Home›Cummins/Onan›Cummins/Onan DFAC

Cummins/Onan DFAC Generator Set

The Cummins/Onan DFAC is a 250 kW (313 kVA) Diesel standby generator set powered by a Cummins/Onan LTA10 engine. It is available at 110/190 V, 115/200 V, 120/208 V, 120/240 V, 127/220 V, 139/240 V, 220/380 V, 240/416 V, 254/440 V, 277/480 V and 347/600 V, 3-phase and 60 Hz. It holds about 36 L (9.5 gal) of oil and 49 L (12.9 gal) of coolant, with a maximum ambient rating of 50 °C. Starting uses 2 group-8 batteries rated 1400 CCA at 24 V. The set measures 3404×1270×1617 mm (134.0×50.0×63.7 in) and weighs about 2676 kg (5900 lb). The same LTA10 engine also powers generator sets from AKSA.

250 kW
Standby
36.0 L
Oil capacity
4
Document types

How to read your Cummins/Onan serial & model number →

Typical fuel consumption for 250–255 kW Diesel generators →

Compare with other 250–255 kW Diesel generators →

Specifications

FuelDiesel
Frequency60.0 Hz
Standby power250 kW
Standby kVA313
Prime power225 kW
ControllerDetector, PowerCommand, PowerCommand 2100, PowerCommand 3100
Oil capacity36.0 L
Voltage options110/190 V, 115/200 V, 120/208 V, 120/240 V, 127/220 V, 139/240 V, 220/380 V, 240/416 V, 254/440 V, 277/480 V, 347/600 V
Phasethree phase
Battery group8D
Battery cranking1400 CCA
Battery voltage24 V
Battery quantity2
Coolant capacity49 L
Max ambient50 °C
Dimensions (L×W×H)3404×1270×1617 mm
Dry weight2676 kg
Wet weight2762 kg

Engine

Cummins/Onan LTA10
Oil capacity36.0 L
Coolant capacity49.0 L

Filters for the Cummins/Onan LTA10

6

Engine-mounted filters the filter manufacturers list for this engine family. These come from the engine, not from this generator set’s own parts list, so confirm against your serial number before ordering.

SystemFilterDescriptionCross-references
Oil filterP550777Lube Filter, Spin-On BypassCUMMINS 3021658, CUMMINS 33004232, NAPA 1749, BALDWIN B7577 FridayParts $43.56
Oil filterP551670Lube Filter, Spin-On Full FlowCUMMINS 298670, CUMMINS 299670, NAPA 1970, CARBOCOL 0026 FridayParts $26.68
Fuel filterP550105Fuel Filter, Spin-On PrimaryCUMMINS 154700, CUMMINS 154710, NAPA 3109, NAPA 3405 buy
Fuel / water separatorP558000Fuel Filter, Water Separator Spin-On Twist&DrainCUMMINS 3308638, CUMMINS 3308683, NAPA 3405, NAPA 3693 KuduParts $24.00 FridayParts $25.66
Fuel / water separatorP550106Fuel Filter, Water Separator Spin-OnCUMMINS 154789, CUMMINS 156164, NAPA 3405, BALDWIN BF957-D FridayParts $285.60
Coolant filterP554071Coolant Filter, Spin-OnCUMMINS 209604, CUMMINS 209606, NAPA 4071, WALGAHN-MOTORENTECHN 00811412 FridayParts $397.60

Same engine, other brands

1 brand

The Cummins/Onan LTA10 in this set also powers 2 generator sets sold under 1 other brand. Service parts and maintenance intervals for the engine are shared; enclosure, alternator, controller and ratings are not.

BrandModels
AKSAAC250, AC275

Maintenance & consumables

for the Cummins/Onan LTA10
ItemSpecCapacityPart #Interval
Air filter—
Fuel filter—
Oil filter—268 hr
Battery—
Belt—
Coolant-5049.0—
OilCummins engine Operation and Maintenance Manual36.0 L—
Spark plug—

Service intervals

1
ItemActionHoursMonthsNotes
Rupture basin leak detect switchTest12 moSome areas may require weekly inspections by safety code.

