceeds 115% of the normal running speed for more than 0.3 seconds.ShutdownContact an authorized dealer for service.
Engine Speed LowEngine Speed LowEngine speed drops below 85% of the normal running speed for more than 3 seconds.ShutdownReduce the load. Check enclosure thermostat and reset if tripped. Contact an authorized dealer for service.
Exer Not SchExercise Not ScheduledNo exercise is scheduled on the controller.WarningSet the exerciser per Section 3.6
Frequency HighFrequency HighGoverned frequency exceeds 110% of the system's frequency setpoint for more than 10 seconds. Active 10 seconds after engine start.ShutdownContact an authorized distributor/dealer for service
Frequency LowFrequency LowGoverned frequency falls below 90% of the system frequency setting for more than 10 seconds, or 1 Hz below setting for more than 60 seconds. Active 10 seconds after engine start.ShutdownReduce the load and restart; on 20RCA/RCAL check enclosure thermostat; contact dealer if it persists
Lo Crank VltLow Cranking VoltageBattery voltage dropped below 3.5 VDC during engine cranking.WarningCharge or replace the battery.
Locked RotorLocked RotorNo engine rotation sensed during cranking; shuts down 3 seconds after detectionShutdownCheck the battery. Check for loose connections. Contact an authorized dealer for service.
Low Oil Level or Oil PressureLow Oil Level or Oil PressureOil level switch on the 26 kW indicates low oil level. LOP switch indicates low oil pressure for more than 5 seconds. Active 30 seconds after crank disconnect. Does not protect against low oil level.ShutdownCheck for leaks in the lubrication system. Check the oil level and add oil if low. Check the oil level or oil pressure switch and wiring. If fault persists, do not run the generator set; contact an authorized dealer.
MainPwrOverLMainPwrOverLMain power overload; an over current fault on the controller output (short circuit).ShutdownContact an authorized distributor/dealer for service
Not in AutoNot in AutoThe generator set is not in Automatic (standby) mode. Remote start and stop commands from a transfer switch or remote switch will be ignored.WarningPress AUTO to place the generator set in Automatic mode, when appropriate.
Oil Press LowOil Pressure LowThe LOP switch indicates low oil pressure for more than 5 seconds. Function becomes active 30 seconds after crank disconnect (30 second inhibit). The low oil pressure shutdown does not protect against low oil level.ShutdownCheck for leaks in the lubrication system. Check the oil level and add oil if the level is low. Check the oil pressure switch and wiring. If the fault persists, do not run the generator set. Contact an authorized dealer for service.
Over CrankOver CrankThree unsuccessful starting attempts.ShutdownCheck the fuel supply, spark plug, and battery. Check for loose connections. Contact an authorized dealer for service.
Spd Sens FltSpeed Sensor FaultEngine speed sensor has failed or engine stalled.ShutdownContact an authorized distributor/dealer for service
Volts L1-L2 HighVolts L1-L2 HighOutput voltage exceeds 120% of the system nominal voltage for more than 2 seconds.ShutdownContact an authorized distributor/dealer for service
Volts L1-L2 LowVolts L1-L2 LowOutput voltage falls below 80% of the nominal system voltage for more than 10 seconds.ShutdownReduce the load and restart; on 20RCA/RCAL check enclosure thermostat; contact dealer if it persists

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Procedures

12
RDC2 Voltage Calibration Using SiteTech adjustment

Tools: digital voltmeter, personal computer, SiteTech software

  1. Connect PC to controller via USB
  2. With generator off, connect multimeter across L1/L2 (AC volts)
  3. Start generator set
  4. Compare voltmeter reading to controller display
  5. Calculate new Genset Calibration Factor Voltage using (Vmeter / Vcontrol) x Fold = Fnew
  6. Enter new value into SiteTech and click Apply Changes
  7. Verify voltmeter matches controller display
  8. Repeat for L2-L3 and L3-L1 if three-phase
  9. Press OFF to stop generator set
RDC2 Voltage Calibration Using the Controller Keypad adjustment

