Kohler — Starter Solenoid Pull-In Coil Test
Testing & diagnosis · Starter System
From a Kohler service manual covering: CH1000, CH940, CH960, CH980. Check it applies to your exact model before use.
Applies to: Kohler CH940, Kohler CH960, Kohler CH980
Before you start
- Do not leave 12 volt test leads connected longer than necessary.
Procedure
- Use a 12 volt power supply and 2 test leads.
- Connect 1 lead to flat spade S/start terminal on solenoid.
- Momentarily connect other lead to lower large post terminal.
- Solenoid should energize with audible click and plunger should retract.
- Repeat test several times.
- Use ohmmeter on Rx2K scale across 2 large post terminals.
- Perform actuation test and check for continuity.