Specifications
| Fuel | Diesel |
|---|---|
| Frequency | 60.0 Hz |
| Standby power | 230 kW |
| Standby kVA | 288 |
| Prime power | 210 kW |
| Controller | Detector, PowerCommand, PowerCommand 2100, PowerCommand 3100 |
| Oil capacity | 36.0 L |
| Voltage options | 110/190 V, 115/200 V, 120/208 V, 120/240 V, 127/220 V, 139/240 V, 220/380 V, 240/416 V, 254/440 V, 277/480 V, 347/600 V |
| Phase | 3 |
| Battery group | 8D |
| Battery cranking | 1400 CCA |
| Battery voltage | 24 V |
| Battery quantity | 2 |
| Coolant capacity | 49 L |
| Max ambient | 50 °C |
| Dimensions (L×W×H) | 3404×1270×1617 mm |
| Dry weight | 2676 kg |
| Wet weight | 2762 kg |
Filters for the Cummins/Onan LTA10
6Engine-mounted filters the filter manufacturers list for this engine family. These come from the engine, not from this generator set’s own parts list, so confirm against your serial number before ordering.
| System | Filter | Description | Cross-references | |
|---|---|---|---|---|
| Oil filter | P550777 | Lube Filter, Spin-On Bypass | CUMMINS 3021658, CUMMINS 33004232, NAPA 1749, BALDWIN B7577 | FridayParts $43.56 |
| Oil filter | P551670 | Lube Filter, Spin-On Full Flow | CUMMINS 298670, CUMMINS 299670, NAPA 1970, CARBOCOL 0026 | FridayParts $26.68 |
| Fuel filter | P550105 | Fuel Filter, Spin-On Primary | CUMMINS 154700, CUMMINS 154710, NAPA 3109, NAPA 3405 | buy |
| Fuel / water separator | P558000 | Fuel Filter, Water Separator Spin-On Twist&Drain | CUMMINS 3308638, CUMMINS 3308683, NAPA 3405, NAPA 3693 | KuduParts $24.00 FridayParts $25.66 |
| Fuel / water separator | P550106 | Fuel Filter, Water Separator Spin-On | CUMMINS 154789, CUMMINS 156164, NAPA 3405, BALDWIN BF957-D | FridayParts $285.60 |
| Coolant filter | P554071 | Coolant Filter, Spin-On | CUMMINS 209604, CUMMINS 209606, NAPA 4071, WALGAHN-MOTORENTECHN 00811412 | FridayParts $397.60 |
Same engine, other brands
1 brandThe Cummins/Onan LTA10 in this set also powers 2 generator sets sold under 1 other brand. Service parts and maintenance intervals for the engine are shared; enclosure, alternator, controller and ratings are not.
| Brand | Models |
|---|---|
| AKSA | AC250, AC275 |
Maintenance & consumables
for the Cummins/Onan LTA10| Item | Spec | Capacity | Part # | Interval | |
|---|---|---|---|---|---|
| Air filter | — | ||||
| Fuel filter | Direct injection, number 2 diesel fuel; fuel filter; automatic electric fuel shutoff | — | |||
| Oil filter | — | 268 hr | |||
| Battery | Two 12V Group 8D batteries | — | |||
| Belt | — | ||||
| Coolant | -50 | 49.0 | — | ||
| Oil | 36.0 L | — | |||
| Spark plug | — |
Service intervals
1| Item | Action | Hours | Months | Notes |
|---|---|---|---|---|
| Rupture basin leak detect switch | Test | 12 mo | Some areas may require weekly inspections by safety code. |
Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.
Service specifications
60| Type | Item | Value | Unit | Condition |
|---|---|---|---|---|
| Clearance | Angular alignment T.I.R. limit | not more than .001 | in per inch of radius | center of shaft to indicator axis |
| Clearance | Angular alignment maximum T.I.R. | 0.001 | inch per inch of radius (center of shaft to indicator axis) | measuring deflection to bolt heads |
| Clearance | Float switch assembly float lift clearance below C-clip stop | 1/8 | inch (3 mm) | use a feeler gauge |
| Clearance | Generator-to-engine angular alignment (T.I.R.) | .001 in. per inch of radius (center of shaft to indicator axis), maximum | in | 750 kW gensets and larger |
| Clearance | MPU sensor to gear tooth adjustment | back out one quarter turn | turn | after contacting gear tooth |
| Clearance | Vibration isolator base elevation difference | 0.25 | inch (6 mm) | all isolator bases within this elevation of each other |
| Clearance | Vibration isolator clearance between top plate and base | 0.25 | inch (6 mm) | nominal or greater |
| Clearance | Vibration isolator top plate to base clearance | 0.25 | inch (6 mm) | nominal, or greater |
| Gap | Angular alignment total indicator reading (T.I.R.) | 0.001 | inch per inch of radius | maximum |
| Gap | Float switch lift to test open | 1/8 | inch | below C-clip stop |
| Gap | MPU sensor to flywheel ring gear tooth | back it out one quarter turn | turn | sensor threaded in until it just touches gear tooth |
| Other | AVR Droop setting | 5 | % at full load, 0 PF | |
| Other | AVR voltage regulation (load regulation) | approximately ±0.5 | % RMS | |
| Other | Angular alignment maximum T.I.R. | .001 | inch per inch of radius | center of shaft to indicator axis |
