Service parts for the 15REOZD
Grouped by system, with how many of each the parts manual calls for.
Air intake
1 requiredFuel system
1 requiredOil system
1 requiredBelts
1 requiredPrices captured from merchant listings; some links are affiliate links. Confirm against your serial number before ordering.
Specifications
| Fuel | Diesel |
|---|---|
| Frequency | 60.0 Hz |
| Standby power | 15 kW |
| Controller | Decision-Maker 3000 |
| Oil capacity | 4.7 L |
| Alternator | GM78570-MA5 |
| Voltage options | 120 V, 240 V |
| Phase | Single |
| Rated current | 20 A |
| Circuit breaker | 20 A |
| Battery group | Group 27 |
| Battery cranking | 650 CCA |
| Battery voltage | 12 V |
| Battery quantity | 1 |
| Coolant capacity | 2.0 L |
| Wet weight | 748 kg |
| Sound level | 71.0 dBA @ 7 m |
| Fuel tank | 152.0 L |
Filters & service parts
model family| Item | Spec | Capacity | Part # | Interval | |
|---|---|---|---|---|---|
| Air filter | ×1 | GM42265 | 250 hr | Amazon eBay | |
| Fuel filter | GM32359 | 50 hr | Amazon $22.24 eBay $26.87 KuduParts $20.00 | ||
| Oil filter | 252834 | 50 hr | Amazon $13.66 eBay $27.95 PartsGeek $7.98 | ||
| Belt | 225022 | 50 hr | Amazon eBay |
Compiled from this model's family documentation — may include parts for closely-related variants. Confirm the exact part for your serial number.
Service specifications
52| Type | Item | Value | Unit | Condition |
|---|---|---|---|---|
| Torque | American Standard fastener 1-12 | 283.0 Nm (209 ft. lb.) | Nm (ft. lb.) | assembled into cast iron or steel, grade 2 or 5 |
| Torque | American Standard fastener 1-8 | 259.0 Nm (191 ft. lb.) | Nm (ft. lb.) | assembled into cast iron or steel, grade 2 or 5 |
| Torque | American Standard fastener 1/2-13 | 60.0 Nm (44 ft. lb.) | Nm (ft. lb.) | assembled into cast iron or steel, grade 2 or 5 |
| Torque | American Standard fastener 1/2-20 | 66.0 Nm (49 ft. lb.) | Nm (ft. lb.) | assembled into cast iron or steel, grade 2 or 5 |
| Torque | American Standard fastener 1/4-20 | 6.8 Nm (60 in. lb.) | Nm (in. lb.) | assembled into cast iron or steel, grade 2 or 5 |
| Torque | American Standard fastener 1/4-28 | 8.1 Nm (72 in. lb.) | Nm (in. lb.) | assembled into cast iron or steel, grade 2 or 5 |
| Torque | American Standard fastener 10-24 | 2.9 Nm (26 in. lb.) | Nm (in. lb.) | assembled into cast iron or steel, grade 2 or 5 |
| Torque | American Standard fastener 10-32 | 2.9 Nm (26 in. lb.) | Nm (in. lb.) | assembled into cast iron or steel, grade 2 or 5 |
| Torque | American Standard fastener 3/4-10 | 199.0 Nm (147 ft. lb.) | Nm (ft. lb.) | assembled into cast iron or steel, grade 2 or 5 |
| Torque | American Standard fastener 3/4-16 | 222.0 Nm (164 ft. lb.) | Nm (ft. lb.) | assembled into cast iron or steel, grade 2 or 5 |
| Torque | American Standard fastener 3/8-16 | 24.0 Nm (18 ft. lb.) | Nm (ft. lb.) | assembled into cast iron or steel, grade 2 or 5 |
