Kohler — Prepare the Site, Outdoor Installations, Enclosed Units
Installation · generator set site
From a Kohler service manual covering: 10REOZD, 15REOZD, 20REOZD. Check it applies to your exact model before use.
Applies to: Kohler 10REOZD, Kohler 15REOZD, Kohler 20REOZD
Procedure
- Obtain a building permit and contact local utility companies to mark underground pipes and cables.
- Clear combustible materials from an area at least 2.4 m (8 ft.) beyond the exhaust end.
- Spread a 76-mm (3-in.) thick layer of gravel to support the concrete mounting pad.
- Lay a concrete pad that extends at least 152 mm (6 in.) beyond the generator set on all sides.
- Include mounting bolts at locations shown on the dimension drawing.
Specs & values
- Location at least 0.9 m (3 ft.) from any building or structure
- Minimum 2.4 m (8 ft.) clearance beyond the exhaust end