Home›Cummins/Onan›Cummins/Onan DQKAB

Cummins/Onan DQKAB Generator Set

The Cummins/Onan DQKAB is a 2000 kW (2500 kVA) Diesel standby generator set powered by a Cummins/Onan QSK60 engine. It is available at 219/380 V, 254/440 V, 277/480 V, 347/600 V, 2400/4160 V, 7200/1247 V, 7620/1320 V and 7970/1380 V, 3-phase, 60 Hz and rated N/A A. It holds about 334 L (88.2 gal) of oil and 492 L (130.0 gal) of coolant, with a maximum ambient rating of 40 °C. Starting uses N/A group-N/A battery rated 2200 CCA at 24 V. The set measures 6175×2534×3043 mm (243.1×99.8×119.8 in), weighs about 17382 kg (38321 lb) and produces 99.7 dBA at 7 m. An integrated tank holds N/A L (None gal), roughly N/A hours of runtime. The same QSK60 engine also powers generator sets from AKSA.

2000 kW
Standby
60.2 L
Displacement
334.0 L
Oil capacity
3
Document types

How to read your Cummins/Onan serial & model number →

Typical fuel consumption for 2000–2005 kW Diesel generators →

Compare with other 2000–2005 kW Diesel generators →

Service parts for the DQKAB

Grouped by system, with how many of each the parts manual calls for.

Fuel system

1 required
A055Y798Fuel filter (primary)$5944.00eBay

Oil system

1 required
F60-1500Oil filtersee priceAmazon

Belts

1 required
B60-1500Beltsee priceAmazon

Ignition

1 required
S60-1500Spark plugsee priceAmazon

Prices captured from merchant listings; some links are affiliate links. Confirm against your serial number before ordering.

Specifications

FuelDiesel
Frequency60.0 Hz
Standby power2000 kW
Standby kVA2500
Prime power1825 kW
EmissionsEPA Tier 2
ControllerEDS-1065, HMI320, PowerCommand, PowerCommand 3.3, PowerCommand 3.3 (PCC3300, PowerCommand 3201, PowerCommand PCC 3201
Oil capacity334.0 L
AlternatorN/A (2-pole)
Voltage options219/380 V, 254/440 V, 277/480 V, 347/600 V, 2400/4160 V, 7200/1247 V, 7620/1320 V, 7970/1380 V
Phase3
Rated currentN/A A
Power factor0.8
Circuit breakerN/A A
Battery groupN/A
Battery cranking2200 CCA
Battery voltage24 V
Battery quantityN/A
Coolant capacity492 L
Max ambient40 °C
Dimensions (L×W×H)6175×2534×3043 mm
Dry weight17382 kg
Wet weight17908 kg
Sound level44.1 dBA @ 7 m
Fuel tank14628.0 L
Tank runtimeN/A hr

Engine

Cummins/Onan QSK60
Oil capacity100.0 L
Coolant capacity42.0 L
Displacement60.2 L
Aspirationturbocharged
Rated speed1800 rpm

Filters for the Cummins/Onan QSK60

3

Engine-mounted filters the filter manufacturers list for this engine family. These come from the engine, not from this generator set’s own parts list, so confirm against your serial number before ordering.

SystemFilterDescriptionCross-references
Fuel / water separatorP552006Fuel Filter, Water Separator Spin-On Twist&DrainCUMMINS 3089916, CUMMINS 4095189, NAPA 3645, BALDWIN BF1262 FridayParts $42.88

Listed for this engine in only one kind of machine, so they may depend on how the engine was installed:

SystemFilterDescriptionCross-references
Oil filterP550596Lube Filter, Spin-On Full FlowBALDWIN B7217, WALGAHN-MOTORENTECHN 00811323, M.D.F. SARL 025366, HITACHI 113240232 KuduParts $48.00 FridayParts $49.99
Coolant filterP552071Coolant Filter, Spin-On Sca PlusCUMMINS 299080, CUMMINS 299880, NAPA 4071, TORO 012706560 FridayParts $37.53

Same engine, other brands

1 brand

The Cummins/Onan QSK60 in this set also powers 1 generator set sold under 1 other brand. Service parts and maintenance intervals for the engine are shared; enclosure, alternator, controller and ratings are not.