| Torque | American Standard fastener 3/8-24 | 27.0 Nm (20 ft. lb.) | Nm (ft. lb.) | assembled into cast iron or steel, grade 2 or 5 |
| Torque | American Standard fastener 5/16-18 | 13.6 Nm (120 in. lb.) | Nm (in. lb.) | assembled into cast iron or steel, grade 2 or 5 |
| Torque | American Standard fastener 5/16-24 | 14.9 Nm (132 in. lb.) | Nm (in. lb.) | assembled into cast iron or steel, grade 2 or 5 |
| Torque | American Standard fastener 5/8-11 | 113.0 Nm (83 ft. lb.) | Nm (ft. lb.) | assembled into cast iron or steel, grade 2 or 5 |
| Torque | American Standard fastener 5/8-18 | 128.0 Nm (94 ft. lb.) | Nm (ft. lb.) | assembled into cast iron or steel, grade 2 or 5 |
| Torque | American Standard fastener 7/16-14 | 39.0 Nm (29 ft. lb.) | Nm (ft. lb.) | assembled into cast iron or steel, grade 2 or 5 |
| Torque | American Standard fastener 7/16-20 | 43.0 Nm (32 ft. lb.) | Nm (ft. lb.) | assembled into cast iron or steel, grade 2 or 5 |
| Torque | American Standard fastener 8-32 | 1.8 Nm (16 in. lb.) | Nm (in. lb.) | assembled into cast iron or steel, grade 2 or 5 |
| Torque | American Standard fastener 9/16-12 | 81.0 Nm (60 ft. lb.) | Nm (ft. lb.) | assembled into cast iron or steel, grade 2 or 5 |
| Torque | American Standard fastener 9/16-18 | 91.0 Nm (67 ft. lb.) | Nm (ft. lb.) | assembled into cast iron or steel, grade 2 or 5 |
| Torque | Metric fastener M10 x 1.25 | 31.0 Nm (23 ft. lb.) | Nm (ft. lb.) | assembled into cast iron or steel, grade 5.8 or 8.8 |
| Torque | Metric fastener M10 x 1.50 | 30.0 Nm (22 ft. lb.) | Nm (ft. lb.) | assembled into cast iron or steel, grade 5.8 or 8.8 |
| Torque | Metric fastener M12 x 1.50 | 56.0 Nm (41 ft. lb.) | Nm (ft. lb.) | assembled into cast iron or steel, grade 5.8 or 8.8 |
| Torque | Metric fastener M12 x 1.75 | 53.0 Nm (39 ft. lb.) | Nm (ft. lb.) | assembled into cast iron or steel, grade 5.8 or 8.8 |
| Torque | Metric fastener M14 x 1.50 | 87.0 Nm (64 ft. lb.) | Nm (ft. lb.) | assembled into cast iron or steel, grade 5.8 or 8.8 |
| Torque | Metric fastener M14 x 2.00 | 83.0 Nm (61 ft. lb.) | Nm (ft. lb.) | assembled into cast iron or steel, grade 5.8 or 8.8 |
| Torque | Metric fastener M16 x 1.50 | 132.0 Nm (97 ft. lb.) | Nm (ft. lb.) | assembled into cast iron or steel, grade 5.8 or 8.8 |
| Torque | Metric fastener M16 x 2.00 | 127.0 Nm (94 ft. lb.) | Nm (ft. lb.) | assembled into cast iron or steel, grade 5.8 or 8.8 |
| Torque | Metric fastener M18 x 1.50 | 189.0 Nm (140 ft. lb.) | Nm (ft. lb.) | assembled into cast iron or steel, grade 5.8 or 8.8 |
| Torque | Metric fastener M18 x 2.50 | 179.0 Nm (132 ft. lb.) | Nm (ft. lb.) | assembled into cast iron or steel, grade 5.8 or 8.8 |
| Torque | Metric fastener M6 x 1.00 | 6.2 Nm (4.6 ft. lb.) | Nm (ft. lb.) | assembled into cast iron or steel, grade 5.8 or 8.8 |
| Torque | Metric fastener M8 x 1.00 | 16.0 Nm (11 ft. lb.) | Nm (ft. lb.) | assembled into cast iron or steel, grade 5.8 or 8.8 |