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Service specifications

60
TypeItemValueUnitCondition
ClearanceAngular alignment T.I.R. limitnot more than .001in per inch of radiuscenter of shaft to indicator axis
ClearanceAngular alignment maximum T.I.R.0.001inch per inch of radius (center of shaft to indicator axis)measuring deflection to bolt heads
ClearanceFloat switch assembly float lift clearance below C-clip stop1/8inch (3 mm)use a feeler gauge
ClearanceGenerator-to-engine angular alignment (T.I.R.).001 in. per inch of radius (center of shaft to indicator axis), maximumin750 kW gensets and larger
ClearanceMPU sensor to gear tooth adjustmentback out one quarter turnturnafter contacting gear tooth
ClearanceVibration isolator base elevation difference0.25inch (6 mm)all isolator bases within this elevation of each other
ClearanceVibration isolator clearance between top plate and base0.25inch (6 mm)nominal or greater
ClearanceVibration isolator top plate to base clearance0.25inch (6 mm)nominal, or greater
GapAngular alignment total indicator reading (T.I.R.)0.001inch per inch of radiusmaximum
GapFloat switch lift to test open1/8inchbelow C-clip stop
GapMPU sensor to flywheel ring gear toothback it out one quarter turnturnsensor threaded in until it just touches gear tooth
OtherAVR Droop setting5% at full load, 0 PF
OtherAVR voltage regulation (load regulation)approximately ±0.5% RMS
OtherAngular alignment maximum T.I.R..001inch per inch of radiuscenter of shaft to indicator axis
OtherAngular alignment maximum T.I.R..001 inches per inch of radiusin/incenter of shaft to indicator axis
OtherBattery specific gravity (high ambient, above 95F/35C)1.225recommended to reduce electrolyte loss
OtherBattery specific gravity (recharge threshold)below 1.260
OtherBattery specific gravity, fully chargedapproximately 1.260specific gravityat 80 F (27 C)
OtherFuel lift height limit6feet(1.8 meters) between fuel lift pump and bottom of dip tube
OtherGOV GAIN default value for paralleling applications70%
OtherMaximum cranking voltage drop2voltsdifference between battery and starter terminals while cranking
OtherOver/Under Frequency Sensor Module - Over Hz Set, 50 Hz nominal55Hzreset 53 Hz
OtherOver/Under Frequency Sensor Module - Over Hz Set, 60 Hz nominal65Hzreset 63 Hz
OtherOver/Under Frequency Sensor Module - Under Hz Set, 50 Hz nominal45Hzreset 47 Hz
OtherOver/Under Frequency Sensor Module - Under Hz Set, 60 Hz nominal55Hzreset 57 Hz
OtherOver/Under Voltage Sensor Module time delaytypically 25 percent, approximately 2.5seconds
OtherOvercrank cranking limit75secondsthree 15-second cranking cycles with two 15-second rest periods
OtherOvercurrent shutdown threshold110% of rated% of ratedPCC time/current calculation
OtherOvercurrent warning threshold110% of rated for 60 seconds% of ratedgenerator output current
OtherOverload warning threshold105% of standby or 115% of prime% of ratingthree-phase power output; load dump after five seconds, warning after 60 seconds
OtherREG VHZ (underfrequency roll-off) adjustable range1 through 50; normal range 7 through 21
OtherShort circuit shutdown threshold175% of rated% of ratedgenerator output current
OtherStart delay adjustment range0 to 300seconds
OtherStop delay adjustment range0 to 600seconds
OtherUnder Frequency Roll Off (UFRO) knee point, 50 Hz units48 to 49Hz
OtherUnder Frequency Roll Off (UFRO) knee point, 60 Hz units58 to 59Hz
OtherUnder-frequency roll-off threshold (UFRO)typically 59 Hz for 60 Hz applications and 49 Hz for 50 Hz applicationsHzAVR UFRO pot preset
OtherWeak battery warning thresholdbelow 60% of nominal for two seconds% of nominalduring starting
PressureEngine oil pressure - K19 normal50-70psi (345-482 kPa)run mode
PressureEngine oil pressure - K38 normal45-65psi (310-448 kPa)run mode
PressureEngine oil pressure - K50 normal50-70psi (345-482 kPa)run mode
PressureEngine oil pressure - L10/M11 normal30-50psi (207-345 kPa)run mode
PressureEngine oil pressure - NTA 855 normal35-50psi (241-345 kPa)run mode
PressureEngine oil pressure - V28 normal50-90psi (345-620 kPa)run mode
PressureEngine oil pressure shutdown limit - L10/M1120psi (138 kPa)run mode value
PressureEngine oil pressure shutdown limit - L10/M118psi (55 kPa)idle mode value
PressureEngine oil pressure warning limit - L10/M1112psi (83 kPa)idle mode value
PressureEngine oil pressure warning limit - L10/M1125psi (172 kPa)run mode value
PressureK19 engine idle oil pressure20psi (138 kPa)idle
PressureK19 engine normal oil pressure50-70psi (345-482 kPa)normal run
PressureK19 normal oil pressure (run/idle)50-70 / 20psi (345-482 / 138 kPa)NORM run / IDLE
PressureK19 oil pressure shutdown limit10psi (69 kPa)idle mode
PressureK19 oil pressure shutdown limit35psi (241 kPa)run mode
PressureK19 oil pressure shutdown/warning limitsshutdown 35 psi (241 kPa) run; warning 40 psi (276 kPa) run; shutdown 10 psi (69 kPa) idle; warning 15 psi (103 kPa) idlepsi (kPa)
PressureK19 oil pressure warning limit15psi (103 kPa)idle mode
PressureK19 oil pressure warning limit40psi (276 kPa)run mode
PressureK38 engine idle oil pressure20psi (138 kPa)idle
PressureK38 engine normal oil pressure45-65psi (310-448 kPa)normal run
PressureK38 normal oil pressure (run/idle)45-65 / 20psi (310-448 / 138 kPa)NORM run / IDLE
PressureK38 oil pressure shutdown limit10psi (69 kPa)idle mode

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Recommended fluids

FluidGradeStandardAmbientCapacityNotes
Coolantsoft water / E.G. / DCA mixtureCooling system to be filled with soft water/E.G./DCA mixture (on-site review checklist).
CoolantNFPA 110above 4°CNFPA 110 recommends engine jacket water coolant heaters where minimum ambient is above 40°F (4°C); coolant maintained at minimum 90°F (32°C). Cooling system capacity with standard radiator: DFAB/DFAC 13 Gal (49 L); DFBF 13.5 Gal (51 L); DFCC 13.5 Gal (51 L); DFCE 15 Gal (57 L).
FuelASTM No. 2 dieselCummins engine Operation and Maintenance Manual alternate diesel fuelsCummins engines normally use ASTM No. 2 diesel fuel. Never use galvanized or copper fuel lines, fittings or fuel tanks.
FuelASTM No. 2 diesel fuelASTM No. 2Cummins engines normally use ASTM No. 2 diesel fuel; they will operate on alternate diesel fuels within the specifications shown in the Cummins engine Operation and Maintenance Manual. Never use galvanized or copper fuel lines, fittings or fuel tanks.
FuelDieselDay tank fuel transfer pump maintains reservoir of diesel fuel in the day tank.
Fuelnumber 2 diesel fuelDirect injection fuel system
GreaseLithium based greaseMobilux No. 2 or Shell Alvania R32.74 oz (81 ml)Generator end bearing. Temperature range -22F to +248F (-30C to +120C). Grease should be equally divided between the bearing, bearing cap cavity, and bearing cartridge cavity.
GreaseLithium based-30°C to 120°C81.0 mlMobilux No. 2 or Shell Alvania R3; generator end bearing; temperature range -22 F to +248 F (-30 C to +120 C); grease divided between bearing, bearing cap cavity and cartridge cavity.
GreaseLithium based grease, Mobilux No. 2 or Shell Alvania R3-30°C to 120°C2.74 oz (81 ml)End bearing lubricant; grease equally divided between bearing, bearing cap cavity and bearing cartridge cavity.