BrandModels
AKSAAC2060

Maintenance & consumables

for the Cummins/Onan QSK60
ItemSpecCapacityPart #Interval
Air filterDry replaceable element—1000 hr
Fuel filterTwo-stage spin-on fuel filters and water separator system. Stage 1 has a three element, 7-micron filter and Stage 2 has a three element, 3-micron filter.A055Y798 Amazon eBay $5944.00
Oil filterCummins OE filterF60-1500240 hr Amazon eBay
Battery—480 hr
BeltCummins OE beltB60-15003360 hr Amazon eBay
Coolant4000.0 L—7304 hr
Coolant filternot specified—1000 hr
Oil334.0 L—1000 hr
Spark plugCummins OE spark plugS60-1500240 hr Amazon eBay

Service specifications

47
TypeItemValueUnitCondition
OtherAC waveform THD (THDV)< 5%no load to full linear load
OtherAC waveform total harmonic distortion< 5% no load to full linear load, < 3% for any single harmonic
OtherBMEP at set rated load (prime)1885kPaprime rating
OtherBMEP at set rated load (standby)2109kPastandby rating
OtherBreaker fail to synchronize default time delay120sadjustable 10–900 s
OtherDerate above 1402 m (4600 ft) / 40 °C4.5% per 305 m (1000 ft) and 11.0% per 10 °C (18 °F)standby and prime
OtherFrequency regulationIsochronous
OtherGovernor regulation classISO8528 Part 1 Class G3
OtherHigh AC voltage shutdown default110%% of nominal voltagefor 10 s; adjustable 105–125%, 0.1–10 s
OtherInstantaneous pickup (Ii) range (Micrologic 3.0 and 5.0)1.5–12 x Inx In
OtherLong-time delay tr0.5–24sat 6 x Ir
OtherLong-time pickup (Ir) adjustment range0.4–1.0 x Inx Insensor plug rating In
OtherLow AC voltage shutdown default85%% of reference voltagefor 10 s; adjustable 50–95%, 2–20 s
OtherOver frequency shutdown/warning default6Hz above nominalfor 20 s, disabled; adjustable 2–10 Hz above set point, 1–20 s
OtherOver load (kW) warning default105%% of rated kWadjustment range 80–140%, 0–120 s delay; default 60 s
OtherPiston speed11.4m/s
OtherRandom frequency variation± 0.25%
OtherReverse Var shutdown default20%% of rated Varfor 10 s; adjustable 15–50%, 10–60 s
OtherReverse power shutdown default10%% of standby kWfor 3 s; adjustable 5–20%, 1–15 s
OtherShort circuit protection threshold175%% of ratingoutput current on any phase
OtherTelephone Harmonic Factor (THF)< 3
OtherTelephone Influence Factor (TIF)< 50per NEMA MG1-22.43
OtherUnder frequency shutdown default6Hz below referencefor 10 s; adjustable 2–10 Hz below set point, 5–20 s
OtherWire stripping length1.38 In (35 mm)in
PressureBMEP at set rated load2413 (350)kPa (psi)standby rating
PressureMaximum air cleaner restriction6.2kPa
PressureMaximum back pressure6.8kPaexhaust
PressureMaximum back pressure6.8 (27)kPa (in H2O)
PressureMaximum cooling air flow static restriction0.12kPa
PressureMaximum fuel inlet restriction16.9 (5)kPa (in Hg)
PressureMaximum fuel inlet restriction30kPa
PressureMaximum fuel return line restriction34kPa
PressureMaximum fuel return line restriction34 (10)kPa (in Hg)
SpeedOverspeed limit2100 ±50rpm
SpeedRated speed1800rpm60 Hz
TemperatureAmbient design (standard set-mounted radiator)50°C
TemperatureExhaust temperature at set rated load (prime)463°Cprime
TemperatureExhaust temperature at set rated load (standby)469°Cstandby
TemperatureMaximum aftercooler inlet temp49°C
TemperatureMaximum aftercooler inlet temp66 (150)°C (°F)
TemperatureMaximum fuel inlet temperature71°C
TemperatureMaximum jacket water outlet temp104 (220)°C (°F)optional remote radiator cooling
TemperatureMaximum jacket water outlet temp (remote radiator)104°Cstandby
TorqueCircuit breaker terminal tightening torque (AWG 1/0...750 kcmil)548.75 Lbf.In (62 N.m)Lbf.In0.08…0.62 in² (50…400 mm²)
VoltageRandom voltage variation± 0.5%
VoltageStandard temperature rise150°CStandby at 40 °C ambient
VoltageVoltage regulation, no load to full load± 0.5%