| Other | Angular alignment maximum T.I.R. | .001 inches per inch of radius | in/in | center of shaft to indicator axis |
| Other | Battery specific gravity (high ambient, above 95F/35C) | 1.225 | recommended to reduce electrolyte loss | |
| Other | Battery specific gravity (recharge threshold) | below 1.260 | ||
| Other | Battery specific gravity, fully charged | approximately 1.260 | specific gravity | at 80 F (27 C) |
| Other | Fuel lift height limit | 6 | feet | (1.8 meters) between fuel lift pump and bottom of dip tube |
| Other | GOV GAIN default value for paralleling applications | 70 | % | |
| Other | Maximum cranking voltage drop | 2 | volts | difference between battery and starter terminals while cranking |
| Other | Over/Under Frequency Sensor Module - Over Hz Set, 50 Hz nominal | 55 | Hz | reset 53 Hz |
| Other | Over/Under Frequency Sensor Module - Over Hz Set, 60 Hz nominal | 65 | Hz | reset 63 Hz |
| Other | Over/Under Frequency Sensor Module - Under Hz Set, 50 Hz nominal | 45 | Hz | reset 47 Hz |
| Other | Over/Under Frequency Sensor Module - Under Hz Set, 60 Hz nominal | 55 | Hz | reset 57 Hz |
| Other | Over/Under Voltage Sensor Module time delay | typically 25 percent, approximately 2.5 | seconds | |
| Other | Overcrank cranking limit | 75 | seconds | three 15-second cranking cycles with two 15-second rest periods |
| Other | Overcurrent shutdown threshold | 110% of rated | % of rated | PCC time/current calculation |
| Other | Overcurrent warning threshold | 110% of rated for 60 seconds | % of rated | generator output current |
| Other | Overload warning threshold | 105% of standby or 115% of prime | % of rating | three-phase power output; load dump after five seconds, warning after 60 seconds |
| Other | REG VHZ (underfrequency roll-off) adjustable range | 1 through 50; normal range 7 through 21 | ||
| Other | Short circuit shutdown threshold | 175% of rated | % of rated | generator output current |
| Other | Start delay adjustment range | 0 to 300 | seconds | |
| Other | Stop delay adjustment range | 0 to 600 | seconds | |
| Other | Under Frequency Roll Off (UFRO) knee point, 50 Hz units | 48 to 49 | Hz | |
| Other | Under Frequency Roll Off (UFRO) knee point, 60 Hz units | 58 to 59 | Hz | |
| Other | Under-frequency roll-off threshold (UFRO) | typically 59 Hz for 60 Hz applications and 49 Hz for 50 Hz applications | Hz | AVR UFRO pot preset |
| Other | Weak battery warning threshold | below 60% of nominal for two seconds | % of nominal | during starting |
| Pressure | Engine oil pressure - K19 normal | 50-70 | psi (345-482 kPa) | run mode |
| Pressure | Engine oil pressure - K38 normal | 45-65 | psi (310-448 kPa) | run mode |
| Pressure | Engine oil pressure - K50 normal | 50-70 | psi (345-482 kPa) | run mode |
| Pressure | Engine oil pressure - L10/M11 normal | 30-50 | psi (207-345 kPa) | run mode |
| Pressure | Engine oil pressure - NTA 855 normal | 35-50 | psi (241-345 kPa) | run mode |
| Pressure | Engine oil pressure - V28 normal | 50-90 | psi (345-620 kPa) | run mode |
| Pressure | Engine oil pressure shutdown limit - L10/M11 | 20 | psi (138 kPa) | run mode value |
| Pressure | Engine oil pressure shutdown limit - L10/M11 | 8 | psi (55 kPa) | idle mode value |
| Pressure | Engine oil pressure warning limit - L10/M11 | 12 | psi (83 kPa) | idle mode value |
| Pressure | Engine oil pressure warning limit - L10/M11 | 25 | psi (172 kPa) | run mode value |
| Pressure | K19 engine idle oil pressure | 20 | psi (138 kPa) | idle |
| Pressure | K19 engine normal oil pressure | 50-70 | psi (345-482 kPa) | normal run |
| Pressure | K19 normal oil pressure (run/idle) | 50-70 / 20 | psi (345-482 / 138 kPa) | NORM run / IDLE |
| Pressure | K19 oil pressure shutdown limit | 10 | psi (69 kPa) | idle mode |
| Pressure | K19 oil pressure shutdown limit | 35 | psi (241 kPa) | run mode |
| Pressure | K19 oil pressure shutdown/warning limits | shutdown 35 psi (241 kPa) run; warning 40 psi (276 kPa) run; shutdown 10 psi (69 kPa) idle; warning 15 psi (103 kPa) idle | psi (kPa) | |
| Pressure | K19 oil pressure warning limit | 15 | psi (103 kPa) | idle mode |
| Pressure | K19 oil pressure warning limit | 40 | psi (276 kPa) | run mode |
| Pressure | K38 engine idle oil pressure | 20 | psi (138 kPa) | idle |
| Pressure | K38 engine normal oil pressure | 45-65 | psi (310-448 kPa) | normal run |
| Pressure | K38 normal oil pressure (run/idle) | 45-65 / 20 | psi (310-448 / 138 kPa) | NORM run / IDLE |
| Pressure | K38 oil pressure shutdown limit | 10 | psi (69 kPa) | idle mode |
Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.