| Torque | Metric fastener M8 x 1.25 | 15.0 Nm (11 ft. lb.) | Nm (ft. lb.) | assembled into cast iron or steel, grade 5.8 or 8.8 |
| Torque | Pressure wire connector with internal-drive socket-head screw; socket size across flats 12.7 mm (1/2 in.) | 56.5 Nm (500 in. lb.) | Nm (in. lb.) | |
| Torque | Pressure wire connector with internal-drive socket-head screw; socket size across flats 14.3 mm (9/16 in.) | 67.8 Nm (600 in. lb.) | Nm (in. lb.) | |
| Torque | Pressure wire connector with internal-drive socket-head screw; socket size across flats 3.2 mm (1/8 in.) | 5.1 Nm (45 in. lb.) | Nm (in. lb.) | |
| Torque | Pressure wire connector with internal-drive socket-head screw; socket size across flats 4.0 mm (5/32 in.) | 11.4 Nm (100 in. lb.) | Nm (in. lb.) | |
| Torque | Pressure wire connector with internal-drive socket-head screw; socket size across flats 4.8 mm (3/16 in.) | 13.8 Nm (120 in. lb.) | Nm (in. lb.) | |
| Torque | Pressure wire connector with internal-drive socket-head screw; socket size across flats 5.6 mm (7/32 in.) | 17.0 Nm (150 in. lb.) | Nm (in. lb.) | |
| Torque | Pressure wire connector with internal-drive socket-head screw; socket size across flats 6.4 mm (1/4 in.) | 22.6 Nm (200 in. lb.) | Nm (in. lb.) | |
| Torque | Pressure wire connector with internal-drive socket-head screw; socket size across flats 7.9 mm (5/16 in.) | 31.1 Nm (275 in. lb.) | Nm (in. lb.) | |
| Torque | Pressure wire connector with internal-drive socket-head screw; socket size across flats 9.5 mm (3/8 in.) | 42.4 Nm (375 in. lb.) | Nm (in. lb.) | |
| Torque | Screw-type pressure wire connector, wire size 1/0-2/0 AWG (53.5-67.4 mm2), other connections | 20.3 Nm (180 in. lb.) | Nm (in. lb.) | |
| Torque | Screw-type pressure wire connector, wire size 1250-2000 kcmil (635-1016 mm2), other connections | 67.8 Nm (600 in. lb.) | Nm (in. lb.) | |
| Torque | Screw-type pressure wire connector, wire size 18-10 AWG (0.82-5.3 mm2), other connections | 8.5 Nm (75 in. lb.) | Nm (in. lb.) | |
| Torque | Screw-type pressure wire connector, wire size 250-350 kcmil (127-177 mm2), other connections | 36.7 Nm (325 in. lb.) | Nm (in. lb.) | |
| Torque | Screw-type pressure wire connector, wire size 3 AWG (26.7 mm2), other connections | 16.9 Nm (150 in. lb.) | Nm (in. lb.) | |
| Torque | Screw-type pressure wire connector, wire size 3/0-4/0 AWG (85.0-107.2 mm2), other connections | 28.2 Nm (250 in. lb.) | Nm (in. lb.) | |
| Torque | Screw-type pressure wire connector, wire size 500 kcmil (253 mm2), other connections | 42.4 Nm (375 in. lb.) | Nm (in. lb.) | |
| Torque | Screw-type pressure wire connector, wire size 6-4 AWG (13.3-21.2 mm2), other connections | 12.4 Nm (110 in. lb.) | Nm (in. lb.) | |
| Torque | Screw-type pressure wire connector, wire size 800-1000 kcmil (406-508 mm2), other connections | 56.5 Nm (500 in. lb.) | Nm (in. lb.) |
Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.