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Fault codes

80
CodeNameMeaningSeverityAction
101IDLE MODEIndicates that the engine is operating in idle mode (governed at 800 RPM, generator build-up inhibited).WarningRemove ground from engine idle input to return to normal speed and voltage.
102EMERGENCY STOPIndicates local or remote Emergency Stop.ShutdownTurn the switch clockwise and allow it to pop out (local only). Move the Run/Off/Auto switch to Off. Press the Reset switch. Select Run or Auto, as required.
121SPEED SIGNAL LOSTMag pickup speed indication is not being sensed.ShutdownRestart and check RPM on the digital display.
135OIL PRESSURE SENSOR HEngine oil pressure sender signal is shorted high.WarningCheck sender/connectors/wires.
141OIL PRESSURE SENSOR LEngine oil pressure sender signal is shorted low.WarningCheck sender/connectors/wires.
143PRE-LOW OIL PRESEngine oil pressure has dropped to an unacceptable level.WarningIf critical loads, wait until next shutdown period and follow code 415.
144COOL SENSOR HIGHEngine coolant temperature signal is shorted high.WarningCheck sender/connectors/wires.
145COOL SENSOR LOWEngine coolant temperature signal is shorted low.WarningCheck sender/connectors/wires.
146PRE-HIGH COOL TMPEngine has begun to overheat.WarningReduce load; check air inlets/outlets; follow code 151 if engine can be stopped.
151HIGH COOLANT TEMPEngine has overheated above the shutdown trip point.ShutdownAllow cool down; check coolant level, cooling airflow, fan belt, blower fan and circulation pumps.
197LOW COOLANT LEVELEngine coolant level has fallen below the warning trip point.WarningCheck coolant level and replenish if low; reset control.
200LOW OIL PRESSUREIndicates engine oil pressure has dropped to an unacceptable level.WarningIf generator is powering critical loads and cannot be shut down, wait until next shutdown period and then follow 201-SHUTDOWN procedure. Access the Oil Pressure menu prior to clearing the fault.
201LOW OIL PRESSUREIndicates engine oil pressure has dropped below the shutdown trip point.ShutdownCheck oil level, lines and filters. If oil system is OK but oil level is low, replenish. Reset control and restart. Oil pressure limits are listed in Table 4-3.
204OIL PRES SENDERIndicates that the control has sensed that the engine oil pressure sender is out of its working range.WarningCheck that the engine oil pressure sender is properly connected.
210LOW COOLANT TEMPSet is not operating. Warning occurs when engine coolant temperature is 70° F (21° C) or lower.WarningIndicates engine coolant heater is not operating or is not circulating coolant. Check coolant heater power supply, low coolant level, and heater element current draw.
211HIGH COOLANT TEMPIndicates the engine coolant temperature is getting close to the recommended maximum temperature limit: 215° F (102° C) − standby or 207° F (97° C) − primary.WarningReduce load if possible by turning off non-critical loads. Check air inlets and outlets and remove any obstructions to airflow. If engine can be stopped, follow 212-SHUTDOWN procedure.
212HIGH COOLANT TEMPIndicates engine has overheated (coolant temperature above 215° F (102° C) − standby or 207° F (97° C) − primary).ShutdownAllow engine to cool down completely. Check for obstructions to cooling airflow; check fan belt; check coolant mixture; check blower fan and circulation pumps on remote radiator installations. Reset control and restart.
213COOLANT SENDERIndicates that the resistance of the coolant temperature sender is out of range.WarningCheck the resistance of the sender. Resistance should be 500 to 2k ohms.
214LOW COOLANT LVLIndicates engine coolant level has fallen below the trip point.WarningAllow engine to cool down completely. Check coolant level in both radiator and coolant recovery bottle and replenish if low. Look for coolant leakage points and repair if necessary.
215LOW COOLANT LVLIndicates engine coolant level has fallen below the trip point.ShutdownAllow engine to cool down completely. Check coolant level in both radiator and coolant recovery bottle and replenish if low. Reset control and restart after correcting problem. Shutdown will not occur if genset is in Idle mode (low coolant warning only).
220MAG PICKUPIndicates mag pickup speed indication is not being sensed or does not match generator set output frequency.ShutdownRestart and check RPM on the digital display.
221FAIL TO CRANKIndicates possible fault with control or starting system.ShutdownCheck fuse F3 on the Engine Interface board. Check for poor battery cable connections; clean battery cable terminals and tighten. Recharge or replace a discharged or defective battery.
222OVERCRANKIndicates possible fuel system problem.ShutdownCheck for empty fuel tank, fuel leaks, or plugged fuel lines. Check for dirty fuel filter and replace if necessary. Check for dirty or plugged air filter and replace if necessary. Reset the control and restart after correcting the problem.
223OVERSPEEDEngine has exceeded normal operating speed (115% ±1% of nominal).ShutdownCheck mechanical fuel linkage and actuator; check governor output module (A38) and digital board (A32).
224FAIL TO SYNCHRONIZEGenerator set has not synchronized to the system bus within the allowable time frame.WarningCheck governor system stability; adjust governing and synchronizer parameters; check fuel system.
226FAIL TO CLOSEParalleling breaker has been given a signal to close, but has not closed properly.ShutdownVerify breaker charging mechanism; check close signal; verify auxiliary contact signals.
230LOW DC VOLTAGEIndicates battery voltage is below 10 VDC.WarningRecharge or replace the battery; check the battery charger fuse. Clean and tighten battery cable connections. Check engine DC alternator; replace if normal charging voltage is not obtained. Check float level if applicable.
231HIGH DC VOLTAGEIndicates battery voltage exceeds 32 VDC.WarningCheck float level on battery charger if applicable (lower float level). Check engine DC alternator; replace if normal battery charging voltage is not obtained.
232WEAK BATTERYIndicates battery voltage drops below 60% of nominal for two seconds, during starting.WarningDischarged or defective battery. See Warning message 230, LOW DC VOLTAGE.
234OVERSPEEDEngine has exceeded normal operating speed.ShutdownCheck for large block load removal, flammable vapors or leaking turbocharger seals.
235LOW COOLANT LEVELEngine coolant level has fallen below the shutdown trip point.ShutdownCheck coolant level and replenish if low; reset control.
240LOW FUEL−DAYIndicates day tank fuel supply is running low.WarningCheck fuel supply and replenish as required.
241LOW FUELIndicates day tank fuel supply is running low.WarningCheck fuel supply and replenish as required.
250EEPROM ERRORPCC memory error; data corruption of critical operating parameters.ShutdownPerform initial start setup procedure; replace digital board (A32) if fault repeats.
251EEPROM ERRORPCC memory error; data corruption of noncritical operating parameters.WarningPerform adjustment and calibration procedures; replace digital board (A32) if fault repeats.
