Cummins/Onan NTA855 — Ground Fault Relay Test
Testing & diagnosis · Optional Ground Fault Alarm Relay (GFR)
For the Cummins/Onan NTA855, from the Cummins/Onan service manual.
Applies to: Cummins/Onan DFAB, Cummins/Onan DFAC, Cummins/Onan DFBF, Cummins/Onan DFCB, Cummins/Onan DFCC, Cummins/Onan DFCE, Cummins/Onan NTA855, Cummins/Onan LTA10 engine, Cummins/Onan NT855 engine, Cummins/Onan NTA855 engine
Procedure
- Verify that the N-G Fault Indicator on the GFR is not lit; if lit, the neutral-to-ground bonding jumper circuit is open.
- Move the control switch to the Run position.
- Press the TEST switch on the ground fault relay.
- Verify that the control panel warning message is displayed and the Fault Indicator (>I) on the GFR is lit.
- Reset the control panel fault, which also resets the ground fault relay.
Specs & values
- Time delay setting of zero to one second
- Current setting of 5 to 1200 amperes
Full service-parts list: Cummins/Onan DFBF →, Cummins/Onan DFCC →, Cummins/Onan DFCE →
Source: Cummins/Onan service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.