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Recommended fluids

FluidGradeStandardAmbientCapacityNotes
FuelASTM D975 No. 2-DASTM D975Cetane number: 40-50. 300-500 ppm Sulfur. Fuel inlet temperature 40°C (104°F) reference.
FuelASTM D975 No. 2-D, 300-500 ppm SulfurASTM D975Cetane number: 40-50. Reference conditions: air inlet temperature 25 °C (77 °F), fuel inlet temperature 40 °C (104 °F)

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Fault codes

10
CodeNameMeaningSeverityAction
27Low AC voltage shutdownVoltage on any phase has dropped below a preset value.ShutdownAdjustable 50-95% of reference voltage, time delay 2-20 seconds; default 85% for 10 seconds.
32Reverse power shutdownReverse power detected.ShutdownAdjustment range 5-20% of standby kW rating, delay 1-15 seconds; default 10%, 3 seconds.
40Reverse Var shutdownReverse reactive power detected.ShutdownAdjustable 15-50% of rated Var output, delay 10-60 seconds; default 20%, 10 seconds.
46Negative sequence overcurrent warningExcessive imbalances in the three phase load currents and/or power factors.WarningControl protects generator from damage due to phase imbalance.
51Overcurrent warning/shutdownImplementation of the thermal damage curve with instantaneous trip level based on CT ratio and application power rating.ShutdownAmpSentry protective relay action; see document R1053 time over current curve.
51GGround fault overcurrentDetects a ground fault via external ground fault relay contact input or measured ground current from external CT.ShutdownTime delays and thresholds adjustable via InPower or HMI.
59High AC voltage shutdownOutput voltage on any phase exceeds preset values; trip time inversely proportional to amount above threshold.ShutdownAdjustable 105-125% of nominal voltage, time delay 0.1-10 seconds; default 110% for 10 seconds.
81 uUnder Frequency ShutdownGenset output frequency cannot be maintained. Adjustable 2-10 Hz below reference governor set point, time delay 5-20 s. Default 6 Hz, 10 s.Shutdown
81oOver frequency shutdown/warningGenset is operating at a potentially damaging frequency level.WarningAdjustable 2-10 Hz above nominal governor set point, 1-20 second delay; default 6 Hz, 20 seconds, disabled.
81uUnder frequency shutdownGenset output frequency cannot be maintained.ShutdownAdjustable 2-10 Hz below reference governor set point, 5-20 second delay; default 6 Hz, 10 seconds.

