PowerCommand Controller

The PowerCommand is a generator-set controller. It is used on generator sets from Cummins/Onan and MQ Power, including the 1250DFLE, 1500DFLE, 1750 and 1800 DQKC.

270
Generator sets
2
Brands
3–3000 kW
Power range
4
Fuel types

Generator sets using this controller

270

Used across brands: Cummins/Onan, MQ Power

Cummins/Onan 1250DFLECummins/Onan 1500DFLECummins/Onan 1750Cummins/Onan 1800 DQKCCummins/Onan 2000Cummins/Onan 2000 DQKCCummins/Onan 2250Cummins/Onan 2500Cummins/Onan 3.0 GCAACummins/Onan 6CTA8.3 series engineCummins/Onan 713DFHBCummins/Onan 750DFGECummins/Onan 800DFHDCummins/Onan C100 D5Cummins/Onan C1000 D5Cummins/Onan C1000 D6Cummins/Onan C1000D5BCummins/Onan C1000D6BCummins/Onan C1000N6Cummins/Onan C110 D5Cummins/Onan C1100 D5Cummins/Onan C1100 D5BCummins/Onan C110D6Cummins/Onan C110D6BCummins/Onan C120D5Cummins/Onan C1250 D6Cummins/Onan C1300N6Cummins/Onan C135 D6Cummins/Onan C1400 D5Cummins/Onan C145D6Cummins/Onan C150 D5Cummins/Onan C1500 D6Cummins/Onan C1500 D6RGCummins/Onan C1500D6RCummins/Onan C150D6RCummins/Onan C1600D6RGCummins/Onan C1675 D5Cummins/Onan C170 D6Cummins/Onan C175 D6Cummins/Onan C180 D5Cummins/Onan C180 D6Cummins/Onan C185 D6Cummins/Onan C200 D5Cummins/Onan C200 D6Cummins/Onan C2000 D6Cummins/Onan C2000D2RCummins/Onan C2000D6RGCummins/Onan C200D6RCummins/Onan C200N6Cummins/Onan C220 D5Cummins/Onan C225 D6Cummins/Onan C2250 D6ACummins/Onan C250 D5Cummins/Onan C2750 D5Cummins/Onan C3000 D5Cummins/Onan C350 D5Cummins/Onan C350 D6Cummins/Onan C3500 D5Cummins/Onan C3750 D5Cummins/Onan C380 D5Cummins/Onan C400 D5Cummins/Onan C400 D5eCummins/Onan C400 D6Cummins/Onan C400D6FCummins/Onan C400N5CCummins/Onan C440 D5Cummins/Onan C450 D5eCummins/Onan C450 D6eCummins/Onan C450D5Cummins/Onan C500 D5eCummins/Onan C500 D6eCummins/Onan C500D6RCummins/Onan C55 D5Cummins/Onan C550 D5Cummins/Onan C55N6CCummins/Onan C580N6Cummins/Onan C600 D6Cummins/Onan C635N6Cummins/Onan C640 D5Cummins/Onan C690N6Cummins/Onan C700 D5Cummins/Onan C750 D6Cummins/Onan C80 D5Cummins/Onan C800 D6Cummins/Onan C800D6RGCummins/Onan C80D6RCummins/Onan C825 D5Cummins/Onan C90 D5Cummins/Onan C900 D5Cummins/Onan C900 D6Cummins/Onan C900D6BCummins/Onan C90D6BCummins/Onan DFABCummins/Onan DFACCummins/Onan DFBFCummins/Onan DFCBCummins/Onan DFCCCummins/Onan DFCECummins/Onan DFECummins/Onan DFGBCummins/Onan DFGE 60 HzCummins/Onan DFHACummins/Onan DFHBCummins/Onan DFHDCummins/Onan DFHD 60 HzCummins/Onan DFJDCummins/Onan DFLCCummins/Onan DFLECummins/Onan DFMCummins/Onan DGBBCummins/Onan DGBCCummins/Onan DGCBCummins/Onan DGCGCummins/Onan DGDACummins/Onan DGDBCummins/Onan DGDKCummins/Onan DGFACummins/Onan DGFA 60 HzCummins/Onan DGFCCummins/Onan DGFSCummins/Onan DNACCummins/Onan DNADCummins/Onan DNAECummins/Onan DNAFCummins/Onan DQABCummins/Onan DQAECummins/Onan DQAFCummins/Onan DQBBCummins/Onan DQCACummins/Onan DQCBCummins/Onan DQCCCummins/Onan DQDAACummins/Onan DQFAACummins/Onan DQFABCummins/Onan DQFACCummins/Onan DQFADCummins/Onan DQHABCummins/Onan DQKAACummins/Onan DQKABCummins/Onan DQPAACummins/Onan DQPABCummins/Onan DSHAA 60 HzCummins/Onan DSHACCummins/Onan GFABCummins/Onan GFBACummins/Onan GFBBCummins/Onan GFBCCummins/Onan GFEACummins/Onan GFEBCummins/Onan GFJACummins/Onan GFJBCummins/Onan GFJCCummins/Onan GFLACummins/Onan GFLCCummins/Onan GFPACummins/Onan GTA855Cummins/Onan GTA855ECummins/Onan K38 Series C1010 D5 PCCummins/Onan PCC 1302Cummins/Onan QSB7Cummins/Onan QSK78 seriesCummins/Onan QSL9-G5Cummins/Onan QSX15Cummins/Onan QSX15 seriesCummins/Onan RS 36Cummins/Onan RS100Cummins/Onan RS50Cummins/Onan RS60Cummins/Onan S3.8 seriesMQ Power CG500C2MQ Power CG800C2