252EEPROM ERRORPCC memory error; data corruption of noncritical operating parameters.WarningVerify selected values; repeat save operation; replace digital board (A32) if fault repeats.
260CUSTOMER FAULT 1When a customer defined input is closed to ground, the corresponding fault message is displayed. Default message; editable for customer site requirements.WarningFault functions can be programmed to initiate a shutdown or a warning.
261GROUND FAULTWhen a customer defined input is closed to ground, the corresponding fault message is displayed. Default message; editable for customer site requirements.WarningFault functions can be programmed to initiate a shutdown or a warning.
262RUPTURE BASINWhen a customer defined input is closed to ground, the corresponding fault message is displayed. Default message; editable for customer site requirements.WarningFault functions can be programmed to initiate a shutdown or a warning.
263HIGH GEN TEMPWhen a customer defined input is closed to ground, the corresponding fault message is displayed. Default message; editable for customer site requirements.WarningFault functions can be programmed to initiate a shutdown or a warning.
270PHASE ROTATIONThe phase relationship between the generator set and the system bus is not matched.ShutdownVerify genset phase rotation matches bus; verify control wiring to bus PT module.
272FIRST STARTPowerCommand control is not receiving a proper signal from the system master first start sensor.WarningVerify Master First Start Sensor and interconnection wiring.
301HIGH AC VOLTAGEOne or more phase voltages exceeded 130% of nominal, or exceeded 110% of nominal for 10 seconds.ShutdownCheck PCC, alternator, excitation circuit, and PT/CT module wiring.
303LOW AC VOLTAGEOne or more phase voltages dropped below 85% of nominal for 10 seconds.ShutdownCheck PMG/field wiring, rotating rectifier, load and connectors.
313UNDER FREQUENCYIndicates that engine speed has dropped below 90% of nominal for 10 seconds. Five seconds before shutdown, a Load Dump signal is initiated.ShutdownCheck fuel supply, intake air supply and load.
320OVERCURRENTIndicates that generator output current has exceeded 110% of rated for 60 seconds.WarningCheck load and load lead connections.
321OVERCURRENTIndicates that generator output current has exceeded 110% of rated, and that a PCC time/current calculation has initiated an overcurrent shutdown.ShutdownCheck load and load lead connections.
322SHORT CIRCUITIndicates that generator output current has exceeded 175% of rated.ShutdownCheck load and load lead connections.
330OVERLOADIndicates that three-phase power output exceeds 105% of standby (or 115% of prime) rating. After five seconds, the Load Dump output is activated. After 60 seconds, the OVERLOAD warning is activated.WarningCheck load and load lead connections.
335REVERSE POWERIndicates improper CT or PT phasing. (Non-parallel units only.)ShutdownCheck CT / PT wiring. Refer to CT Installation in Section 5.
337LOSS OF EXCITATIONAlternator excitation system is improperly adjusted or has failed.ShutdownCheck output voltage calibration, load sharing lines, and leading power factor loads.
359FAIL TO STARTEngine cranks but fails to start after last crank time.ShutdownCheck fuel tank, leaks, fuel lines, fuel filter, air filter; check fuel solenoid and actuator.
415LOW OIL PRESSUREEngine oil pressure has dropped below the shutdown trip point.ShutdownCheck oil level, lines and filters; replenish if low; reset control.
421OIL TEMPEngine oil temperature has exceeded the warning threshold.WarningReduce load; check air inlets/outlets; check engine oil level.
441LOW BAT VOLTAGEBattery voltage supply to the control is approaching a low level.WarningRecharge or replace battery; check charger fuse, connections and DC alternator.
442HIGH BAT VOLTAGEBattery voltage supply is approaching a high level.WarningCheck battery charger float level; check battery wiring/calibration.
1123SHUTDOWN AFTER BSShutdown fault occurred while Battle Short was enabled and then disabled.ShutdownReview Fault History and perform corrective action.
1124DELAYED SHUTDOWNShutdown fault became active while Delayed Shutdown feature was enabled.WarningReview Fault History and perform corrective action.
1131BATTLE SHORT ACTIVEControl is in Battle Short mode.WarningBypasses several critical fault shutdowns for emergency operation.
1311, 1312, 1317, 1318CUSTOMER INPUT #1 - #4Optional customer-selected fault input is active.WarningCheck external wiring and active input (closed/open) selection.
1334CRIT SCALER ORIncorrect feature or calibration entered into control.ShutdownReload correct calibration.
1335NONCRIT SCALER ORIncorrect feature or calibration entered into control.WarningReload correct calibration.
1416FAIL TO SHUTDOWNGenset continues to run after shutdown command.WarningCheck Battle Short feature enabled condition.
1417POWER DOWN ERRORController cannot power down.WarningCheck for possible battery drain.
1433EMERGENCY STOPLocal Emergency Stop.ShutdownPull button out; move switch to O; press Fault Acknowledge/Reset; select Manual or Auto.
1434REMOTE E-STOPRemote Emergency Stop.ShutdownSee code 1433 to reset.
1435Engine ColdEngine jacket water coolant temperature falls below 70°F (21°C); Warning LED illuminated (provided to meet NFPA 110 requirements)WarningCheck the coolant heaters for proper operation
1438FAIL TO CRANKEngine failed to crank after PCC received a start signal.ShutdownCheck starter, fuse F3, K4 relay, E-Stop switch and MPU circuit.
1442WEAK BATTERYBattery voltage at or below weak battery warning trip point during cranking.WarningSee code 441 for corrective action.
1443BATTERY FAILEDDead battery - engine will not start.ShutdownSee code 441 for corrective action.
1444KW OVERLOADGenerator output power exceeded 105% of genset rating.WarningCheck load and load lead connections; check CTs.
1445SHORT CIRCUITGenerator output current has exceeded 175% of rated.ShutdownCheck load and load lead connections.
1446HIGH AC VOLTAGEOne or more phase voltages exceeded 130% of nominal.ShutdownCheck fault simulation, load removal, threshold settings, Base board/generator.
1447LOW AC VOLTAGEPhase voltages dropped below 85% of nominal for 10 seconds.ShutdownCheck overload, output terminal connections, PMG/field wiring, rectifier diodes.
1448UNDER FREQUENCYEngine speed dropped below 90% of nominal for 10 seconds.ShutdownCheck fuel supply, intake air supply and load.
1449OVER FREQUENCYFrequency is 10% above base frequency for 20 seconds.WarningCheck fuel or air delivery; check connections.
1452GEN CB NOT CLOSEGenset circuit breaker (S2) failed to close when PTC is enabled.WarningRefer to Section 5 troubleshooting charts.
1453GEN CB NOT OPENGenset circuit breaker (S2) failed to open when PTC is enabled.WarningRefer to Section 5 troubleshooting charts.
1459REVERSE POWERImproper CT phasing.ShutdownCheck wiring to voltage sense circuit; refer to CT Installation in Section 6.
1461LOSS OF FIELDLoss of field (electric) due to reverse kVAR.ShutdownCheck excitation circuit.