Recommended fluids
| Fluid | Grade | Standard | Ambient | Capacity | Notes |
|---|---|---|---|---|---|
| Coolant | soft water / E.G. / DCA mixture | Cooling system to be filled with soft water/E.G./DCA mixture (on-site review checklist). | |||
| Coolant | NFPA 110 | above 4°C | NFPA 110 recommends engine jacket water coolant heaters where minimum ambient is above 40°F (4°C); coolant maintained at minimum 90°F (32°C). Cooling system capacity with standard radiator: DFAB/DFAC 13 Gal (49 L); DFBF 13.5 Gal (51 L); DFCC 13.5 Gal (51 L); DFCE 15 Gal (57 L). | ||
| Fuel | ASTM No. 2 diesel | Cummins engine Operation and Maintenance Manual alternate diesel fuels | Cummins engines normally use ASTM No. 2 diesel fuel. Never use galvanized or copper fuel lines, fittings or fuel tanks. | ||
| Fuel | ASTM No. 2 diesel fuel | ASTM No. 2 | Cummins engines normally use ASTM No. 2 diesel fuel; they will operate on alternate diesel fuels within the specifications shown in the Cummins engine Operation and Maintenance Manual. Never use galvanized or copper fuel lines, fittings or fuel tanks. | ||
| Fuel | Diesel | Day tank fuel transfer pump maintains reservoir of diesel fuel in the day tank. | |||
| Fuel | Number 2 diesel fuel | ||||
| Grease | Lithium based grease | Mobilux No. 2 or Shell Alvania R3 | 2.74 oz (81 ml) | Generator end bearing. Temperature range -22F to +248F (-30C to +120C). Grease should be equally divided between the bearing, bearing cap cavity, and bearing cartridge cavity. | |
| Grease | Lithium based | -30°C to 120°C | 81.0 ml | Mobilux No. 2 or Shell Alvania R3; generator end bearing; temperature range -22 F to +248 F (-30 C to +120 C); grease divided between bearing, bearing cap cavity and cartridge cavity. | |
| Grease | Lithium based grease, Mobilux No. 2 or Shell Alvania R3 | -30°C to 120°C | 2.74 oz (81 ml) | End bearing lubricant; grease equally divided between bearing, bearing cap cavity and bearing cartridge cavity. |
Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.
Fault codes
80| Code | Name | Meaning | Severity | Action |
|---|---|---|---|---|
| 101 | IDLE MODE | Indicates that the engine is operating in idle mode (governed at 800 RPM, generator build-up inhibited). | Warning | Remove ground from engine idle input to return to normal speed and voltage. |
| 102 | EMERGENCY STOP | Indicates local or remote Emergency Stop. | Shutdown | Turn the switch clockwise and allow it to pop out (local only). Move the Run/Off/Auto switch to Off. Press the Reset switch. Select Run or Auto, as required. |
| 121 | SPEED SIGNAL LOST | Mag pickup speed indication is not being sensed. | Shutdown | Restart and check RPM on the digital display. |
| 135 | OIL PRESSURE SENSOR H | Engine oil pressure sender signal is shorted high. | Warning | Check sender/connectors/wires. |
| 141 | OIL PRESSURE SENSOR L | Engine oil pressure sender signal is shorted low. | Warning | Check sender/connectors/wires. |
| 143 | PRE-LOW OIL PRES | Engine oil pressure has dropped to an unacceptable level. | Warning | If critical loads, wait until next shutdown period and follow code 415. |
| 144 | COOL SENSOR HIGH | Engine coolant temperature signal is shorted high. | Warning | Check sender/connectors/wires. |
| 145 | COOL SENSOR LOW | Engine coolant temperature signal is shorted low. | Warning | Check sender/connectors/wires. |
| 146 | PRE-HIGH COOL TMP | Engine has begun to overheat. | Warning | Reduce load; check air inlets/outlets; follow code 151 if engine can be stopped. |
| 151 | HIGH COOLANT TEMP | Engine has overheated above the shutdown trip point. | Shutdown | Allow cool down; check coolant level, cooling airflow, fan belt, blower fan and circulation pumps. |
| 197 | LOW COOLANT LEVEL | Engine coolant level has fallen below the warning trip point. | Warning | Check coolant level and replenish if low; reset control. |
| 200 | LOW OIL PRESSURE | Indicates engine oil pressure has dropped to an unacceptable level. | Warning | If generator is powering critical loads and cannot be shut down, wait until next shutdown period and then follow 201-SHUTDOWN procedure. Access the Oil Pressure menu prior to clearing the fault. |
| 201 | LOW OIL PRESSURE | Indicates engine oil pressure has dropped below the shutdown trip point. | Shutdown | Check oil level, lines and filters. If oil system is OK but oil level is low, replenish. Reset control and restart. Oil pressure limits are listed in Table 4-3. |
| 204 | OIL PRES SENDER | Indicates that the control has sensed that the engine oil pressure sender is out of its working range. | Warning | Check that the engine oil pressure sender is properly connected. |
| 210 | LOW COOLANT TEMP | Set is not operating. Warning occurs when engine coolant temperature is 70° F (21° C) or lower. | Warning | Indicates engine coolant heater is not operating or is not circulating coolant. Check coolant heater power supply, low coolant level, and heater element current draw. |
| 211 | HIGH COOLANT TEMP | Indicates the engine coolant temperature is getting close to the recommended maximum temperature limit: 215° F (102° C) − standby or 207° F (97° C) − primary. | Warning | Reduce load if possible by turning off non-critical loads. Check air inlets and outlets and remove any obstructions to airflow. If engine can be stopped, follow 212-SHUTDOWN procedure. |
| 212 | HIGH COOLANT TEMP | Indicates engine has overheated (coolant temperature above 215° F (102° C) − standby or 207° F (97° C) − primary). | Shutdown | Allow engine to cool down completely. Check for obstructions to cooling airflow; check fan belt; check coolant mixture; check blower fan and circulation pumps on remote radiator installations. Reset control and restart. |
| 213 | COOLANT SENDER | Indicates that the resistance of the coolant temperature sender is out of range. | Warning | Check the resistance of the sender. Resistance should be 500 to 2k ohms. |
