PowerCommand Controller

The PowerCommand is a generator-set controller. It is used on generator sets from Cummins/Onan and MQ Power, including the 1250DFLE, 1500DFLE, 1800 DQKC and 2000 DQKC.

266
Generator sets
2
Brands
3–2750 kW
Power range
3
Fuel types

Generator sets using this controller

266

Used across brands: Cummins/Onan, MQ Power

Cummins/Onan 1250DFLECummins/Onan 1500DFLECummins/Onan 1800 DQKCCummins/Onan 2000 DQKCCummins/Onan 3.0 GCAACummins/Onan 6CTA8.3 series engineCummins/Onan 713DFHBCummins/Onan 750DFGECummins/Onan 800DFHDCummins/Onan BTPCCummins/Onan C100 D5Cummins/Onan C1000 D5Cummins/Onan C1000 D6Cummins/Onan C1000D5BCummins/Onan C1000D6Cummins/Onan C1000N6Cummins/Onan C100D6RTCummins/Onan C110 D5Cummins/Onan C1100 D5Cummins/Onan C1100 D5BCummins/Onan C1250 D5ACummins/Onan C1250 D6Cummins/Onan C1300N6Cummins/Onan C135 D6Cummins/Onan C1400 D5Cummins/Onan C150 D5Cummins/Onan C1500 D6Cummins/Onan C1500D6Cummins/Onan C1500D6RGCummins/Onan C150D6RCummins/Onan C1600D6RGCummins/Onan C1675 D5Cummins/Onan C175 D6Cummins/Onan C1760 D5eCummins/Onan C180 D6Cummins/Onan C200Cummins/Onan C200 D5Cummins/Onan C200 D6Cummins/Onan C2000 D5Cummins/Onan C2000 D6Cummins/Onan C2000D2RCummins/Onan C2000D6RGCummins/Onan C200N6Cummins/Onan C220 D5Cummins/Onan C225 D6Cummins/Onan C2250 D5Cummins/Onan C2250 D6ACummins/Onan C230D6RTCummins/Onan C250 D5Cummins/Onan C2500 D5ACummins/Onan C2750 D5Cummins/Onan C275N6CCummins/Onan C3000 D5Cummins/Onan C300D6Cummins/Onan C350 D5Cummins/Onan C350 D6Cummins/Onan C380 D5Cummins/Onan C400 D5Cummins/Onan C400 D6Cummins/Onan C400N5CCummins/Onan C440 D5Cummins/Onan C450 D5eCummins/Onan C450 D6eCummins/Onan C450D5Cummins/Onan C450D6Cummins/Onan C500 D5eCummins/Onan C500 D6eCummins/Onan C500D5Cummins/Onan C500D6Cummins/Onan C55 D5Cummins/Onan C550 D5Cummins/Onan C55N6CCummins/Onan C580N6Cummins/Onan C600 D6Cummins/Onan C60D6Cummins/Onan C635N6Cummins/Onan C640 D5Cummins/Onan C690N6Cummins/Onan C700 D5Cummins/Onan C750 D6Cummins/Onan C80 D5Cummins/Onan C800 D6Cummins/Onan C800D6RGCummins/Onan C80D6RCummins/Onan C825 D5Cummins/Onan C90 D5Cummins/Onan C900 D5Cummins/Onan C900 D6Cummins/Onan C900D6Cummins/Onan DFCCCummins/Onan DFECummins/Onan DFHACummins/Onan DFHBCummins/Onan DFHDCummins/Onan DFJDCummins/Onan DFLCCummins/Onan DFLECummins/Onan DFMCummins/Onan DGBBCummins/Onan DGBCCummins/Onan DGCBCummins/Onan DGCGCummins/Onan DGDACummins/Onan DGDBCummins/Onan DGDKCummins/Onan DGFACummins/Onan DGFCCummins/Onan DGFSCummins/Onan DNACCummins/Onan DNADCummins/Onan DNAECummins/Onan DNAFCummins/Onan DQABCummins/Onan DQAFCummins/Onan DQBBCummins/Onan DQCACummins/Onan DQCBCummins/Onan DQCCCummins/Onan DQFAACummins/Onan DQFABCummins/Onan DQFACCummins/Onan DQFADCummins/Onan DQHABCummins/Onan DQKAACummins/Onan DQKABCummins/Onan DQKBCummins/Onan DQKCCummins/Onan DQKDCummins/Onan DQKHCummins/Onan DQPAACummins/Onan DQPABCummins/Onan G8.3GCCummins/Onan GFABCummins/Onan GFBACummins/Onan GFBBCummins/Onan GFEBCummins/Onan GFJACummins/Onan GFJBCummins/Onan GFJCCummins/Onan GFLACummins/Onan GFLCCummins/Onan GTA855Cummins/Onan GTA855ECummins/Onan K38 Series C1010 D5 PCCummins/Onan NTA855Cummins/Onan Not explicitly stated in the documentCummins/Onan PCC 1302Cummins/Onan QSB7G5Cummins/Onan QSK78 seriesCummins/Onan QSL9-G5Cummins/Onan QSX15 seriesCummins/Onan RS100Cummins/Onan RS36Cummins/Onan RS50Cummins/Onan RS60Cummins/Onan S-1383eMQ Power CG500C2MQ Power CG800C2