Showing the first 80 of 125 codes.

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Procedures

12
Adjust Start/Stop Delays (PCC Adjust Menu) adjustment

⚠ Electrostatic discharge will damage circuit boards. Always wear a grounding wrist strap when working inside control box.

  1. Press the button next to ADJUST in the Main Menu; the VOLTAGE submenu appears.
  2. Press the button next to >> to move through VOLTAGE and FREQUENCY to the START DELAY submenu.
  3. Use the buttons next to the up and down symbols to set the start delay.
  4. Press >> to move to the STOP DELAY submenu and set the stop delay.
  5. Press >> to move to the IDLE SPEED submenu and set idle speed (only in idle mode).
  6. Press >> to move to SAVE/EXIT; select SAVE then EXIT to return to Main menu.
Adjusting Values/Parameters (PCC Adjust Menu) adjustment
  1. Press the button next to the arrow symbol in the display until the + and - symbols are displayed.
  2. If necessary, press the button next to the arrows to move to the numeric character to change.
  3. Press + to increase the value or select the parameter; press - to decrease the value or select the parameter.
  4. Press the save symbol to save changes; changes are not saved if Home or Previous Main Menu is pressed first.
Aligning Generator with Engine (Angular Alignment) adjustment

⚠ Accidental starting of the generator set during this procedure presents the hazard of severe personal injury or death.

Tools: Dial indicator, Shims

  1. Disconnect the negative (-) battery cable(s) before beginning.
  2. Fasten a dial indicator to the generator shaft or cooling fan with the sensing point on the capscrew head or flat surface of the drive disc at the bolt circle diameter.
  3. Bar the engine over in a clockwise rotation as viewed from engine flywheel; do not allow it to roll back on compression.
  4. Determine the total indicator reading (T.I.R.) as the sum of the maximum positive and negative dial indicator readings over one revolution.
  5. Measure the distance from the center of the generator shaft to the indicator measuring point.
  6. Measure the distance from the generator side of the flex discs to the center of the generator mounting bolt.
  7. Compare the distances; multiply this ratio times one half the T.I.R. to approximate the amount of shims to remove or add.
Angular Alignment Procedure adjustment

⚠ Accidental starting of the generator set during this procedure presents the hazard of severe personal injury or death. Make sure to disconnect the negative (-) battery cable(s) before beginning.

Tools: Dial indicator, Wooden shims

  1. Disconnect the negative (-) battery cable(s) before beginning.
  2. Fasten a dial indicator to the generator shaft or cooling fan with sensing point on capscrew head or flat surface of drive disc at bolt circle diameter.
  3. Bar the engine over in a clockwise rotation as viewed from engine flywheel; do not allow it to roll back on compression.
  4. Record maximum positive and negative dial indicator readings as the engine completes one revolution.
  5. T.I.R. equals the sum of the maximum positive and negative readings.
  6. Maximum T.I.R. should not be more than .001 inch for each inch of radius.
  7. Remove equal shims from under both generator mounting feet to lower the generator.
Angular Alignment Procedure (750 kW Gensets and Larger) adjustment

⚠ Accidental starting of the generator set during this procedure presents the hazard of severe personal injury or death. Make sure to disconnect the negative (-) battery cable(s) before beginning.