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Procedures

3
Trip Unit Operation Verification diagnostic

Tools: Trip unit test kit

  1. Connect a test kit to the trip unit test plug receptacle.
  2. Perform verification tests per instructions shipped with the test kit to verify trip unit functions.
Battery replacement / battery rack installation maintenance
  1. Isolate DC supply before working on battery connections.
  2. Install battery rack with hold-down, floor standing.
  3. Install battery with minimum 2200 amps capacity at -18 °C to 0 °C.
  4. Verify 24 volt negative ground connection.
Trip Unit Switch Adjustment operation

⚠ Wait a minimum of 15 minutes after circuit breaker trips before resetting to allow thermal imaging to reset completely to zero.

Tools: Wire seal MICROTUSEAL

  1. Open switch cover.
  2. Adjust the appropriate switches to desired values.
  3. Replace switch cover.
  4. Use wire seal MICROTUSEAL, if necessary, to provide tamper evidence.

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Voltage reconnection

VoltagePhaseConnectionLeadsNotes
124703-phaseWye, 3-phaseWinding No. 87; Feature Code B567; ADS-521; Temp rise 105/80 C; Duty S/P; Max surge kVA 6038
12470-138003Wye, 3-phaseWinding no. 6062Temp rise 125/105/80 °C; ADS-521; feature code B448; max surge kVA 91
12470-138003-phaseWye, 3-phaseWinding No. 91; Feature Code B448; ADS-521; Temp rise 125/105/80 C; Duty S/P/C; Max surge kVA 6062
13200-138003-phaseWye, 3-phaseWinding No. 91; Feature Code B612; ADS-521; Temp rise 105/80 C; Duty S/P; Max surge kVA 6062
138003-phaseWye, 3-phaseWinding No. 91; Feature Code B610; ADS-521; Temp rise 80 C; Duty S; Max surge kVA 6833
220/38036 leads6Winding no. 13; 125°C rise rating 2004 kW / 2505 kVA; stator resistance L-L 0.00102 Ohms; rotor resistance 2.31 Ohms @22°C
240/41636 leads6Winding no. 13; 125°C rise rating 2004 kW / 2505 kVA; stator resistance L-L 0.00102 Ohms; rotor resistance 2.31 Ohms @22°C
254/44036 leads6Winding no. 312; 125°C rise rating 2000 kW / 2500 kVA; stator resistance L-L 0.00152 Ohms; rotor resistance 2.31 Ohms @22°C
277/48036 leads6Winding no. 312; 125°C rise rating 2080 kW / 2600 kVA; stator resistance L-L 0.00152 Ohms; rotor resistance 2.31 Ohms @22°C
277/4803Wye, 4 WireFeature code R002-2 Voltage-277/480, 3 Phase, Wye, 4 Wire
346/60036 leads6Winding no. 07; 125°C rise rating 2080 kW / 2600 kVA; stator resistance L-L 0.00220 Ohms; rotor resistance 2.31 Ohms @22°C
3803Wye, 3-phaseWinding no. 7327Temp rise 150/125/105 °C; ADS-335; feature code B595; max surge kVA 312
3803-phaseWye, 3-phaseWinding No. 13; Feature Code B595; ADS-515; Temp rise 150/125/105 C; Duty S/P/C; Max surge kVA 7327
41603Wye, 3-phaseWinding no. 6307Temp rise 125/105/80 °C; ADS-324; feature code B467; max surge kVA 51
41603-phaseWye, 3-phaseWinding No. 51; Feature Code B467; ADS-518; Temp rise 125/105/80 C; Duty S/P/C; Max surge kVA 6307
4403-phaseWye, 3-phaseWinding No. 312; Feature Code B663; ADS-334; Temp rise 125/105/80 C; Duty S/P/C; Max surge kVA 7361
4803Wye, 3-phaseWinding no. 7361Temp rise 125/105/80 °C; ADS-333; feature code B462; max surge kVA 312
4803-phaseWye, 3-phaseWinding No. 312; Feature Code B462; ADS-334; Temp rise 125/105/80 C; Duty S/P/C; Max surge kVA 7361
6003Wye, 3-phaseWinding no. 7361Temp rise 125/105/80 °C; ADS-333; feature code B465; max surge kVA 07
6003-phaseWye, 3-phaseWinding No. 07; Feature Code B465; ADS-334; Temp rise 125/105/80 C; Duty S/P/C; Max surge kVA 7361

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Common questions

What is the power rating of the Cummins/Onan DQKAB?