| 214 | LOW COOLANT LVL | Indicates engine coolant level has fallen below the trip point. | Warning | Allow engine to cool down completely. Check coolant level in both radiator and coolant recovery bottle and replenish if low. Look for coolant leakage points and repair if necessary. |
| 215 | LOW COOLANT LVL | Indicates engine coolant level has fallen below the trip point. | Shutdown | Allow engine to cool down completely. Check coolant level in both radiator and coolant recovery bottle and replenish if low. Reset control and restart after correcting problem. Shutdown will not occur if genset is in Idle mode (low coolant warning only). |
| 220 | MAG PICKUP | Indicates mag pickup speed indication is not being sensed or does not match generator set output frequency. | Shutdown | Restart and check RPM on the digital display. |
| 221 | FAIL TO CRANK | Indicates possible fault with control or starting system. | Shutdown | Check fuse F3 on the Engine Interface board. Check for poor battery cable connections; clean battery cable terminals and tighten. Recharge or replace a discharged or defective battery. |
| 222 | OVERCRANK | Indicates possible fuel system problem. | Shutdown | Check for empty fuel tank, fuel leaks, or plugged fuel lines. Check for dirty fuel filter and replace if necessary. Check for dirty or plugged air filter and replace if necessary. Reset the control and restart after correcting the problem. |
| 223 | OVERSPEED | Engine has exceeded normal operating speed (115% ±1% of nominal). | Shutdown | Check mechanical fuel linkage and actuator; check governor output module (A38) and digital board (A32). |
| 224 | FAIL TO SYNCHRONIZE | Generator set has not synchronized to the system bus within the allowable time frame. | Warning | Check governor system stability; adjust governing and synchronizer parameters; check fuel system. |
| 226 | FAIL TO CLOSE | Paralleling breaker has been given a signal to close, but has not closed properly. | Shutdown | Verify breaker charging mechanism; check close signal; verify auxiliary contact signals. |
| 230 | LOW DC VOLTAGE | Indicates battery voltage is below 10 VDC. | Warning | Recharge or replace the battery; check the battery charger fuse. Clean and tighten battery cable connections. Check engine DC alternator; replace if normal charging voltage is not obtained. Check float level if applicable. |
| 231 | HIGH DC VOLTAGE | Indicates battery voltage exceeds 32 VDC. | Warning | Check float level on battery charger if applicable (lower float level). Check engine DC alternator; replace if normal battery charging voltage is not obtained. |
| 232 | WEAK BATTERY | Indicates battery voltage drops below 60% of nominal for two seconds, during starting. | Warning | Discharged or defective battery. See Warning message 230, LOW DC VOLTAGE. |
| 234 | OVERSPEED | Engine has exceeded normal operating speed. | Shutdown | Check for large block load removal, flammable vapors or leaking turbocharger seals. |
| 235 | LOW COOLANT LEVEL | Engine coolant level has fallen below the shutdown trip point. | Shutdown | Check coolant level and replenish if low; reset control. |
| 240 | LOW FUEL−DAY | Indicates day tank fuel supply is running low. | Warning | Check fuel supply and replenish as required. |
| 241 | LOW FUEL | Indicates day tank fuel supply is running low. | Warning | Check fuel supply and replenish as required. |
| 250 | EEPROM ERROR | PCC memory error; data corruption of critical operating parameters. | Shutdown | Perform initial start setup procedure; replace digital board (A32) if fault repeats. |
| 251 | EEPROM ERROR | PCC memory error; data corruption of noncritical operating parameters. | Warning | Perform adjustment and calibration procedures; replace digital board (A32) if fault repeats. |
| 252 | EEPROM ERROR | PCC memory error; data corruption of noncritical operating parameters. | Warning | Verify selected values; repeat save operation; replace digital board (A32) if fault repeats. |
| 260 | CUSTOMER FAULT 1 | When a customer defined input is closed to ground, the corresponding fault message is displayed. Default message; editable for customer site requirements. | Warning | Fault functions can be programmed to initiate a shutdown or a warning. |
| 261 | GROUND FAULT | When a customer defined input is closed to ground, the corresponding fault message is displayed. Default message; editable for customer site requirements. | Warning | Fault functions can be programmed to initiate a shutdown or a warning. |
| 262 | RUPTURE BASIN | When a customer defined input is closed to ground, the corresponding fault message is displayed. Default message; editable for customer site requirements. | Warning | Fault functions can be programmed to initiate a shutdown or a warning. |
| 263 | HIGH GEN TEMP | When a customer defined input is closed to ground, the corresponding fault message is displayed. Default message; editable for customer site requirements. | Warning | Fault functions can be programmed to initiate a shutdown or a warning. |
| 270 | PHASE ROTATION | The phase relationship between the generator set and the system bus is not matched. | Shutdown | Verify genset phase rotation matches bus; verify control wiring to bus PT module. |
| 272 | FIRST START | PowerCommand control is not receiving a proper signal from the system master first start sensor. | Warning | Verify Master First Start Sensor and interconnection wiring. |
| 301 | HIGH AC VOLTAGE | One or more phase voltages exceeded 130% of nominal, or exceeded 110% of nominal for 10 seconds. | Shutdown | Check PCC, alternator, excitation circuit, and PT/CT module wiring. |
| 303 | LOW AC VOLTAGE | One or more phase voltages dropped below 85% of nominal for 10 seconds. | Shutdown | Check PMG/field wiring, rotating rectifier, load and connectors. |
