| 101 | IDLE MODE | Indicates that the engine is operating in idle mode. Grounding the engine idle input causes generator build-up to be inhibited and the engine to be governed at 800 RPM. | Warning | Remove ground from engine idle input to return to normal speed and voltage. |
| 102 | EMERGENCY STOP | Indicates local or remote Emergency Stop. | Shutdown | Turn the switch clockwise and allow it to pop out (local only). Move the Run/Off/Auto switch to Off. Press the Reset switch. Select Run or Auto, as required. |
| 1123 | SHUTDOWN AFTER BS | Shutdown fault occurred while Battle Short was enabled and then disabled. | Shutdown | Review Fault History and perform corrective action. |
| 1124 | DELAYED SHUTDOWN | Shutdown fault became active while Delayed Shutdown feature was enabled. | Warning | Review Fault History and perform corrective action. |
| 1131 | BATTLE SHORT ACTIVE | Control is in Battle Short mode. | Warning | None; used for genset operation during emergencies. |
| 121 | SPEED SIGNAL LOST | Mag pickup speed indication is not being sensed. | Shutdown | Restart and check RPM on the digital display. |
| 1311, 1312, 1317, 1318 | CUSTOMER INPUT #1 - #4 | Optional customer-selected fault input is active. | Warning | Disconnect signal lead from TB1 and reset the control; check external wiring/active input selection. |
| 1334 | CRIT SCALER OR | Incorrect feature or calibration was entered into control. | Shutdown | Reload correct feature/calibration file. |
| 1335 | NONCRIT SCALER OR | Incorrect feature or calibration was entered into control. | Warning | Reload correct feature/calibration file. |
| 135 | OIL PRESSURE SENSOR H | Engine oil pressure sender signal is shorted high. | Warning | Check sender/connectors/wires; verify fault simulation not enabled; check 0.5 to 4.5 VDC at P7-13 (OP OUT) and P7-17 (OP COM). |
| 141 | OIL PRESSURE SENSOR L | Engine oil pressure sender signal is shorted low. | Warning | Check sender/connectors/wires; check for shorts/open circuits at P7-13, 17, 21. |
| 1416 | FAIL TO SHUTDOWN | Genset continues to run after shutdown command. | Warning | Check Battle Short feature setting. |
| 1417 | POWER DOWN ERROR | Controller cannot power down. | Warning | Check for possible battery drain. |
| 143 | PRE-LOW OIL PRES | Engine oil pressure has dropped to an unacceptable level. | Warning | If critical loads, wait until next shutdown period and follow code 415. |
| 1433 | EMERGENCY STOP | Local Emergency Stop. | Shutdown | Pull the button out; move switch to O; press Fault Acknowledge/Reset; select Manual or Auto. |
| 1434 | REMOTE E-STOP | Remote Emergency Stop. | Shutdown | See code 1433 to reset. |
| 1435 | LOW COOLANT TEMP | Engine jacket water coolant temperature falls below 70°F (21°C); Warning LED illuminated (provided to meet NFPA 110 requirements) | Warning | Check the coolant heaters for proper operation |
| 1438 | FAIL TO CRANK | Engine failed to crank after the PCC received a start signal. | Shutdown | Test for B+ at the starter; check fuse F3 (2 Amps); check K4 start pilot relay and starter circuitry; refer to code 121. |
| 144 | COOL SENSOR HIGH | Engine coolant temperature signal is shorted high. | Warning | Check sender/connectors/wires; check resistance between P7-30 (IH20) and P7-34 (IH20 COM). |
| 1442 | WEAK BATTERY | During cranking battery voltage at or below weak battery trip point. | Warning | See code 441 for corrective action. |
| 1443 | BATTERY FAILED | Dead battery - engine will not start. | Shutdown | See code 441 for corrective action. |
| 1444 | KW OVERLOAD | Generator output power exceeded 105% of genset rating. | Warning | Check load and load lead connections; check CTs. |
| 1445 | SHORT CIRCUIT | Generator output current has exceeded 175% of rated. | Shutdown | Check load and load lead connections. |
| 1446 | HIGH AC VOLTAGE | Phase voltage exceeded 130% of nominal, or 110% of nominal for 10 seconds. | Shutdown | Check fault simulation; clear fault and restart; refer to Generator/Base Board Isolation Procedure. |
| 1447 | LOW AC VOLTAGE | Phase voltages dropped below 85% of nominal for 10 seconds. | Shutdown | Check overload, output terminal connections, PMG/field wiring, rectifier diodes. |
| 1448 | UNDER FREQUENCY | Engine speed dropped below 90% of nominal for 10 seconds. | Shutdown | Check fuel supply, intake air supply and load; check P8 connections. |
| 1449 | OVER FREQUENCY | Frequency is 10% above base frequency for 20 seconds. | Warning | Check fuel or air delivery; check connections. |
| 145 | COOL SENSOR LOW | Engine coolant temperature signal is shorted low. | Warning | Check sender/connectors/wires; check for shorts at P7-30 and P7-34. |
| 1452 | GEN CB NOT CLOSE | Genset circuit breaker (S2) failed to close when PTC is enabled. | Warning | Refer to Section 5. |