The Cummins/Onan DQKAB is rated 2000 kW standby (2500.0 kVA).

What engine does the Cummins/Onan DQKAB use?

The Cummins/Onan DQKAB is powered by the Cummins/Onan QSK60 engine.

What fuel does the Cummins/Onan DQKAB use?

The Cummins/Onan DQKAB runs on Diesel.

How much oil does the Cummins/Onan DQKAB take?

The Cummins/Onan QSK60 engine in the Cummins/Onan DQKAB has an oil capacity of 100.0 liters.

What is the coolant capacity of the Cummins/Onan DQKAB?

The Cummins/Onan DQKAB cooling system holds 492 liters (130.0 US gallons) for the radiator system including the engine, per the manufacturer specification sheet.

What is the continuous rating of the Cummins/Onan DQKAB?

The Cummins/Onan DQKAB is rated 1825 kW prime (2281 kVA), against 2000 kW standby.

What is the sound level of the Cummins/Onan DQKAB?

The Cummins/Onan DQKAB is rated at 44.1 dBA at 7 m, per the manufacturer specification sheet.

What is the dry weight of the Cummins/Onan DQKAB?

The Cummins/Onan DQKAB has a dry weight of 17382 kg (38320 lb).

What size fuel tank does the Cummins/Onan DQKAB have?

The Cummins/Onan DQKAB has a 14628 liter (3864 US gallon) fuel tank, giving about N/A hours of runtime.

What voltage does the Cummins/Onan DQKAB produce?

The Cummins/Onan DQKAB is offered in 219/380 V, 254/440 V, 277/480 V, 347/600 V, 2400/4160 V, 7200/1247 V, 3-phase.

What size battery does the Cummins/Onan DQKAB need?

The Cummins/Onan DQKAB uses N/A batteryies, 24 V each, 2200 CCA, group N/A, per the manufacturer specification sheet.

What alternator does the Cummins/Onan DQKAB use?

The Cummins/Onan DQKAB uses a N/A alternator. It has 2 poles.

Which oil filter part number does the Cummins/Onan DQKAB take?

The Cummins/Onan DQKAB uses oil filter part number F60-1500.

What fuel filter does the Cummins/Onan DQKAB use?

The Cummins/Onan DQKAB uses fuel filter part number A055Y798.

Troubleshooting

6

Symptoms & remedies

SymptomRemedy
Battle short modeIf enabled and the battle short switch is active, some shutdown faults will be bypassed. However, emergency stop shutdowns and other critical faults are not bypassed.
DerateThe Derate function reduces output power of the genset in response to a fault condition. In utility parallel mode, it actively reduces power by lowering the base load kW to the derated target kW.
Configurable alarm and status inputsThe control accepts up to four configurable alarm or status inputs. The control is programmable for warning, derate, shutdown, shutdown with cooldown or status indication and for labeling the input.
Emergency stopAnnunciated whenever either emergency stop signal is received from an external switch.
General prime mover protectionLow and high battery voltage warning - Indicates status of the battery charging system (failure) by continuously monitoring battery voltage. Weak battery warning - The control system will test the battery each time the genset is signaled to start and indicate a warning if the battery indicates impending failure. Low coolant level warning – Can be set up to be a warning or shutdown.
General prime mover protection - Low and high battery voltage warningIndicates status of battery charging system (failure) by continuously monitoring battery voltage.

Fault codes and symptom→remedy steps extracted from this model’s service/owner documentation; verify against the official manual before servicing. Full Cummins/Onan DQKAB troubleshooting guide (8 entries) →

Repair guides

2

Step-by-step procedures compiled from the Cummins/Onan service manual for this model.