| 313 | UNDER FREQUENCY | Indicates that engine speed has dropped below 90% of nominal for 10 seconds. Five seconds before shutdown, a Load Dump signal is initiated. | Shutdown | Check fuel supply, intake air supply and load. |
| 320 | OVERCURRENT | Indicates that generator output current has exceeded 110% of rated for 60 seconds. | Warning | Check load and load lead connections. |
| 321 | OVERCURRENT | Indicates that generator output current has exceeded 110% of rated, and that a PCC time/current calculation has initiated an overcurrent shutdown. | Shutdown | Check load and load lead connections. |
| 322 | SHORT CIRCUIT | Indicates that generator output current has exceeded 175% of rated. | Shutdown | Check load and load lead connections. |
| 330 | OVERLOAD | Indicates that three-phase power output exceeds 105% of standby (or 115% of prime) rating. After five seconds, the Load Dump output is activated. After 60 seconds, the OVERLOAD warning is activated. | Warning | Check load and load lead connections. |
| 335 | REVERSE POWER | Indicates improper CT or PT phasing. (Non-parallel units only.) | Shutdown | Check CT / PT wiring. Refer to CT Installation in Section 5. |
| 337 | LOSS OF EXCITATION | Alternator excitation system is improperly adjusted or has failed. | Shutdown | Check output voltage calibration, load sharing lines, and leading power factor loads. |
| 359 | FAIL TO START | Engine cranks but fails to start after last crank time. | Shutdown | Check fuel tank, leaks, fuel lines, fuel filter, air filter; check fuel solenoid and actuator. |
| 415 | LOW OIL PRESSURE | Engine oil pressure has dropped below the shutdown trip point. | Shutdown | Check oil level, lines and filters; replenish if low; reset control. |
| 421 | OIL TEMP | Engine oil temperature has exceeded the warning threshold. | Warning | Reduce load; check air inlets/outlets; check engine oil level. |
| 441 | LOW BAT VOLTAGE | Battery voltage supply to the control is approaching a low level. | Warning | Recharge or replace battery; check charger fuse, connections and DC alternator. |
| 442 | HIGH BAT VOLTAGE | Battery voltage supply is approaching a high level. | Warning | Check battery charger float level; check battery wiring/calibration. |
| 1123 | SHUTDOWN AFTER BS | Shutdown fault occurred while Battle Short was enabled and then disabled. | Shutdown | Review Fault History and perform corrective action. |
| 1124 | DELAYED SHUTDOWN | Shutdown fault became active while Delayed Shutdown feature was enabled. | Warning | Review Fault History and perform corrective action. |
| 1131 | BATTLE SHORT ACTIVE | Control is in Battle Short mode. | Warning | Bypasses several critical fault shutdowns for emergency operation. |
| 1311, 1312, 1317, 1318 | CUSTOMER INPUT #1 - #4 | Optional customer-selected fault input is active. | Warning | Check external wiring and active input (closed/open) selection. |
| 1334 | CRIT SCALER OR | Incorrect feature or calibration entered into control. | Shutdown | Reload correct calibration. |
| 1335 | NONCRIT SCALER OR | Incorrect feature or calibration entered into control. | Warning | Reload correct calibration. |
| 1416 | FAIL TO SHUTDOWN | Genset continues to run after shutdown command. | Warning | Check Battle Short feature enabled condition. |
| 1417 | POWER DOWN ERROR | Controller cannot power down. | Warning | Check for possible battery drain. |
| 1433 | EMERGENCY STOP | Local Emergency Stop. | Shutdown | Pull button out; move switch to O; press Fault Acknowledge/Reset; select Manual or Auto. |
| 1434 | REMOTE E-STOP | Remote Emergency Stop. | Shutdown | See code 1433 to reset. |
| 1435 | Engine Cold | Engine jacket water coolant temperature falls below 70°F (21°C); Warning LED illuminated (provided to meet NFPA 110 requirements) | Warning | Check the coolant heaters for proper operation |
| 1438 | FAIL TO CRANK | Engine failed to crank after PCC received a start signal. | Shutdown | Check starter, fuse F3, K4 relay, E-Stop switch and MPU circuit. |
| 1442 | WEAK BATTERY | Battery voltage at or below weak battery warning trip point during cranking. | Warning | See code 441 for corrective action. |
| 1443 | BATTERY FAILED | Dead battery - engine will not start. | Shutdown | See code 441 for corrective action. |
| 1444 | KW OVERLOAD | Generator output power exceeded 105% of genset rating. | Warning | Check load and load lead connections; check CTs. |
| 1445 | SHORT CIRCUIT | Generator output current has exceeded 175% of rated. | Shutdown | Check load and load lead connections. |
| 1446 | HIGH AC VOLTAGE | One or more phase voltages exceeded 130% of nominal. | Shutdown | Check fault simulation, load removal, threshold settings, Base board/generator. |
| 1447 | LOW AC VOLTAGE | Phase voltages dropped below 85% of nominal for 10 seconds. | Shutdown | Check overload, output terminal connections, PMG/field wiring, rectifier diodes. |
| 1448 | UNDER FREQUENCY | Engine speed dropped below 90% of nominal for 10 seconds. | Shutdown | Check fuel supply, intake air supply and load. |
| 1449 | OVER FREQUENCY | Frequency is 10% above base frequency for 20 seconds. | Warning | Check fuel or air delivery; check connections. |
| 1452 | GEN CB NOT CLOSE | Genset circuit breaker (S2) failed to close when PTC is enabled. | Warning | Refer to Section 5 troubleshooting charts. |
| 1453 | GEN CB NOT OPEN | Genset circuit breaker (S2) failed to open when PTC is enabled. | Warning | Refer to Section 5 troubleshooting charts. |
| 1459 | REVERSE POWER | Improper CT phasing. | Shutdown | Check wiring to voltage sense circuit; refer to CT Installation in Section 6. |
| 1461 | LOSS OF FIELD | Loss of field (electric) due to reverse kVAR. | Shutdown | Check excitation circuit. |
Showing the first 80 of 125 codes.
Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.
Procedures
12Adjust Start/Stop Delays (PCC Adjust Menu) adjustment
⚠ Electrostatic discharge will damage circuit boards. Always wear a grounding wrist strap when working inside control box.
- Press the button next to ADJUST in the Main Menu; the VOLTAGE submenu appears.
- Press the button next to >> to move through VOLTAGE and FREQUENCY to the START DELAY submenu.
- Use the buttons next to the up and down symbols to set the start delay.
- Press >> to move to the STOP DELAY submenu and set the stop delay.
- Press >> to move to the IDLE SPEED submenu and set idle speed (only in idle mode).
- Press >> to move to SAVE/EXIT; select SAVE then EXIT to return to Main menu.
Adjusting Values/Parameters (PCC Adjust Menu) adjustment
- Press the button next to the arrow symbol in the display until the + and - symbols are displayed.
- If necessary, press the button next to the arrows to move to the numeric character to change.
- Press + to increase the value or select the parameter; press - to decrease the value or select the parameter.
- Press the save symbol to save changes; changes are not saved if Home or Previous Main Menu is pressed first.
Aligning Generator with Engine (Angular Alignment) adjustment
⚠ Accidental starting of the generator set during this procedure presents the hazard of severe personal injury or death.
Tools: Dial indicator, Shims
- Disconnect the negative (-) battery cable(s) before beginning.
- Fasten a dial indicator to the generator shaft or cooling fan with the sensing point on the capscrew head or flat surface of the drive disc at the bolt circle diameter.
- Bar the engine over in a clockwise rotation as viewed from engine flywheel; do not allow it to roll back on compression.
- Determine the total indicator reading (T.I.R.) as the sum of the maximum positive and negative dial indicator readings over one revolution.
- Measure the distance from the center of the generator shaft to the indicator measuring point.
- Measure the distance from the generator side of the flex discs to the center of the generator mounting bolt.
- Compare the distances; multiply this ratio times one half the T.I.R. to approximate the amount of shims to remove or add.
Angular Alignment Procedure adjustment
⚠ Accidental starting of the generator set during this procedure presents the hazard of severe personal injury or death. Make sure to disconnect the negative (-) battery cable(s) before beginning.
Tools: Dial indicator, Wooden shims
- Disconnect the negative (-) battery cable(s) before beginning.
- Fasten a dial indicator to the generator shaft or cooling fan with sensing point on capscrew head or flat surface of drive disc at bolt circle diameter.
- Bar the engine over in a clockwise rotation as viewed from engine flywheel; do not allow it to roll back on compression.
- Record maximum positive and negative dial indicator readings as the engine completes one revolution.
- T.I.R. equals the sum of the maximum positive and negative readings.
- Maximum T.I.R. should not be more than .001 inch for each inch of radius.
- Remove equal shims from under both generator mounting feet to lower the generator.
Angular Alignment Procedure (750 kW Gensets and Larger) adjustment
⚠ Accidental starting of the generator set during this procedure presents the hazard of severe personal injury or death. Make sure to disconnect the negative (-) battery cable(s) before beginning.
⚠ Do not bar engine over by prying on fan blade.
Tools: Dial indicator, Shims
- Disconnect the negative (-) battery cable(s) before beginning.
- Fasten a dial indicator to the generator shaft or cooling fan, with the sensing point on the capscrew head or drive disc flat surface at bolt circle diameter.
- Bar the engine over clockwise as viewed from the engine flywheel; do not allow it to roll back on compression.
- Total indicator reading (T.I.R.) is the sum of the maximum positive and negative readings as the engine completes one revolution.
- To lower the generator, remove equal shims from under both generator mounting feet; approximate shim amount from the distance ratio.
Angular Alignment Procedure (Generator to Engine) adjustment
⚠ Accidental starting during this procedure presents the hazard of severe personal injury or death.
⚠ Do not bar engine over by prying on fan blade.
Tools: dial indicator
- Disconnect the negative (-) battery cable(s) before beginning.
- Fasten a dial indicator to the generator shaft or cooling fan with sensing point resting on the drive disc capscrew head/flat surface at the bolt circle diameter.
- Bar the engine over in a clockwise rotation as viewed from the engine flywheel; do not allow it to roll back on compression at the end of travel of each reading.
- Record the total indicator reading (T.I.R.) as the sum of the maximum positive and negative dial indicator readings over one engine revolution.
- Compare the measured T.I.R. to the maximum allowed (.001 in. per inch of radius from center of shaft to indicator axis); add or remove shims under the generator mounting feet to correct.
Axial Alignment Procedure adjustment
Tools: Dial indicator, Magnetic base or clamp
- Check axial alignment only when an objectionable vibration is present after angular alignment.
- Fasten dial indicator holding device to skid base, engine block, or generator shell with a magnetic base or clamp; rest sensor on generator shaft hub.
- Bar the engine over clockwise through a couple of rotations; record indicator readings at eight equally spaced points around the shaft diameter.
- To correct out-of-tolerance T.I.R., remove the drive disc capscrews, mark discs and flywheel, rotate 180 degrees from original location, retorque, and recheck.
- If unchanged, rotate the discs to 30, 60 or 90 degrees from their original location.