Also fitted to: Cummins/Onan 1760 (1408), Cummins/Onan 2063 (1650), Cummins/Onan 250 MOH (KTA 19GC), Cummins/Onan C2000N6C, QSV91G single turbo, Cummins/Onan MODEL, Cummins/Onan Model:, Cummins/Onan Not explicitly stated in the document, Cummins/Onan PowerCommand PCC 1302, Cummins/Onan PowerCommand PCC 2300, Cummins/Onan TA Luft – EU Stage.

Troubleshooting

60

Fault codes

CodeMeaningCauseRemedy
1Green RUN lamp lights following engine startup.Indicates all engine systems are normal.No corrective action required.
1One blink indicates shutdown due to high engine coolant temperatureCoolant temperature over 230° F (110° C); the coolant thermostat switch closes at this temperature and actuates the fault circuitObserve Coolant Temperature Gauge (option) for indication of temperature over 230° F (110° C); check coolant level in radiator after allowing engine to cool down; see that the pump belt is OK and has proper tension; check cooling system cleanliness (freedom from contaminants, rust, sludge buildup, etc.)
10LO FUEL LAMP lights. Engine shuts down and LO OIL PRES lamp lights.Indicates engine has run out of fuel.Check fuel level and replenish as required.
101IDLE MODE
101IDLE MODE — Engine continues to operate at reduced RPMIndicates that the engine is operating in idle mode. When the set is operating in the RUN mode, grounding the engine idle input causes generator build-up to be inhibited and the engine to be governed at 800 RPM.When ground is removed from this input, the set returns to normal speed and voltage. When the engine idle function is enabled, the control automatically sets lower oil pressure warning and shutdown trip points to reflect the lower operating speed. When the engine idle function is removed and the set reverts to normal operating speed, the control automatically resets oil pressure warning and shutdown trip points to the normal settings.
101IDLE MODE — Engine continues to operate at reduced RPM.Indicates that the engine is operating in idle mode. When the set is operating in the RUN mode, grounding the engine idle input causes generator build-up to be inhibited and the engine to be governed at 800 RPM.When ground is removed from this input, the set returns to normal speed and voltage. When the engine idle function is enabled, the control automatically sets lower oil pressure warning and shutdown trip points to reflect the lower operating speed. When the engine idle function is removed and the set reverts to normal operating speed, the control automatically resets oil pressure warning and shutdown trip points to the normal settings.
101IDLE MODE — WARNING; Engine continues to operate at reduced RPM.Indicates that the engine is operating in idle mode. When the set is operating in the RUN mode, grounding the engine idle input causes generator build-up to be inhibited and the engine to be governed at 800 RPM.When ground is removed from this input, the set returns to normal speed and voltage. When the engine idle function is enabled, the control automatically sets lower oil pressure warning and shutdown trip points to reflect the lower operating speed. When the engine idle function is removed and the set reverts to normal operating speed, the control automatically resets oil pressure warning and shutdown trip points to the normal settings.
101IDLE MODE — Warning lamp lights
101IDLE MODE — Warning; Engine continues to operate at reduced RPM.Indicates that the engine is operating in idle mode. When the set is operating in the RUN mode, grounding the engine idle input causes generator build-up to be inhibited and the engine to be governed at 800 RPM.When ground is removed from this input, the set returns to normal speed and voltage. When the engine idle function is enabled, the control automatically sets lower oil pressure warning and shutdown trip points to reflect the lower operating speed. When the engine idle function is removed and the set reverts to normal operating speed, the control automatically resets oil pressure warning and shutdown trip points to the normal settings.
102EMERGENCY STOPTo reset the local/remote Emergency Stop button: Pull the button out. Move the Run/Off/Auto switch to Off. Press the Reset switch. Select Run or Auto, as required.
102EMERGENCY STOP — Engine shuts down and will not crankIndicates local or remote Emergency Stop.To reset the local Emergency Stop button: Pull the button out; Move the Run/Off/Auto switch to Off; Press the Reset switch; Select Run or Auto, as required.