Tools: digital voltmeter

  1. With generator off, connect digital multimeter across L1 and L2, set to AC volts
  2. Start generator set with RUN button
  3. Navigate to Generator Metering menu, press Select; Volts L1-L2 displayed
  4. Press Select; voltage number flashes
  5. Use up/down arrows to match voltmeter reading
  6. Press Select to confirm
  7. Step to Return screen
  8. Press OFF to stop generator set
VSC Current (Load) Calibration Using the Controller Keypad adjustment

Tools: clamp-on DC current probe or DC current meter

  1. Connect DC current probe/clamp meter to measure generator current
  2. Start generator with RUN button
  3. Adjust system voltage to obtain rated current output with battery bank attached (or use load bank)
  4. Trip output breaker
  5. Navigate to Generator Metering menu, select Generator Load
  6. Press and hold Select for No-Load Calibration; verify breaker open, confirm Yes
  7. Close output breaker; verify rated output current, confirm Yes
  8. Verify displayed load is correct; recalibrate if necessary
  9. Press OFF to stop generator set
Resetting the Controller After a Fault Shutdown diagnostic

⚠ Always identify and correct cause of fault before resetting

  1. Press Select to go to Overview menu while fault message is displayed
  2. Press Select again to show active fault message
  3. Press Select; 'Confirm Clear Fault: NO' displayed
  4. Press UP arrow; 'Confirm Clear Fault: YES' displayed
  5. Press Select to clear fault
  6. Press Select to return to overview menu; controller changes to OFF mode
  7. Press AUTO to place generator set in automatic mode
Access the Air Intake Area installation
  1. Unlock and raise the enclosure roof.
  2. Pull the air intake panel up and off its four bushings.
  3. Remove the cover panel over the terminal block to make electrical connections.
  4. After connections complete and battery installed, reinstall panels.
Battery Installation Procedure installation

⚠ Battery acid can cause severe injury or death

⚠ Explosion hazard from battery gases

  1. Ensure starting battery is fully charged before placing in service.
  2. Clean battery posts and/or adapters if necessary.
  3. Install battery post adapters, if needed.
  4. Place battery in the housing.
  5. Connect positive (+) lead to engine starting battery.
  6. Connect negative (-) lead to engine starting battery.
Fuel Conversion from NG to LPG, 14RCA/L (Original Fuel System) installation

⚠ Disconnect battery before working on generator set

⚠ Explosive fuel vapors can cause severe injury or death

Tools: straight-blade screwdriver, gas leak detector

  1. Press OFF button on generator set controller.
  2. Disconnect utility power to the generator.
  3. Disconnect engine starting battery, negative lead first.
  4. Turn off and disconnect the fuel supply.
  5. Remove hose clamp and fuel hose from hose fitting.
  6. Use straight-blade screwdriver to remove NG orifice from hose fitting.
  7. Insert LPG orifice into hose fitting and tighten until snug.
  8. Slide hose onto hose fitting and secure with clamp.
  9. Disconnect ignition timing leads 65 and N3 for LPG.
  10. Connect and turn on the new fuel supply.
  11. Reconnect battery leads, negative lead last.
  12. Reconnect utility power to the generator.
  13. Start generator by pressing RUN button.
  14. Check for leaks using a gas leak detector.
  15. Run generator and check operation; press OFF when done.
Fuel Selection, Revised Fuel System, 14/20/26RCA/L installation

⚠ Explosive fuel vapors can cause severe injury or death

Tools: gas leak detector

  1. Press OFF button on generator set controller.
  2. Disconnect utility power to the generator set.
  3. Disconnect engine starting battery, negative lead first.
  4. Turn off the fuel supply.
  5. For NG, turn selection knob clockwise to UP arrow; for LPG, turn counterclockwise about 1/4 turn.
  6. For NG, connect ignition timing lead 65 to N3; for LPG, disconnect lead 65 from N3.
  7. Connect and turn on fuel supply, ensuring it matches the fuel setting.
  8. Reconnect battery leads, negative lead last.
  9. Reconnect utility power to the generator.
  10. Change fuel type setting on RDC2 controller in Genset System menu.
  11. Start generator by pressing RUN button.
  12. Check for leaks using a gas leak detector.
  13. Run generator and check operation; press OFF when done.
Install Carburetor Heater, 17/18/20 kW Models installation

⚠ Accidental starting can cause severe injury or death; disconnect battery cables before working on the generator set, negative lead first.

