Kohler — Voltage Regulator Adjustment Procedure
Adjustments
From a Kohler service manual covering: 10REOZD, 15REOZD, 20REOZD. Check it applies to your exact model before use.
Applies to: Kohler 10REOZD, Kohler 15REOZD, Kohler 20REOZD
Before you start
- The voltage regulation menus on the Decision-Maker 3000 controller will not be displayed for these models.
Procedure
- Verify that the generator set master switch is in the OFF/RESET position.
- Turn the Volts/Hz and the stability potentiometers fully counterclockwise. Connect the voltmeter to the AC circuit or an electrical outlet.
- Move the generator set master switch to the RUN position.
- Change the voltage adjustment control at the controller until the desired output voltage is achieved.
- Rotate the stability potentiometer clockwise until light flicker minimizes.
- Readjust the voltage adjustment control at the controller until the desired output voltage is achieved.
- If the engine has a speed adjustment governor, adjust engine speed to the specified cut-in frequency.
- Rotate the volts/Hz potentiometer clockwise until the voltage level begins to drop.
- Readjust the engine speed to 1800 rpm for 60 Hz models or 1500 rpm for 50 Hz models.
- Readjust the voltage adjustment control until the desired output is achieved.
- Readjust the stability potentiometer until light flicker minimizes.
- Move the generator set master switch to the OFF/RESET position.
Tools required
Tool links are Amazon searches (affiliate links); manufacturer special tools may only be available from a dealer.
Specs & values
- Factory setting is 57.5--58 Hz for 60 Hz models and 47.5--48 Hz for 50 Hz models
- Readjust engine speed to 1800 rpm for 60 Hz or 1500 rpm for 50 Hz
Full service-parts list: Kohler 10REOZD →, Kohler 15REOZD →, Kohler 20REOZD →
Source: Kohler service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.