Recommended fluids
| Fluid | Grade | Standard | Ambient | Capacity | Notes |
|---|---|---|---|---|---|
| Fuel | No. 2 domestic burner oil (diesel) | Fuel Inlet 1/4 NPT; Fuel Return 8 mm (5/16 in.); day tank sizes 38-3952 L (10-1044 gal.); day tank should provide at least 4 hours of fuel consumption; main tank recommended sized for 8 hours of operation at rated load if no code requirement applies; never fill tank more than 95% full |
Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.
Fault codes
2| Code | Name | Meaning | Severity | Action |
|---|---|---|---|---|
| CO-3 | Fault displayed if the CO parameter is set incorrectly | Shutdown | ||
| CO-6 | Fault displayed if the CO parameter is set incorrectly | Shutdown |
Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.
Procedures
12Controller Configuration adjustment
⚠ Be sure to save the new settings immediately before exiting the configuration mode; changes are lost if the controller times out (about 1 minute).
- Hold the Select button and move the master switch to RUN to enter configuration mode.
- Press the down arrow key then the up arrow key 3 times to enter configuration mode (password).
- Set the voltage/frequency parameter Uu for the model.
- Set the unit configuration parameter Uc (marine, standby, mobile).
- Set the engine type parameter Ec.
- Press the up arrow at the Adnc display to enter advanced configuration mode.
- Set the engine data input type Ed.
- Set the battery voltage Bt (12 or 24 VDC).
- Set the communications parameter Cn.
- Enter save mode and save your settings before exiting.
Output Voltage and Frequency Adjustment adjustment
⚠ The generator set must be running during these adjustments.
⚠ The engine speed (frequency) adjustment menus are not accessible on models with mechanical governors.
Tools: multimeter
- Move the master switch to RUN; the engine starts and runtime hours display.
- Hold the Select button about 5 seconds until the program version number displays.
- Press the down arrow key then the up arrow key 3 times to enter adjustment mode.
- 1P: adjust voltage coarse in large increments (approximately 5-7 volts per step).
- 2P: adjust voltage fine in smaller increments (approximately 0.5-0.7 volts per step).
- Adjust voltage stability (gain) coarse and fine.
- 3P: set volts/Hz (00=low, 09=high).
- 4P: adjust engine governor speed coarse and fine.
- 5P: adjust engine governor stability (gain) coarse and fine.
- Enter SAVE mode and save settings before exiting the adjustment mode.
Voltage Regulator Adjustment Procedure adjustment
⚠ The voltage regulation menus on the Decision-Maker 3000 controller will not be displayed for these models.
Tools: voltmeter, frequency meter
- Verify that the generator set master switch is in the OFF/RESET position.
- Turn the Volts/Hz and the stability potentiometers fully counterclockwise. Connect the voltmeter to the AC circuit or an electrical outlet.
- Move the generator set master switch to the RUN position.
- Change the voltage adjustment control at the controller until the desired output voltage is achieved.
- Rotate the stability potentiometer clockwise until light flicker minimizes.
- Readjust the voltage adjustment control at the controller until the desired output voltage is achieved.
- If the engine has a speed adjustment governor, adjust engine speed to the specified cut-in frequency.
- Rotate the volts/Hz potentiometer clockwise until the voltage level begins to drop.
- Readjust the engine speed to 1800 rpm for 60 Hz models or 1500 rpm for 50 Hz models.
- Readjust the voltage adjustment control until the desired output is achieved.
- Readjust the stability potentiometer until light flicker minimizes.
- Move the generator set master switch to the OFF/RESET position.
Cooling System Checklist diagnostic
⚠ Shut down immediately if problems arise during startup
⚠ Recheck belt tension after 5-10 minutes and again after 8-12 hours of operation
- Verify cooling fan position in fan shroud
- Check mounting hardware
- Check fan motor for free rotation
- Check V-belts for alignment and tension
- Fill system with coolant and check all connections for tightness and leaks
- Verify electrical connections secure and power source matches motor nameplate
- Verify no foreign material loose in fan air stream
- With unit running check fan clearance, excessive vibration, excessive noise, coolant leaks
Battery Installation and Connection installation
⚠ Battery gases. Explosion can cause severe injury or death. Do not smoke or permit flames or sparks near a battery.