Also fitted to: Cummins/Onan 250 MOH (KTA 19GC), Cummins/Onan C2000N6C, QSV91G single turbo, Cummins/Onan PowerCommand PCC 1302, Cummins/Onan PowerCommand PCC 2300, Cummins/Onan TA Luft – EU Stage.

Troubleshooting

60

Fault codes

CodeMeaningRemedy
101Engine continues to operate at reduced RPM.
101IDLE MODE
102EMERGENCY STOPTo reset the local/remote Emergency Stop button: Pull the button out. Move the Run/Off/Auto switch to Off. Press the Reset switch. Select Run or Auto, as required.
102Engine shuts down and will not crank.Indicates local or remote Emergency Stop. To reset the local Emergency Stop button : Pull the button out or turn the switch clockwise (button with arrow) and allow it to pop out. Move the Run/Off/Auto switch to Off. Press the Reset switch. Select Run or Auto, as required.
1123A shutdown occurs immediately after moving the customer installed Battle Short switch to OFF with an active but overridden shutdown fault or a shutdown fault that was overridden at any time.
1123Shutdown After Battle Short
1124Delayed Shutdown
1131Battle Short Active
1131Battle Short mode is enabled.
121Speed Signal Lost
121Speed Signal Lost fault.
1244Engine Normal Shutdown
1245CAN - Engine Shutdown
1246CAN - Unknown Engine Fault
1247CAN - Engine Unannounced Fault
1248CAN - Engine Warning Fault
1311Customer Inputs #1
1311 through 1318Customer Defined Fault
1312Customer Inputs #2
1317Customer Inputs #3
1318Customer Inputs #4
1334Crit Scaler OR
1335Non-Crit Scaler OR
135Oil Pressure Sensor High
141Oil Pressure Sensor Low
1416An overridden shutdown fault occurs, but the genset does not shut down.
1416FAIL TO SHUTDOWNStatus ï indicates that the “Fault Bypass” mode is enabled. This mode is primarily used by service personnel for troubleshooting purposes.
1416Fail To Shut Down
1416Fail to Shutdown
1417POWER DOWN ERRORPossible drain on battery. Contact an authorized service center for service.
1417Power Down Failure
143Pre-Low Oil Pressure Sensor
1433Emergency Stop
1433Emergency Stop fault.
1433 / 1434EMERGENCY STOP ï LOCAL / EMERGENCY STOP ï REMOTETo reset the local/remote Emergency Stop button: Pull the button out. Move the O/Manual/Auto switch to O (off). Press the front panel Fault Acknowledge button. Select Manual or Auto, as required.
1434Remote Emergency Stop
1434Remote Emergency Stop fault.
1435Low Coolant Temperature
1438FAIL TO CRANKA. Poor battery cable connections. Clean the battery cable terminals and tighten all connections. b. Discharged or defective battery. Recharge or replace the battery.
1438Fail to Crank
1439FUEL LEVEL LOW IN DAYCheck fuel supply and replenish as required.
144Coolant Temperature Sensor High
1442Weak Battery
1443Battery Failed
1444KW Overload
1445Short Circuit
1446High AC Voltage
1447Low AC Voltage
1448Under Frequency
1449Over Frequency
145Coolant Temperature Sensor Low
146HIGH COOLANT TEMP WARNINGA. Reduce load if possible by turning off non-critical loads. b. Check air inlets and outlets and remove any obstructions to airflow. If engine can be stopped, follow 151 High Coolant Temp Alarm procedure.
146Pre-High Cool Temp
1461Loss of Field
1466Modem Failure
1468Network Error
1469Speed/Hz Match
1471Over Current
1472Over Current
151HIGH COOLANT TEMP ALARMA. Check jacket water coolant level and replenish if low. Look for coolant leakage and repair if necessary. b. Check for obstructions to cooling airflow and correct as necessary. c. Check fan belt and repair if necessary. d. Reset control and restart after locating and correcting problem.

Fault codes and symptom→remedy steps extracted from this controller’s service/owner documentation; verify against the official manual before servicing. Aggregated from the service documentation of generator sets built on this controller.