Parts

90
Part #DescriptionQtySystem
128-0108Insulation, Hose – Bulk (Order By The Foot – 12 Feet Required)-Hose Amazon eBay
130-3684Gasket6Gasket Amazon eBay
130-4546Bracket, Mounting – Coolant Heater2Fluid Amazon eBay
130-4552Cover, Coolant Heater2Fluid Amazon eBay
130-4885Radiator (Includes Jacketwater, Aftercooler, Cap, Overflow Hose and Sight Gauge Sevice Parts) 130–35881Hose Amazon eBay
130-5099Gasket8Gasket Amazon eBay
193-0486Sender, Low Coolant Level1Sensor Amazon eBay
309-0649Thermostat (Includes Connector Socket) (S11)1Thermostat Amazon eBay $144.99
319-3950Gasket, Operator Panel1Gasket Amazon eBay
319-3951Gasket, Switch Panel1Gasket Amazon eBay
323-1445* Seal, Cable (Used With Station 17)2Seal Amazon eBay
323-1708# Seal, Cable (P8)4Seal Amazon eBay
330-0141-04Gasket, Cover1Gasket Amazon eBay
338-3335-01Harness, Wiring – AC – Coolant Heater (From Coolant Heater Bottom To Coolant Heater Control Box) (Includes Conduit Connectors) (30”)1Fluid Amazon eBay
338-3335-09Harness, Wiring – AC – Coolant Heater (From Coolant Heater Bottom To Coolant Heater Control Box) (Includes Conduit Connectors) (108”)1Fluid Amazon eBay
338-3831Harness, Wiring – DC – Engine Heater (From Coolant Heater Control Box To Engine And Main Engine Harness) (Includes Parts Marked *)1Fluid Amazon eBay
338-3832Harness, Wiring – Low Coolant Level Sender (4 Wire, 169”) (Includes Parts Marked *)1Sensor Amazon eBay
4321098765Fault Acknowledge Button1Fault acknowledge button Amazon eBay
502-0656Adapter, Male (1–5/16–12 Tubing to 1” Pipe)2Hose Amazon eBay
502-0827Fitting, Hose – Barbed (1/2” ID Pipe to 3/4” ID Hose)2Hose Amazon eBay
502-0836Fitting, Brass – Hose – Barbed (3/4” Pipe to 3/4” Hose)1Hose Amazon eBay
502-1257Connector, Hose – Barbed (Fits 3/4” ID Hose)2Hose Amazon eBay
503-0189Clamp, Hose1Hose Amazon eBay
503-0249Hose − Bulk (Order by the Foot − 3 Feet Required)1Hose Amazon eBay
503-1136Clamp, Hose16Hose Amazon eBay
503-1418Hose − Bulk (1/4” ID) (Order By The Foot − 18 Feet Required)1Hose Amazon eBay
503-1634-01Hose, Rubber (3/4” ID x 4”)4Hose Amazon eBay
503-1726Hose (5” ID x 6”)1Hose Amazon eBay
503-1727Hose, Radiator (3” ID x 10”)2Hose Amazon eBay
503-1728Hose (3” ID x 5–1/2”)1Hose Amazon eBay
503-1745Hose – Bulk – Front Grease Fitting (Order By The Foot – 2 Feet Required)Hose Amazon eBay
503-1863Hose, Radiator (1–1/2” ID x 4”)6Hose Amazon eBay
503-1872-05Clamp, Hose2Hose Amazon eBay
503-1872-09Clamp, Hose (5” ID)2Hose Amazon eBay
503-2129-05Line, Vent – Flexible – With One Male Pipe Swivel and One Female Pipe Swivel With O–Ring Face Seal (1/4” ID x 94–1/2”) Right Side1Seal Amazon eBay
505-1429Nipple, Pipe – Combination (1–1/2” Pipe to 1–1/2” Hose)2Hose Amazon eBay
509-0283-01Seal1Seal Amazon eBay
511-0161-17Belt, V Ribbed1Belt Amazon eBay
518-0548-24Clamp, Hose2Hose Amazon eBay
518-0548-25Clamp, Hose (3/8” ID)2Hose Amazon eBay
A054B161Schematic DiagramSchematic diagram Amazon eBay
AM47478880Temperature Sender, Exhaust Temperature Replaces 47367178, 87482353, LB52S00001P1Sensor Amazon eBay
AM47520140Sensor, 8-Pin/NH3/Ammonia Replaces 47368956, 84382712Sensor Amazon eBay
AM47520143Sensor, Def/AdBlue Quality Replaces 84553250Sensor Amazon eBay
AM504372225Sensor, MAP Temperature/Pressure Replaces 2852821, 4896794, 504073323Sensor Amazon eBay
FS1006Filter, Fuel Water Separator2Fuel filter Amazon eBay $29.99 NAPA $90.16
LF9050Lube, Combination4Oil filter Amazon eBay $49.99
M-3331970Spacer Gasket for QSK45 and QSK60 Engine applicationsSpacer gasket Amazon eBay
M-3649982Juntade culata de cilindro - sobredimensionada 0,020" - M-3649982Cylinder head盖板 Amazon eBay