⚠ Remove the negative (--) lead first when disconnecting; reconnect the negative (--) lead last.
- Verify that the generator set master control switch is in the OFF/RESET position.
- Ensure that the starting battery is fully charged before placing the battery in service.
- Clean the battery posts and/or adapters if necessary.
- Install battery post adapters, if needed.
- Place the battery on the battery rack on the skid.
- Connect the red battery cable to the positive (+) battery terminal.
- Connect the black battery cable to the negative (--) battery terminal.
- Place the boots over the battery terminals.
- Plug the battery heater and battery charger, if equipped, into the 120 VAC power supply.
Controller Replacement installation
⚠ Disconnect the battery cables before working on the generator set; remove the negative lead first and reconnect it last.
Tools: multimeter, personal computer with Program Loader Software
- Record generator set information required for configuration: model, market, voltage, frequency, phases, battery voltage.
- Place the generator set master switch in the OFF position.
- Disconnect power to the battery charger, if equipped.
- Disconnect the engine starting battery(ies), negative lead first.
- Open the junction box; disconnect the controller at P1, J15, and J16.
- Models ECD/EFCD, EGD/EFGD, EGZD only: disconnect the CO sensor harness at the 4-pin connector.
- Remove four controller mounting screws and remove the old controller.
- ECD/EFCD, EGD/EFGD, EGZD only: install CO sensor module assembly GM46362 on the back of the new controller GM47982.
- Install the new controller and secure with the mounting screws.
- Reconnect the P1, J15, and J16 connectors; connect the CO sensor harness on applicable models.
- Models 10/13/15EG, 10/13/15ERG, 15/30RES, 15/30RYG with S/N before 2053692: cut a 1-in. section of the gray/orange lead entering pin 9 at the ECM connector.
- Check that the generator set master switch is in the OFF position.
- Reconnect the engine starting battery, negative lead last.
- Reconnect power to the battery charger, if equipped.
- Check the controller application software version and load the latest application code if necessary.
Lifting the Generator Set installation
⚠ Unbalanced and elevated weight. Do not lift the generator set from the engine or alternator eyes.
⚠ Never stand under a unit being lifted. Always maintain a safe distance from the unit being lifted.
- Install proper size rigging at the skid lifting eyes providing a direct pull on the skid lifting eye.
- Use a spreader bar to prevent lifting cables from contacting air cleaners, shrouds, or other protruding components.
- Select single or double spreader bar and hook method, or single or double spreader bar and skid lifting bar method.
- Protect cables, chains, and straps from sharp edges.
- After transporting, check radiator alignment and tighten hardware to specified torque.
Lifting the Generator Set with Attached Enclosure installation
⚠ Do not attach hoisting equipment to the enclosure.
- Enclosure attached directly to skid: lift the assembly by lifting on the skid.
- Enclosure attached directly to subbase fuel tank: lift by all subbase fuel tank lifting eyes.
- For generator set, enclosure, and subbase fuel tank package, use ALL lifting eyes on the subbase fuel tank.
Lifting the Subbase Fuel Tank installation
- Confirm the subbase fuel tank has lifting eyes.
- Empty the tank; do not lift a fuel tank containing fuel or any liquid.
- Remove any vent piping longer than 1 m (3.3 ft.) from the fuel tank.
- Attach one or two spreader bars as shown.
Prepare the Site, Indoor Installations, Open Units installation
- Clear all combustible materials from the generator set location.
- Lay a concrete pad that extends at least 152 mm (6 in.) beyond the generator set on all sides.
- Include mounting bolts at the locations shown on the dimension drawing.
- Provide air intake and outlet openings as described in Section 5.1.
Prepare the Site, Outdoor Installations, Enclosed Units installation
- Obtain a building permit and contact local utility companies to mark underground pipes and cables.
- Clear combustible materials from an area at least 2.4 m (8 ft.) beyond the exhaust end.