| 1453 | GEN CB NOT OPEN | Genset circuit breaker (S2) failed to open when PTC is enabled. | Warning | Refer to Section 5. |
| 1459 | REVERSE POWER | Improper CT phasing. | Shutdown | Check wiring to voltage sense circuit; refer to CT Installation in Section 6. |
| 146 | PRE-HIGH COOL TMP | Engine has begun to overheat. | Warning | Reduce load; check air inlets/outlets; follow code 151 if engine can be stopped. |
| 1461 | LOSS OF FIELD | Loss of field (electric) due to reverse kVAR. | Shutdown | Check field circuit. |
| 1466 | MODEM FAILURE | Control cannot communicate with the modem. | Warning | Check for open, short to ground and loose connections to the modem. |
| 1468 | NETWORK ERROR | Momentary loss of communication from the LonWorks Network. | Warning | Refer to the LonWorks Network publications. |
| 1469 | SPEED/HZ MATCH | Measured speed and measured AC output frequency do not agree. | Shutdown | Check calibration file. |
| 1471 | OVER CURRENT | Generator output current exceeded 110% of rated for 60 seconds. | Warning | Check load and load lead connections. |
| 1472 | OVER CURRENT | Output current exceeded 110% of rated and time/current calculation initiated shutdown. | Shutdown | Check load and load lead connections. |
| 151 | HIGH COOLANT TEMP | Engine has overheated above the shutdown trip point. | Shutdown | Allow engine to cool; check coolant level; check airflow obstructions; check fan belt; check blower fan/remote radiator pumps; reset control and restart. |
| 197 | LOW COOLANT LEVEL | Engine coolant level has fallen below the warning trip point. | Warning | Check coolant level and replenish if low; reset control. |
| 200 | LOW OIL PRESSURE | Indicates engine oil pressure has dropped to an unacceptable level. | Warning | If generator is powering critical loads and cannot be shut down, wait until next shutdown period and then follow 201-SHUTDOWN procedure. Access the Oil Pressure menu prior to clearing the fault. |
| 201 | LOW OIL PRESSURE | Indicates engine oil pressure has dropped below the shutdown trip point. | Shutdown | Check oil level, lines and filters; replenish if low; reset control and restart. |
| 204 | OIL PRES SENDER | Indicates that the control has sensed that the engine oil pressure sender is out of its working range. | Warning | Check that the engine oil pressure sender is properly connected. |
| 210 | LOW COOLANT TEMP | Warning occurs when engine coolant temperature is 70°F (21°C) or lower. | Warning | Warning LED illuminates. Check the coolant heaters for proper operation; if operating properly, other precautions may be necessary to warm the engine before applying a load. |
| 211 | HIGH COOLANT TEMP | Indicates the engine coolant temperature is getting close to the recommended maximum temperature limit: 215° F (102° C) − standby or 207° F (97° C) − primary. | Warning | Reduce load if possible; check air inlets and outlets and remove obstructions to airflow. |
| 212 | OIL TEMP SENSOR H | Indicates engine has overheated (coolant temperature above 215° F (102° C) − standby or 207° F (97° C) − primary). | Warning | Check sender/connectors/wires; check resistance between P7-22 (OIL TEMP) and P7-26 (OIL TEMP COM). |
| 213 | OIL TEMP SENSOR L | Resistance of the coolant temperature sender is out of range. | Warning | Check the resistance of the sender; should be 500 to 2k ohms. |
| 214 | LOW COOLANT LVL | Indicates engine coolant level has fallen below the trip point. | Warning | Check coolant level in radiator and coolant recovery bottle; replenish if low; look for leaks. |
| 215 | LOW COOLANT LVL | Indicates engine coolant level has fallen below the trip point. | Shutdown | Allow engine to cool; check coolant level and leakage points; reset control and restart. |
| 220 | MAG PICKUP | Mag pickup speed indication is not being sensed or does not match generator set output frequency. | Shutdown | Restart and check RPM; check PCC model setting; inspect and test MPU. |
| 221 | FAIL TO CRANK | Possible fault with control or starting system. | Shutdown | Check fuse F3 on the Engine Interface board. Check for poor battery cable connections; clean battery cable terminals and tighten. Recharge or replace a discharged or defective battery. |
| 222 | OVERCRANK | Possible fuel system problem. | Shutdown | Check for empty fuel tank, leaks, plugged fuel lines; replace dirty fuel or air filter; reset and restart. |
| 223 | OVERSPEED | Indicates engine has exceeded normal operating speed. (115% ±1% of nominal). | Shutdown | Check mechanical fuel linkage and actuator; check governor output module (A38) and digital board (A32). |