⚠ Hazardous voltage will cause severe injury or death; disconnect all power sources before opening the enclosure.

⚠ Hot surfaces: disconnect power to the heater and allow it to cool before servicing.

  1. Open enclosure roof; locate controller and air cleaner.
  2. Turn off the generator set (master switch or controller OFF button, per model).
  3. Disconnect AC power to the generator set at the distribution panel breaker.
  4. Disconnect the starting battery, negative lead first.
  5. Check nameplate model/spec number and locate heater position per Figure 4.
  6. Remove the air cleaner cover if needed for access.
  7. Disconnect the heating element from the power cord at the plug connector.
  8. Insert the heating element into the threaded opening on the engine and tighten.
  9. Reconnect the power cord to the heater.
  10. Route and connect the power cord per the applicable model wiring option (steps 10-12).
  11. Replace the air cleaner cover if it was removed.
  12. Affix decal GM22387 onto the air cleaner cover.
  13. Reconnect the starting battery, negative lead last.
  14. Reconnect AC power by closing the distribution panel breaker.
  15. For standby operation, move switch to AUTO and reinstall enclosure panels.
Install Carburetor Heater, Models 8-12RESV/RESVL installation

⚠ Accidental starting can cause severe injury or death; disconnect battery cables before working on the generator set, negative lead first.

⚠ Hazardous voltage will cause severe injury or death; disconnect all power sources before opening the enclosure.

⚠ Hot surfaces: install the heater before connecting it to power; disconnect power and allow it to cool before servicing.

  1. Open the enclosure roof.
  2. Press the OFF button on the generator set controller.
  3. Disconnect AC power to the generator set at the distribution panel breaker.
  4. Disconnect the starting battery, negative lead first.
  5. Locate the carburetor heater per Figure 14; remove side panel or air cleaner cover if needed.
  6. Remove and discard the M8 bolt from the carburetor at the heater location.
  7. Thread adapter GM91361 into the M8 hole.
  8. Insert carburetor heater GM57968 into the adapter and tighten.
  9. Connect the extension cord (GM91360 or 3-way GM95628) to the heater cord.
  10. Route the cord to the AC receptacle, securing away from throttle linkage and exhaust.
  11. Plug the cord into the AC receptacle on the generator bulkhead.
  12. Affix decal GM22387 onto the air cleaner cover.
  13. Reconnect the starting battery, negative lead last.
  14. Reconnect AC power by closing the distribution panel breaker.
  15. Press AUTO for standby operation and reinstall enclosure panels.
Installation Procedure, 17/18/20 kW Models installation

⚠ Disconnect battery cables before working on generator set; remove negative lead first.

⚠ Disconnect all power sources before opening enclosure.

⚠ Install heater before connecting power; allow to cool before servicing.

  1. Open enclosure roof; locate controller and engine air cleaner.
  2. Turn off generator set: 17/18RES/RESL move master switch OFF; 20RES/RESL press OFF and remove fuse F3; 20RESA/AL/B/C/CL/D press OFF.
  3. Disconnect AC power by opening circuit breaker in distribution panel.
  4. Disconnect engine starting battery, negative lead first.
  5. Check nameplate model/spec; see Figure 4 for heater location. Heater fits threaded opening on carburetor below air cleaner.
  6. Remove air cleaner cover if easier access needed.
  7. Disconnect heater element from power cord at plug connector (GM57968 or GM88228).
  8. Insert heating element into threaded opening on engine and tighten.
  9. Reconnect power cord to heater.
  10. For 17/18RES/RESL and 20RES/RESL: remove air intake panel; install bushing X-634-15 or X-634-16; route cord through bulkhead; plug into 120 VAC receptacle under controller.
  11. For 120 V 20RESA/AL/B/C/CL/D: route cord away from hot parts; plug into receptacle in engine compartment; use 3-way cord GM95628 if multiple accessories; secure excess cable.
  12. For 240 V 14/20RESA and 20RESC: remove controller screws, remove bulkhead knockout, route cord and insert plug; disconnect 120 VAC harness at 3-pin; connect 3-pin to new 240 VAC connector.
  13. Replace air cleaner cover if removed; affix decal GM22387 as shown.
  14. Check master switch OFF (17/18); reconnect battery, negative last; close distribution breaker. 20RES/RESL: reinstall fuse F3.
  15. For standby, move master switch to AUTO or press AUTO. Reinstall enclosure panels; close and lock roof.
Installation Procedure, Models 8-12RESV/RESVL installation