- Spread a 76-mm (3-in.) thick layer of gravel to support the concrete mounting pad.
- Lay a concrete pad that extends at least 152 mm (6 in.) beyond the generator set on all sides.
- Include mounting bolts at locations shown on the dimension drawing.
Procedure to Fill with Deaeration installation
- Fill the radiator at the filler neck
- Fill the radiator through a top tank or expansion/surge tank inlet before the final hose connection
- Continue filling until coolant appears in the sight glass in the radiator top tank
- Check and correct any leaks in the system
Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.
Voltage reconnection
| Voltage | Phase | Connection | Leads | Notes |
|---|---|---|---|---|
| 100 VAC | 1 | 1Ph, 2W | Uu00; 60 Hz | |
| 100 VAC | 1 | 1Ph, 3W | Uu00; 60 Hz | |
| 100-120/200--240 | single | 4-lead, 3-wire configuration (no jumper lead, two-pole circuit breaker required) | L1, L2 | Leads L1 and L2 are for different phases; never connect them together |
| 100-120/200-240 | single phase, 3-wire | does not use a jumper lead; use a two-pole circuit breaker | L1, L2 (different phases; never connect together) | Four-lead reconnection; application of two single-pole circuit breakers does not conform to NEC for a 200--240-volt load |
| 100/200 VAC | 1 | 1Ph, 3W | Uu08; 60 Hz | |
| 110 VAC | 1 | 1Ph, 2W | Uu05; 50 Hz | |
| 110 VAC | 1 | 1Ph, 3W | Uu05; 50 Hz | |
| 110/190 VAC | 3 | Wye | Uu17; 50 Hz | |
| 110/220 VAC | 1 | 1Ph, 3W | Uu07; 50 Hz | |
| 110/220 VAC | 1 | Dogleg | Uu07; 50 Hz | |
| 110/220 VAC | 3 | Delta | Uu15; 50 Hz | |
| 115 VAC | 1 | 1Ph, 2W | Uu05; 50 Hz | |
| 115/200 VAC | 3 | Wye | Uu23; 50 Hz | |
| 115/230 VAC | 1 | 1Ph, 3W | Uu02; 50 Hz | |
| 115/230 VAC | 1 | Dogleg | Uu06; 50 Hz | |
| 115/230 VAC | 3 | Delta | Uu14; 50 Hz | |
| 120 VAC | 1 | 1Ph, 2W | Uu00; 60 Hz | |
| 120 VAC | 1 | 1Ph, 3W | Uu00; 60 Hz | |
| 120/208 VAC | 3 | Wye | Uu11; 60 Hz | |
| 120/240 VAC | 1 | 1Ph, 3W | Uu01; 60 Hz | |
| 120/240 VAC | 1 | Dogleg | Uu01; 60 Hz | |
| 120/240 VAC | 3 | Delta | Uu10; 60 Hz | |
| 127/220 VAC | 3 | Wye | Uu16; 60 Hz | |
| 139/240 VAC | 3 | Wye | Uu10; 60 Hz | |
| 220 VAC | 1 | 1Ph, 2W | Uu12; 50 Hz | |
| 220/380 VAC | 3 | Wye | Uu19; 60 Hz | |
| 230 VAC | 1 | 1Ph, 2W | Uu02; 50 Hz | |
| 230/400 VAC | 3 | Wye | Uu03; 50 Hz | |
| 240 VAC | 1 | 1Ph, 2W | Uu13; 50 Hz | |
| 240/416 VAC | 3 | Wye | Uu20; 60 Hz |
Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.
Common questions
What size generator is the Kohler 15REOZD?
The Kohler 15REOZD is rated 15 kW standby.
What fuel does the Kohler 15REOZD use?
The Kohler 15REOZD runs on Diesel.
What alternator comes on the Kohler 15REOZD?
The Kohler 15REOZD uses a GM78570-MA5 alternator.
What oil filter fits the Kohler 15REOZD?
The Kohler 15REOZD uses oil filter part number 252834.