Axial Alignment Procedure (Generator to Engine) adjustment
Tools: dial indicator
- Fasten a dial indicator holding device to the skid base, engine block, or generator shell with the sensor point resting on the generator shaft hub.
- Bar the engine over in a clockwise rotation through a couple of rotations, recording indicator readings at eight equally spaced points around the shaft diameter to obtain axial T.I.R.
- Reduce the measured T.I.R. runout by one half if excessive vibration remains after angular alignment.
Governor Calibration Checks adjustment
Tools: Frequency meter or tachometer, Jumper wire
- Start the generator set.
- Adjust engine no-load speed to the desired allowable speed droop using the Run Speed potentiometer.
- With no load, turn GAIN clockwise slowly until engine speed oscillates.
- Reduce GAIN slowly counterclockwise until engine speed is stable.
- Upset the governor by momentarily shorting terminals 7 and 10 on the governor control.
- Apply and remove loads to check generator set response.
HC4-7 Axial Alignment Procedure adjustment
Tools: Dial indicator with magnetic base or clamp
- Check only when an objectionable vibration is present.
- Fasten dial indicator holding device to skid base, engine block, or generator shell with magnetic base or clamp.
- Position sensor point on the generator shaft hub.
- Bar the engine over in a clockwise rotation as viewed from engine flywheel through a couple of rotations.
- Record indicator readings in eight equally spaced points around the shaft diameter.
- Remove the capscrews connecting drive discs and flywheel and mark discs and flywheel.
- Rotate engine or generator so drive disc holes are repositioned 180 degrees from original location.
- Put capscrews back in and retorque. Recheck shaft alignment.
- If runout unchanged, rotate discs to 30, 60 or 90 degrees from original location.
- If T.I.R. does not improve, inspect flywheel pilot and drive disc runouts.
P7 Axial Alignment Procedure adjustment
- Check only when an objectionable vibration is present.
- Remove the capscrews connecting drive discs and flywheel.
- Mark the drive discs and flywheel with respect to each other.
- Rotate engine or generator so drive discs holes are repositioned two bolt holes from original location.
- Put capscrews back in and retorque. Recheck/record vibration levels.
- Repeat this test until drive disc holes are repositioned 180 degrees from original location.
- Review vibration data and position drive disc in lowest recorded level location.
UFRO Adjustments adjustment
⚠ Use an insulated handle screw driver to prevent electrical shock.
Tools: Insulated handle screwdriver, Frequency meter or tachometer
- Make a note of the no-load frequency.
- Determine roll-off frequency by turning the governor speed pot until the LED lights; if okay go to step 5.
- Adjust the governor speed pot to the proper roll-off frequency.
- Turn the UFRO pot until LED goes off, then slowly turn it back until the LED just goes on.
- Adjust the governor speed pot back to the initial frequency setting.
Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.
Voltage reconnection
| Voltage | Phase | Connection | Leads | Notes |
|---|---|---|---|---|
| 12 lead generator sets | Load wires are routed through the CTs | Reconnectable gensets (12 leads) have dual secondary CTs (3 pins); CT wire 2/3 to pin 2 (high voltage) or pin 3 (low voltage). | ||
| 6 lead generator sets | Generator output leads are routed through the CTs | Non-reconnectable gensets (6 leads) have single secondary CTs (2 pins). | ||
| Cummins PowerCommand generic AC Reconnect Wiring Diagram 625-2755 (Rev. D) and 625-3100 (Rev. F) | Applies to models DFAA, DFAB, DFAC, DFBF, DFCB, DFCC, DFEB, DFEC, DFFB, DFGA, DFGB, DFJA, DFJB, DFJC, DFJD, DFLB, DFLC, DFLD, DFMB (625-2755) and models DFAA-DFMB plus DFCE, DFED, DQAA, DQAB, DQBA, DQBB (625-3100). | |||
| Current transformers CT21-U load leads (A phase), CT22-V load leads (B phase), CT23-W load leads (C phase) | CT secondary wire marked 1 to pin 1; wire marked 2/3 to pin 2 for high voltage gensets or pin 3 for low voltage gensets | CT dot must face toward the generator; CTs have dual secondaries (3 pins). | ||
| Generator load terminals stamped U, V, W and N (U=L1, V=L2, W=L3, N=L0) | Stranded load wires bolted to generator reconnection terminal block or circuit breaker lugs | Available generator output voltages and maximum current ratings are specified on the generator set nameplate; line-to-neutral is the lower voltage, line-to-line the higher. Reconnection diagram is located on the upper side cover of the control housing. | ||
| A | CT21 – U load leads | A phase | CT dot must face the generator; CT terminal 1 connects to metering circuit; terminal 2/3 connects to ground. | |
| A (U) | Bus PT module TB1 A | bus A phase | Bus PT module A39. | |
| A (U) | CT21 | U load leads (A phase) | CT dot must face the generator; CT terminal 1 connects to metering circuit, terminal 2/3 to ground. | |
| B | CT22 – V load leads | B phase | CT dot must face the generator; CT terminal 1 connects to metering circuit; terminal 2/3 connects to ground. | |
| B (V) | Bus PT module TB1 B | bus B phase | Bus PT module A39. | |
| B (V) | CT22 | V load leads (B phase) | CT dot must face the generator; terminal 1 to metering circuit, terminal 2/3 to ground. | |
| C | CT23 – W load leads | C phase | CT dot must face the generator; CT terminal 1 connects to metering circuit; terminal 2/3 connects to ground. | |
| C (W) | Bus PT module TB1 C | bus C phase | Bus PT module A39. | |
| C (W) | CT23 | W load leads (C phase) | CT dot must face the generator; terminal 1 to metering circuit, terminal 2/3 to ground. | |
| N | Bus PT module TB1 N | bus neutral | Bus PT module A39. | |
| 110 V - 120 V L-N | 1 | Single phase, 2-wire | PTC module jumper locations | |
| 190 V - 240 V L-L | 3 | Three phase | Use PTC module 0300-5382-01; 50/60 Hz | |
| 200 V - 240 V L-L | 1 | Single phase, 3-wire | PTC module jumper locations | |
| 380 V - 600 V L-L | 3 | Three phase | Use PTC module 0300-5382-02; 50/60 Hz | |
| high voltage genset | 12-lead CT secondary wire marked 2/3 to pin 2 | 2/3 | For high voltage gensets. | |
| low voltage genset | 12-lead CT secondary wire marked 2/3 to pin 3 | 2/3 | For low voltage gensets. |
Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.