⚠ Do not bar engine over by prying on fan blade.

Tools: Dial indicator, Shims

  1. Disconnect the negative (-) battery cable(s) before beginning.
  2. Fasten a dial indicator to the generator shaft or cooling fan, with the sensing point on the capscrew head or drive disc flat surface at bolt circle diameter.
  3. Bar the engine over clockwise as viewed from the engine flywheel; do not allow it to roll back on compression.
  4. Total indicator reading (T.I.R.) is the sum of the maximum positive and negative readings as the engine completes one revolution.
  5. To lower the generator, remove equal shims from under both generator mounting feet; approximate shim amount from the distance ratio.
Angular Alignment Procedure (Generator to Engine) adjustment

⚠ Accidental starting during this procedure presents the hazard of severe personal injury or death.

⚠ Do not bar engine over by prying on fan blade.

Tools: dial indicator

  1. Disconnect the negative (-) battery cable(s) before beginning.
  2. Fasten a dial indicator to the generator shaft or cooling fan with sensing point resting on the drive disc capscrew head/flat surface at the bolt circle diameter.
  3. Bar the engine over in a clockwise rotation as viewed from the engine flywheel; do not allow it to roll back on compression at the end of travel of each reading.
  4. Record the total indicator reading (T.I.R.) as the sum of the maximum positive and negative dial indicator readings over one engine revolution.
  5. Compare the measured T.I.R. to the maximum allowed (.001 in. per inch of radius from center of shaft to indicator axis); add or remove shims under the generator mounting feet to correct.
Axial Alignment Procedure adjustment

Tools: Dial indicator, Magnetic base or clamp

  1. Check axial alignment only when an objectionable vibration is present after angular alignment.
  2. Fasten dial indicator holding device to skid base, engine block, or generator shell with a magnetic base or clamp; rest sensor on generator shaft hub.
  3. Bar the engine over clockwise through a couple of rotations; record indicator readings at eight equally spaced points around the shaft diameter.
  4. To correct out-of-tolerance T.I.R., remove the drive disc capscrews, mark discs and flywheel, rotate 180 degrees from original location, retorque, and recheck.
  5. If unchanged, rotate the discs to 30, 60 or 90 degrees from their original location.
Axial Alignment Procedure (Generator to Engine) adjustment

Tools: dial indicator

  1. Fasten a dial indicator holding device to the skid base, engine block, or generator shell with the sensor point resting on the generator shaft hub.
  2. Bar the engine over in a clockwise rotation through a couple of rotations, recording indicator readings at eight equally spaced points around the shaft diameter to obtain axial T.I.R.
  3. Reduce the measured T.I.R. runout by one half if excessive vibration remains after angular alignment.
Governor Calibration Checks adjustment

Tools: Frequency meter or tachometer, Jumper wire

  1. Start the generator set.
  2. Adjust engine no-load speed to the desired allowable speed droop using the Run Speed potentiometer.
  3. With no load, turn GAIN clockwise slowly until engine speed oscillates.
  4. Reduce GAIN slowly counterclockwise until engine speed is stable.
  5. Upset the governor by momentarily shorting terminals 7 and 10 on the governor control.
  6. Apply and remove loads to check generator set response.
HC4-7 Axial Alignment Procedure adjustment

Tools: Dial indicator with magnetic base or clamp

  1. Check only when an objectionable vibration is present.
  2. Fasten dial indicator holding device to skid base, engine block, or generator shell with magnetic base or clamp.
  3. Position sensor point on the generator shaft hub.
  4. Bar the engine over in a clockwise rotation as viewed from engine flywheel through a couple of rotations.
  5. Record indicator readings in eight equally spaced points around the shaft diameter.
  6. Remove the capscrews connecting drive discs and flywheel and mark discs and flywheel.
  7. Rotate engine or generator so drive disc holes are repositioned 180 degrees from original location.
  8. Put capscrews back in and retorque. Recheck shaft alignment.
  9. If runout unchanged, rotate discs to 30, 60 or 90 degrees from original location.
  10. If T.I.R. does not improve, inspect flywheel pilot and drive disc runouts.
P7 Axial Alignment Procedure adjustment
  1. Check only when an objectionable vibration is present.
  2. Remove the capscrews connecting drive discs and flywheel.
  3. Mark the drive discs and flywheel with respect to each other.
  4. Rotate engine or generator so drive discs holes are repositioned two bolt holes from original location.
  5. Put capscrews back in and retorque. Recheck/record vibration levels.
  6. Repeat this test until drive disc holes are repositioned 180 degrees from original location.
  7. Review vibration data and position drive disc in lowest recorded level location.
UFRO Adjustments adjustment

⚠ Use an insulated handle screw driver to prevent electrical shock.

Tools: Insulated handle screwdriver, Frequency meter or tachometer

  1. Make a note of the no-load frequency.
  2. Determine roll-off frequency by turning the governor speed pot until the LED lights; if okay go to step 5.
  3. Adjust the governor speed pot to the proper roll-off frequency.
  4. Turn the UFRO pot until LED goes off, then slowly turn it back until the LED just goes on.
  5. Adjust the governor speed pot back to the initial frequency setting.