Which fuel filter part number does the Kohler 15REOZD take?
The Kohler 15REOZD uses fuel filter part number GM32359.
What air filter does the Kohler 15REOZD use?
The Kohler 15REOZD uses air filter part number GM42265.
Troubleshooting
4Symptoms & remedies
| Symptom | Cause | Remedy |
|---|---|---|
| Generator does not start | Faulty starter motor or battery | Check and replace the starter motor if necessary. Check and charge the battery. |
| Engine overheats | Coolant level is low, thermostat is faulty, radiator fins are dirty | Add coolant to recommended level. Replace thermostat if it is faulty. Clean radiator fins. |
| Generator produces insufficient power | Fuel filter is clogged, governor settings are incorrect | Clean or replace the fuel filter. Adjust governor settings as per manufacturer's instructions. |
| Engine runs rough | Air intake system is dirty, fuel solenoid is faulty | Inspect and clean air intake system. Check and replace fuel solenoid if necessary. |
Fault codes and symptom→remedy steps extracted from this model’s service/owner documentation; verify against the official manual before servicing.
Parts
26model family| Part # | Description | Qty | System | |
|---|---|---|---|---|
| 225006 | Gasket, thermostat | 1 | Gasket | Amazon eBay |
| 225022 | Belt, fan | 1 | Belt | Amazon eBay |
| 249865 | Gasket, thermostat | 1 | Gasket | Amazon eBay |
| 252834 | Filter, oil | 1 | Oil filter | Amazon $13.66 eBay $27.95 PartsGeek $7.98 |
| GM28823 | Sensor, oil temperature | 1 | Sensor | Amazon eBay $50.00 |
| GM32112-KA1 | Oil pressure sender kit (also -KP1) | Sensor | buy | |
| GM32359 | Filter, fuel | 1 | Fuel filter | Amazon $22.24 eBay $26.87 KuduParts $20.00 |
| GM34387 | Thermostat | 1 | Thermostat | Amazon eBay |
| GM35299-KA1 | Sender kit (also -KP1) | Sensor | buy | |
| GM42265 | Element, air cleaner | 1 | Air filter | Amazon eBay |
| GM42266 | Element, air cleaner | 1 | Air filter | Amazon eBay $22.50 |
| GM45891-KA1 | OP and WT sender kit | Sensor | buy | |
| GM46362 | CO sensor module assembly | 1 | Sensor | buy |
| GM47465 | Filter, oil | 1 | Oil filter | Amazon $13.66 eBay $23.52 FridayParts $20.19 |
| GM50552-KA1 | Oil pressure sender kit | Sensor | buy | |
| 223316 | Fuse, 10 A, 250 V | 1 | Service part / kit | Amazon $171.06 eBay $31.37 |
| GM28483 | SCR module | Service part / kit | FridayParts $258.90 | |
| GM28707 | Controller Assy ADC 2100 | 1 | Service part / kit | buy |
| GM32337-KP1 | Remote Digital Gauge for Marine | Service part / kit | buy | |
| GM32337-KP2 | Remote Digital Gauge for Mobile and Residential/Commercial | Service part / kit | buy | |
| GM42037 | Controller Assy ADC 2100 | 1 | Service part / kit | buy |
| GM46035-KP1 | Three-Inch Digital Gauge | Service part / kit | buy | |
| GM46308-KP1 | Electronic governor kit | Service part / kit | buy | |
| GM47164-KP1 | Electronic governor kit | Service part / kit | buy | |
| GM47982 | Controller Assy ADC 2100 | 1 | Service part / kit | buy |
| GM50822-KP1 | Two-Inch Digital Gauge | Service part / kit | buy |
Compiled from this model's family documentation — may include parts for closely-related variants. Confirm the exact part for your serial number. See the full parts catalog to search and cross-reference.
Fuel consumption
| Rating | Load | L/h | gal/h |
|---|---|---|---|
| Prime | 100% | 0.5 | 0.14 |
| Standby | 100% | 0.5 | 0.14 |