Kohler TP-6808 — Automatic Operation Test

Testing & diagnosis · transfer switch and generator set controller

For the Kohler TP-6808, from the Kohler service manual.

Browse Kohler generators & specs →

Procedure

  1. Use the generator set controller to schedule a loaded exercise.
  2. Set the exercise mode to Loaded Full Speed.
  3. Set Exercise time a few minutes after current time; set date to today.
  4. Press AUTO on the generator set controller.
  5. Verify the engine starts and the transfer switch transfers the load.
  6. After 20 minutes, verify load transfers back to utility power.
  7. Reprogram the exerciser for 20 minutes weekly or every two weeks.

Source: Kohler service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.