⚠ Disconnect battery cables before working on generator set; remove negative lead first.

⚠ Disconnect all power sources before opening enclosure.

⚠ Install heater before connecting power; allow to cool before servicing.

  1. Open enclosure roof.
  2. Press OFF button on generator set controller.
  3. Disconnect AC power by opening circuit breaker in distribution panel.
  4. Disconnect engine starting battery, negative lead first.
  5. See Figure 13 for heater location. Remove louvered side panel and/or air cleaner cover for access if necessary.
  6. Remove and discard M8 bolt from carburetor at heater location.
  7. Thread adapter GM91361 into M8 hole.
  8. Insert carburetor heater GM57968 into adapter and tighten.
  9. Connect extension cord GM91360 or 3-way extension cord GM95628 to heater cord.
  10. Route cord to AC receptacle as shown; secure with cable ties away from throttle linkage and exhaust.
  11. Plug cord into AC receptacle on generator bulkhead.
  12. Affix decal GM22387 onto air cleaner cover.
  13. Reconnect battery, negative lead last.
  14. Reconnect AC power by closing circuit breaker.
  15. For standby, press AUTO. Reinstall enclosure panels; close and lock roof.

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Voltage reconnection

VoltagePhaseConnectionLeadsNotes
12-volt engine electrical system, single starter motor, negative groundBattery negative to ground terminal on or near starter motor; battery positive to positive terminal on starter solenoidAll generator set models use a negative ground with a 12-volt engine electrical system
Engine start connection for non-RXT transfer switch or remote start/stop switchTerminals 3 and 4 on generator set terminal blockRoute engine start leads through separate conduit from AC power and load leads
RXT transfer switch to generator set terminal block A, B, PWR, COMP10-1 through P10-4 (transfer switch) to A, B, PWR, COM (generator set)Terminal block connections 3 and 4 not used with Model RXT ATS
100/2001Single
100/2003Delta
110/2201Single
110/2203Delta
115/2301Single
12 VDCSingle starter motor, negative ground engine electrical systemPositive (+) to starter solenoid terminal; negative (-) to ground terminal on or near starter motorRemove negative lead first when disconnecting, reconnect negative lead last
1201SingleGenset System Voltage/Frequency/Phase table for controller setup
120/2083Wye
120/208, 120/240, 277/48033-phase 2G712
120/24012F7 (4 lead)4Single phase, 1.0 power factor
120/2401Single
120/2401Single phase41.0 power factor
120/2401Single phase 2F74
120/2403Delta
127/2203Wye
2201Single
220/3803Wye
2301Single
230/4003Wye
2401Single
240/4163Wye
277/4803Wye

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Common questions

What is the oil capacity of the Kohler CH1000?

The Kohler CH1000 engine has an oil capacity of 1.9 liters.

What is the displacement of the Kohler CH1000?

The Kohler CH1000 has a displacement of 0.999 liters with 2 cylinders.

Which generators use the Kohler CH1000 engine?

The Kohler CH1000 powers 4 generator set(s), including Kohler 18RCAL, Kohler 20RCA, Kohler 20RES, Kohler RESA.

How often should you change the oil in the Kohler CH1000?

The Kohler CH1000 oil change interval is every 200 hours.

What is a common problem with the Kohler CH1000 engine?

A commonly reported issue on generators using the Kohler CH1000 is: The generator set cranks but does not start, starts hard, lacks power, or operates erratically.. Cause: Air cleaner clogged.. Fix: Clean and/or replace the air cleaner..