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Voltage reconnection

VoltagePhaseConnectionLeadsNotes
12 lead generator setsLoad wires are routed through the CTsReconnectable gensets (12 leads) have dual secondary CTs (3 pins); CT wire 2/3 to pin 2 (high voltage) or pin 3 (low voltage).
6 lead generator setsGenerator output leads are routed through the CTsNon-reconnectable gensets (6 leads) have single secondary CTs (2 pins).
Cummins PowerCommand generic AC Reconnect Wiring Diagram 625-2755 (Rev. D) and 625-3100 (Rev. F)Applies to models DFAA, DFAB, DFAC, DFBF, DFCB, DFCC, DFEB, DFEC, DFFB, DFGA, DFGB, DFJA, DFJB, DFJC, DFJD, DFLB, DFLC, DFLD, DFMB (625-2755) and models DFAA-DFMB plus DFCE, DFED, DQAA, DQAB, DQBA, DQBB (625-3100).
Current transformers CT21-U load leads (A phase), CT22-V load leads (B phase), CT23-W load leads (C phase)CT secondary wire marked 1 to pin 1; wire marked 2/3 to pin 2 for high voltage gensets or pin 3 for low voltage gensetsCT dot must face toward the generator; CTs have dual secondaries (3 pins).
Generator load terminals stamped U, V, W and N (U=L1, V=L2, W=L3, N=L0)Stranded load wires bolted to generator reconnection terminal block or circuit breaker lugsAvailable generator output voltages and maximum current ratings are specified on the generator set nameplate; line-to-neutral is the lower voltage, line-to-line the higher. Reconnection diagram is located on the upper side cover of the control housing.
ACT21 – U load leadsA phaseCT dot must face the generator; CT terminal 1 connects to metering circuit; terminal 2/3 connects to ground.
A (U)Bus PT module TB1 Abus A phaseBus PT module A39.
A (U)CT21U load leads (A phase)CT dot must face the generator; CT terminal 1 connects to metering circuit, terminal 2/3 to ground.
BCT22 – V load leadsB phaseCT dot must face the generator; CT terminal 1 connects to metering circuit; terminal 2/3 connects to ground.
B (V)Bus PT module TB1 Bbus B phaseBus PT module A39.
B (V)CT22V load leads (B phase)CT dot must face the generator; terminal 1 to metering circuit, terminal 2/3 to ground.
CCT23 – W load leadsC phaseCT dot must face the generator; CT terminal 1 connects to metering circuit; terminal 2/3 connects to ground.
C (W)Bus PT module TB1 Cbus C phaseBus PT module A39.
C (W)CT23W load leads (C phase)CT dot must face the generator; terminal 1 to metering circuit, terminal 2/3 to ground.
NBus PT module TB1 Nbus neutralBus PT module A39.
110 V - 120 V L-N1Single phase, 2-wirePTC module jumper locations
190 V - 240 V L-L3Three phaseUse PTC module 0300-5382-01; 50/60 Hz
200 V - 240 V L-L1Single phase, 3-wirePTC module jumper locations
380 V - 600 V L-L3Three phaseUse PTC module 0300-5382-02; 50/60 Hz
high voltage genset12-lead CT secondary wire marked 2/3 to pin 22/3For high voltage gensets.
low voltage genset12-lead CT secondary wire marked 2/3 to pin 32/3For low voltage gensets.

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Common questions

How many kW is the Cummins/Onan DFAC?

The Cummins/Onan DFAC is rated 250 kW standby (313.0 kVA).

What engine is in the Cummins/Onan DFAC?

The Cummins/Onan DFAC is powered by the Cummins/Onan LTA10 engine.

Is the Cummins/Onan DFAC diesel or gas?

The Cummins/Onan DFAC runs on Diesel.

What's the oil capacity on a Cummins/Onan DFAC?

The Cummins/Onan LTA10 engine in the Cummins/Onan DFAC has an oil capacity of 36.0 liters.

How much coolant does the Cummins/Onan DFAC hold?

The Cummins/Onan DFAC cooling system holds 49 liters (12.9 US gallons) for the radiator system including the engine, per the manufacturer specification sheet.

What is the prime power rating of the Cummins/Onan DFAC?

The Cummins/Onan DFAC is rated 225 kW prime (281 kVA), against 250 kW standby.

What is the dry weight of the Cummins/Onan DFAC?

The Cummins/Onan DFAC has a dry weight of 2676 kg (5899 lb).

What voltages is the Cummins/Onan DFAC available in?

The Cummins/Onan DFAC is offered in 110/190 V, 115/200 V, 120/208 V, 120/240 V, 127/220 V, 139/240 V, three phase-phase.

What battery does the Cummins/Onan DFAC use?

The Cummins/Onan DFAC uses 2 batteryies, 24 V each, 1400 CCA, group 8D, per the manufacturer specification sheet.

Troubleshooting

6

Fault codes

CodeMeaningCauseRemedy
101IDLE MODE — WARNING; Engine continues to operate at reduced RPM.Indicates that the engine is operating in idle mode. When the set is operating in the RUN mode, grounding the engine idle input causes generator build-up to be inhibited and the engine to be governed at 800 RPM.When ground is removed from this input, the set returns to normal speed and voltage. When the engine idle function is enabled, the control automatically sets lower oil pressure warning and shutdown trip points to reflect the lower operating speed. When the engine idle function is removed and the set reverts to normal operating speed, the control automatically resets oil pressure warning and shutdown trip points to the normal settings.
102EMERGENCY STOP — SHUTDOWN; Engine shuts down and will not crank.Indicates local or remote Emergency Stop.To reset the local Emergency Stop button: Pull the button out or turn the switch clockwise (button with arrow) and allow it to pop out; Move the Run/Off/Auto switch to Off; Press the Reset switch; Select Run or Auto, as required.
200LOW OIL PRESSURE — WARNINGIndicates engine oil pressure has dropped to an unacceptable level.If generator is powering critical loads and cannot be shut down, wait until next shutdown period then follow 201 Low Oil Pressure procedure. If engine can be stopped, follow 201 procedure. To check oil pressure, access Oil Pressure menu prior to clearing the fault.