M-4089203Juego Turbo e Interenfriador N. ° de Pieza1Turbocharger Amazon eBay
M-4089233Juego Turbo e Interenfriador N. ° de Pieza1Turbocharger Amazon eBay
MCBQSK0045Turbocharger Installation KitGasket Amazon eBay
MCBQSK0048Water Pump Gasket SetGasket Amazon eBay
MCBQSK0058Water Pump Gasket SetGasket Amazon eBay
QSK60Gas engineEngine Amazon eBay FridayParts $8.65 SinoCMP $119.00
QSK60-G9Engine model for C2500 D5A generator setsEngine Amazon eBay $129895.00
0130-5997-05Cummins Part No. 312/212, 37564; Cummins Part No. 312/212, 37604; Cummins Part No. 212, 37558; Cummins Part No. 212, 37614; Cummins Part No. 212, 37627; Cummins Part No. 313/312, 0179-2921; Cummins Part No. 313/312, 0179-2988; Cummins Part No. 312, 0179-3291; Cummins Part No. 312/212, 130-5791; Cummins Part No. 312/212, 37644; Cummins Part No. 312/212, 37624; Cummins Part No. 312/212, 37625; Cummins Part No. 212, 37648; Cummins Part No. 212, 37643; Cummins Part No. 212, 37678; Cummins Part No. 212, 37665; Cummins Part No. 312/212, 37676; Cummins Part No. 312/212, 37610; Cummins Part No. 313/212, 37642Service part / kit Amazon eBay
0179-2862Nema 284T frame has the following arrangement: 6311 C3 / 18gram Polyrex – EM /20,000h6Service part / kit Amazon eBay
0179-3291Nema 284T frame has the following arrangement: 6311 C3 / 11gram Polyrex – EM /20,000h8Service part / kit Amazon eBay
130-5077-02Tube, Heater1Service part / kit Amazon eBay
130-5078-02Tube, Heater1Service part / kit Amazon eBay
130-5079-02Tube, Heater1Service part / kit Amazon eBay
130-5080-02Tube, Heater1Service part / kit Amazon eBay
130-5089-02Tube, Heater1Service part / kit Amazon eBay
323-1491* Pin, Contact (Used With Inline G)3Service part / kit Amazon eBay
323-1492* Socket, Contact (Used In Stations 18, 19)4Service part / kit Amazon eBay
323-1688* Socket, Contact (Used In P1)6Service part / kit Amazon eBay
323-1718* Pin, Contact (Used In Station 17)2Service part / kit Amazon eBay
4-2002PowerCommand Control1Service part / kit Amazon eBay
898-1254-25Sleeving – Heater Leads (59”)1Service part / kit Amazon eBay
A056A610RECOMMENDED SPARES LIST (RSL) FOR DQKAD GENERATOR SETS1Service part / kit Amazon eBay
A056A611RECOMMENDED SPARES LIST (RSL) FOR DQKAE GENERATOR SETS1Service part / kit Amazon eBay
A056A612RECOMMENDED SPARES LIST (RSL) FOR DQKAF GENERATOR SETS1Service part / kit Amazon eBay
A056F840Recommended Spares List (RSL) for DQKAN Generator SetsService part / kit Amazon eBay
M-3089173Bushing - CamshaftService part / kit Amazon eBay
M-4007741Bushing - CamshaftService part / kit Amazon eBay
M-4089083Single Cylinder HeadARService part / kit Amazon eBay
M-4089200Juego de Junta Modul. N. ° de Pieza4Service part / kit Amazon eBay
M-4089201Juego Posenfriador Cuadrante N. ° de Pieza4Service part / kit Amazon eBay
M-4089202Juego Sistema Enfriamiento N. ° de Pieza1Service part / kit Amazon eBay
M-4089231Juego de Junta Modul. N. ° de Pieza4Service part / kit Amazon eBay
M-4089232Juego Posenfriador Cuadrante N. ° de Pieza4Service part / kit Amazon eBay
M-4089307Juego Bomba Inferior N. ° de Pieza1Service part / kit Amazon eBay
M-4089308Juego Combustible Inferior N. ° de Pieza1Service part / kit Amazon eBay
M-4089508Juego de Junta Modul. N. ° de Pieza4Service part / kit Amazon eBay
M-4089509Juego Sistema Enfriamiento N. ° de Pieza1Service part / kit Amazon eBay
M-4089874Juego Bloque Inferior N. ° de Pieza1Service part / kit Amazon eBay
M-4955369Juego Posenfriador Cuadrante N. ° de Pieza4Service part / kit Amazon eBay
M-4955370Juego de Junta Modul. N. ° de Pieza4Service part / kit Amazon eBay
M-4956000Culata Cilindro Simple N. ° de Pieza AR1Service part / kit Amazon eBay