| 224 | FAIL TO SYNCHRONIZE | Generator set has not synchronized to the system bus within the allowable time frame. | Warning | Check governor system stability; adjust governing and synchronizer parameters; check fuel system. |
| 226 | FAIL TO CLOSE | Paralleling breaker has been given a signal to close, but has not closed properly. | Shutdown | Verify breaker charging mechanism; check close signal; verify auxiliary contact signals. |
| 230 | LOW DC VOLTAGE | Indicates battery voltage is below 10 VDC. | Warning | Recharge or replace the battery; check the battery charger fuse. Clean and tighten battery cable connections. Check engine DC alternator; replace if normal charging voltage is not obtained. Check float level if applicable. |
| 231 | HIGH DC VOLTAGE | Indicates battery voltage exceeds 32 VDC. | Warning | Lower battery charger float level if applicable; check engine DC alternator. |
| 232 | WEAK BATTERY | Indicates battery voltage drops below 60% of nominal for two seconds, during starting. | Warning | See LOW DC VOLTAGE 230. |
| 2327 | PTC FAULT | PTC module or communication link not working properly when PTC enabled. | Warning | Check blinking light on PTC module; check B+ TB3-3 to TB3-4; check PTC status voltage TB3-5 to TB3-6 (~0.2 VDC); repower control. |
| 2329 | LOW S1 FREQUENCY | Low utility (S1) frequency. | Warning | Check S1 AC inputs and wiring to PTC at TB5; check sensor set points. |
| 2331 | LOW S1 VOLTAGE | Low utility (S1) voltage. | Warning | Repower PCC 2100 control to clear; check S1 AC inputs at TB5; check S1 pickup/dropout set points. |
| 2335 | EXCITATION FAULT | Loss of all three voltage sense leads or failure in excitation circuit. | Shutdown | Check field wiring (X1 and X2) for shorts or opens. |
| 2336 | MEMORY ERROR | Control memory error; data corruption of critical operating parameters. | Shutdown | Try reloading calibration file. |
| 2337 | PWR TRAN DISABLED | PTC module available but PTC feature not enabled. | Warning | Use InPower to enable PTC feature; cycle power off for 5 seconds then repower. |
| 2338 | PWR TRAN FAILURE | PTC module trim enabled but control could not communicate with PTC module. | Warning | Check blinking light and B+ TB3-3 to TB3-4; check connections between TB2 and TB3; cycle power. |
| 2339 | PWR DOWN ENABLED | Power Down (sleep) function enabled but PTC module or network board is active. | Warning | None required. |
| 234 | OVERSPEED | Engine has exceeded normal operating speed. | Shutdown | Clear fault and restart genset; check fault threshold; monitor RPM; check electronic governor actuator. |
| 2341 | HIGH CONTROL TEMP | Control temperature above normal (158 F [70 C]) for time greater than set time. | Warning | Check genset room air flow. |
| 2342 | TOO LONG IN IDLE | Genset has been in Idle mode too long. | Warning | Exit idle mode. |
| 235 | LOW COOLANT LEVEL | Engine coolant level has fallen below the shutdown trip point. | Shutdown | Check coolant level and replenish; look for leaks; reset control and restart. |
| 2358 | HIGH S1 VOLTAGE | Utility (S1) voltage increased above the over-voltage threshold. | Warning | Measure S1 AC inputs at PTC module; check utility nominal voltage; check sensor set points. |
| 2396 | S1 CB NOT CLOSE | Utility contact (S1) failed to close with PTC enabled. | Warning | Refer to Section 5. |
| 2397 | S1 CB NOT OPEN | Utility contact (S1) failed to open with PTC enabled. | Warning | Refer to Section 5. |
| 240 | LOW FUEL−DAY | Indicates day tank fuel supply is running low. | Warning | Check fuel supply and replenish as required. |
| 241 | LOW FUEL | Low fuel signal received. | Warning | Check fuel supply and replenish; check for short to ground in external wiring. |
| 250 | EEPROM ERROR | PCC memory error; data corruption of critical operating parameters. | Shutdown | Perform initial start setup procedure; replace digital board (A32) if fault repeats. |
| 251 | EEPROM ERROR | PCC memory error; data corruption of noncritical operating parameters. | Warning | Perform adjustment and calibration procedures; replace digital board (A32) if fault repeats. |
| 252 | EEPROM ERROR | PCC memory error; data corruption of noncritical operating parameters. | Warning | Verify selected values; repeat save operation; replace digital board (A32) if fault repeats. |
| 260 | CUSTOMER FAULT 1 | When a customer defined input is closed to ground, the corresponding fault message is displayed. Default message; editable for customer site requirements. | Warning | Isolate source of false signal; repair external wiring or replace A34. |
| 261 | GROUND FAULT | When a customer defined input is closed to ground, the corresponding fault message is displayed. Default message; editable for customer site requirements. | Warning | Isolate source of false signal; repair external wiring or replace A34. |