102EMERGENCY STOP — Engine shuts down and will not crank.Indicates local or remote Emergency Stop.To reset the local Emergency Stop button: Pull the button out or turn the switch clockwise (button with arrow) and allow it to pop out. Move the Run/Off/Auto switch to Off. Press the Reset switch. Select Run or Auto, as required.
102EMERGENCY STOP — SHUTDOWN; Engine shuts down and will not crank.Indicates local or remote Emergency Stop.To reset the local Emergency Stop button: Pull the button out or turn the switch clockwise (button with arrow) and allow it to pop out; Move the Run/Off/Auto switch to Off; Press the Reset switch; Select Run or Auto, as required.
102EMERGENCY STOP — Shutdown lamp lights
102EMERGENCY STOP — Shutdown; Engine shuts down and will not crank.Indicates local or remote Emergency Stop.To reset the local Emergency Stop button: Pull the button out or turn the switch clockwise (button with arrow) and allow it to pop out; Move the Run/Off/Auto switch to Off; Press the Reset switch; Select Run or Auto, as required.
11LO ENG TEMP lamp lights. Set is in standby mode but is not operating. (Lamp lights when engine coolant temperature is 70° F (21° C) or lower. Since the lamp goes out after the engine warms up, there should be no cause for alarm even during initial generator set operation.)Indicates engine coolant heater is not operating, not circulating coolant or ambient temperature too cold for heater to keep up with demand.Check for the following conditions: a. Coolant heater not connected to power supply. Check for blown fuse or disconnected heater cord and correct as required. b. Check for low coolant level and replenish if required. Look for possible coolant leakage points and repair as required. c. Contact an authorized service center if none of the above.
111Internal ECM Failure
111Internal ECM error
1117ECM POWER LOST — Lamp: Warning. Indicates that “Keyswitch” to the ECM was NOT removed for 30 seconds before removing battery power to the ECM (removing connectors or battery cable).To reset, place the O/Manual/Auto switch in the O position and press E-Stop and wait 30 seconds. Remove E-Stop and press the Fault Reset button.
1117ECM power lost
1117Power Lost With Ignition On
1118Prelube relay driver
112Actuator not responding
1121Fail To Disconnect
1121Failed to Disconnect
1122Rated To Idle Delay
1122Rated/Idle Trans
1123A shutdown occurs immediately after moving the customer installed Battle Short switch to OFF with an active but overridden shutdown fault or a shutdown fault that was overridden at any time.
1123Shutdown After BS
1123Shutdown After Battle Short
1123Shutdown After Battle Short — Battle Short is suspended and a shutdown occurs immediately if moving the customer installed Battle Short switch to OFF with an active but overridden shutdown fault or a shutdown fault that was overridden at any time.
1123Shutdown After Battle Short — ShutdownMoving the customer installed Battle Short switch to OFF with an active but overridden shutdown fault or a shutdown fault that was overridden at any time
1124DELAYED SHUTDOWN — Lamp: Warning. A shutdown fault became active while the Delayed Shutdown feature was enabled. The shutdown will be delayed by the delayed shutdown time entered.Review Fault History and perform corrective action.
1124Delayed Shutdown
1124Delayed Shutdown — Warning
1124Delayed Shutdown — Wrng
1124Delayed shutdown
1128Mixer Inlet Humidity Sensor: Volt Above Normal
1129Mixer Inlet Humidity Sensor: Volt Below Normal
113Actuator sensor fault
1131Battle Sh Active
1131Battle Sh Active — Warning
1131Battle Sh Active — Warning status indicator is lit.Battle Short mode is enabled.
1131Battle Sh Active — When Battle Short mode is enabled, the Warning status indicator is lit, along with displayed fault code 1131.
1131Battle Short Active
1131Battle Short Active — WarningThe control is in Battle Short mode (used to bypass several fault shutdowns therefore allowing generator set operation during emergencies)If possible, investigate any fault codes that are being bypassed
1131Battle Short mode is enabled.
1132Controlled Shutdown
1139UFD Injector 1 Error
1141UFD Injector 2 Error
1142UFD Injector 3 Error
1143UFD Injector 4 Error
1144UFD Injector 5 Error
1145UFD Injector 6 Error
115Eng Crank Sensor Error
115No speed signal
115Speed Signal Lost — Shtdn
115Speed signal lost
116Time press sensor high
117Time press sensor low

Fault codes and symptom→remedy steps extracted from this controller’s service/owner documentation; verify against the official manual before servicing. Aggregated from the service documentation of generator sets built on this controller.