Symptoms & remedies

SymptomCauseRemedy
Control does not power up when the Run/Off/Auto switch is set to Run or the Self Test switch is pressed.There is no DC power to the control.Check for battery disconnected, discharged, or improperly connected; Fuse F1 (20A/32V, Type 3AG) may be open. Replace with the same type. (Fuse is mounted near engine starter/solenoid, see Figure 4-2); Contact an authorized service center.
Warning, Shutdown, and Non-Automatic lamps are not lit. Digital display shows main menu or selected menu.Indicates all engine systems are normal.No corrective action required.
Non-Automatic lamp flashes.Indicates Run/Off/Auto switch is not in the Auto position. This will prevent automatic starting if an automatic transfer switch is used.Move the Run/Off/Auto switch to the Auto position for automatic operation.

Fault codes and symptom→remedy steps extracted from this model’s service/owner documentation; verify against the official manual before servicing. Full Cummins/Onan DFAC troubleshooting guide (115 entries) →

Parts

12
Part #DescriptionQtySystem
0300-4623-05DFAA (600V)1Current transformer Amazon eBay
0300-4623-06DFAB (600V)1Current transformer Amazon eBay $153.95
0300-4623-07DFAC (600V)1Current transformer Amazon eBay
0300-4623-17DFAA BR (0-480V)1Current transformer Amazon eBay $165.95
0300-4623-19DFAB BR (0-480V)1Current transformer Amazon eBay
0300-4623-21DFAC BR (0-480V)1Current transformer Amazon eBay
960-0167Battery, Group Number: 8D, CCA (minimum): 1400, Cold Soak® -40°F (-40°C)2Battery Amazon eBay
A40-TB1-2SWITCHED B+Belt Amazon eBay
A40-TB1-4GROUNDBelt Amazon eBay
A40-TB1-7COMMON ALARMBelt Amazon eBay
A40-TB1-8JUMPER WIREBelt Amazon eBay
LF3000Lube, Spin-On1Oil filter Amazon eBay $76.00 NAPA $66.59

Service, wear & replacement parts referenced for this model and its engine — confirm the exact part for your serial number. See the full parts catalog to search and cross-reference.

Fuel consumption

RatingLoadL/hgal/h
Prime25%20.05.2
Prime50%32.08.5
Prime75%45.011.9
Prime100%58.015.3
Standby25%21.05.5
Standby50%35.09.3
Standby75%50.013.1
Standby100%59.015.6

Available documents

Spec sheet — Cummins-installation-manual-DFAA-DFAB-DFAC-DFBC-DFBF-DFBD-DFBE-DFBF-DFCB-DFCC-DFCE-DFEB-DFEC-DFED-DFFA-DFFB-DFGA-DFGB-DFGC-DFJA-DFJB-DFJC-DFJD-DFLA-DFLB-DFLC-DFLD-DFLE-DFMB-DQAA-DQAB-DQBA-DQBB (Cummins/Onan)Spec sheet — cummins DFAC 250 kW 60Hz spec sheet (Cummins/Onan)Operator's manual — 960-0171 Cummins DFAB DFAC Operator's Manual (12-2012) (Cummins/Onan)Operator's manual — 960-0175 Cummins DFAB DFAC Operator's Manual (2-2013) (Cummins/Onan)Parts manual — 0932-0112 Onan Post-Sale Literature Index (07-1998) (Cummins/Onan)Parts manual — 0960-0204 (Cummins/Onan)Parts manual — 960-0260 Onan DFAA DFAB DFAC Parts Catalog (6-1997) (Cummins/Onan)Parts manual — 960-0293 Cummins DFAB DFAC Parts Manual (3-2003) (Cummins/Onan)Parts manual — 960-0298 Cummins DFAB DFAC Parts Manual (12-2012) (Cummins/Onan)Service manual — 9-3Service manual — 900-0519D Cummins DF- DQ Models Digital Paralleling (4-2005) (Cummins/Onan)Service manual — 960-0167 Cummins DFAB DFAC Operator's Manual (1-2003) (Cummins/Onan)Service manual — 960-0504 Onan DFxx series Generator Control Service Manual 04-1993 (Cummins/Onan)Service manual — 960-0507C Cummins DFAA thru DFMB DQAA Service Manual (2-2004) (Cummins/Onan)Service manual — 960-0519C Cummins DFAB DFB DFC DFG DFLC Series Service Manual (2-2004) (Cummins/Onan)Service manual — 960-0619D Cummins DFA DFB DFC DFE DFF DFG DFJ DFL DFM DQA DQB Installation (6-2003) (Cummins/Onan)Service manual — 960-0631B Cummins DFAB DFAC DFBF DFCC DFCE Installation Manual (2-2004) (Cummins/Onan)Service manual — 960-0634C Cummins DFAB DFBF DFCB DFCC DFCE Installation Manual (2-2004) (Cummins/Onan)Service manual — Cummins-3100-PowerCommand-DFAA-DFAB-DFAC-DFBC-DFBD-DFBE-DFBF-DFCB-DFCC-DFCE-DFEB-DFEC-DFED-DFFA-DFFB-DFGA-DFGB-DFGC-DFJA-DFJB-DFJC-DFJD-DFLA-DFLB-DFLC-DFLD-DFLE-DFMB-DQAA-DQAB-DQBB (Cummins/Onan)Service manual — DFxx Generator Set Service Manual PCC3100 (Cummins/Onan)Service manual — Detector Control Generator Set Service Manual (Cummins/Onan)

This page was generated from the 21 manufacturer documents above by automated extraction; every figure shown is copied from one of them. How the data is compiled.