Service, wear & replacement parts referenced for this model and its engine — confirm the exact part for your serial number. See the full parts catalog to search and cross-reference.

Fuel consumption

RatingLoadL/hgal/h
Prime470.0124.1
Prime3%381.0100.6
Prime25%159.042.0
Prime50%246.065.0
Prime75%337.089.0
Prime100%424.0112.0
Standby535.0141.3
Standby3%407.0107.3
Standby25%167.044.0
Standby50%261.069.0
Standby75%356.094.0
Standby100%458.0121.0

Available documents

Spec sheet — Cummins-1750-kW-Diesel-Generator-Model-DQKAA-1508675-QSK60-Spec-Sheet (Cummins/Onan)Spec sheet — Cummins-2000-DQKAB QSK60-G6-NR2 (Cummins/Onan)Spec sheet — Cummins-2000-kW-DQKAB-Diesel-Generator-Specsheet (Cummins/Onan)Spec sheet — Cummins-DQKAB-data-sheet (Cummins/Onan)Spec sheet — Cummins-DQKAB-spec-sheet (Cummins/Onan)Spec sheet — New-Cummins-DQKAA-submittal (Cummins/Onan)Spec sheet — New-Cummins-DQKAB-OPU-submittal (Cummins/Onan)Spec sheet — cummins-dqkab-1535 (Cummins/Onan)Reference — 0058537Parts manual — 0961-0210 I28 202305 (Cummins/Onan)

This page was generated from the 10 manufacturer documents above by automated extraction; every figure shown is copied from one of them. How the data is compiled.

Full service, cheapest listings

Priced items from this model's own parts manual.

Fuel filter (primary) A055Y798$5944.00