Common questions
What is the power rating of the Cummins/Onan DFAB?
The Cummins/Onan DFAB is rated 230 kW standby (288.0 kVA).
What engine does the Cummins/Onan DFAB use?
The Cummins/Onan DFAB is powered by the Cummins/Onan LTA10 engine.
What fuel does the Cummins/Onan DFAB use?
The Cummins/Onan DFAB runs on Diesel.
What is the oil capacity of the Cummins/Onan DFAB?
The Cummins/Onan LTA10 engine in the Cummins/Onan DFAB has an oil capacity of 36.0 liters.
What is the cooling system capacity of the Cummins/Onan DFAB?
The Cummins/Onan DFAB cooling system holds 49 liters (12.9 US gallons) for the radiator system including the engine, per the manufacturer specification sheet.
What is the prime power rating of the Cummins/Onan DFAB?
The Cummins/Onan DFAB is rated 210 kW prime (263 kVA), against 230 kW standby.
What is the dry weight of the Cummins/Onan DFAB?
The Cummins/Onan DFAB has a dry weight of 2676 kg (5899 lb).
What voltages is the Cummins/Onan DFAB available in?
The Cummins/Onan DFAB is offered in 110/190 V, 115/200 V, 120/208 V, 120/240 V, 127/220 V, 139/240 V, 3-phase.
What battery does the Cummins/Onan DFAB use?
The Cummins/Onan DFAB uses 2 batteryies, 24 V each, 1400 CCA, group 8D, per the manufacturer specification sheet.
Troubleshooting
6Fault codes
| Code | Meaning | Cause | Remedy |
|---|---|---|---|
| 101 | IDLE MODE — WARNING; Engine continues to operate at reduced RPM. | Indicates that the engine is operating in idle mode. When the set is operating in the RUN mode, grounding the engine idle input causes generator build-up to be inhibited and the engine to be governed at 800 RPM. | When ground is removed from this input, the set returns to normal speed and voltage. When the engine idle function is enabled, the control automatically sets lower oil pressure warning and shutdown trip points to reflect the lower operating speed. When the engine idle function is removed and the set reverts to normal operating speed, the control automatically resets oil pressure warning and shutdown trip points to the normal settings. |
| 102 | EMERGENCY STOP — SHUTDOWN; Engine shuts down and will not crank. | Indicates local or remote Emergency Stop. | To reset the local Emergency Stop button: Pull the button out or turn the switch clockwise (button with arrow) and allow it to pop out; Move the Run/Off/Auto switch to Off; Press the Reset switch; Select Run or Auto, as required. |
| 200 | LOW OIL PRESSURE — WARNING | Indicates engine oil pressure has dropped to an unacceptable level. | If generator is powering critical loads and cannot be shut down, wait until next shutdown period then follow 201 Low Oil Pressure procedure. If engine can be stopped, follow 201 procedure. To check oil pressure, access Oil Pressure menu prior to clearing the fault. |
Symptoms & remedies
| Symptom | Cause | Remedy |
|---|---|---|
| Control does not power up when the Run/Off/Auto switch is set to Run or the Self Test switch is pressed. | There is no DC power to the control. | Check for battery disconnected, discharged, or improperly connected; Fuse F1 (20A/32V, Type 3AG) may be open. Replace with the same type. (Fuse is mounted near engine starter/solenoid, see Figure 4-2); Contact an authorized service center. |
| Warning, Shutdown, and Non-Automatic lamps are not lit. Digital display shows main menu or selected menu. | Indicates all engine systems are normal. | No corrective action required. |
| Non-Automatic lamp flashes. | Indicates Run/Off/Auto switch is not in the Auto position. This will prevent automatic starting if an automatic transfer switch is used. | Move the Run/Off/Auto switch to the Auto position for automatic operation. |
Fault codes and symptom→remedy steps extracted from this model’s service/owner documentation; verify against the official manual before servicing. Full Cummins/Onan DFAB troubleshooting guide (148 entries) →
Repair guides
12- Adjust Start/Stop Delays (PCC Adjust Menu)
- Adjusting Values/Parameters (PCC Adjust Menu)
- Angular Alignment Procedure (750 kW Gensets and Larger)
- Axial Alignment Procedure
- Battery Connections (Prestart)
- Fuel Pump Control AC Connections (240 VAC / 120 VAC Conversion)
- Fuel Pump Control AC Connections (240 VAC to 120 VAC)
- Generator Set Grounding Procedure
- Ground Fault Relay Test
- Megger and PI Test
- Vibration Isolators Installation and Adjustment
- Vibration Isolators Installation and Adjustment Procedure
Step-by-step procedures compiled from the Cummins/Onan service manual for this model.
Parts
12| Part # | Description | Qty | System | |
|---|---|---|---|---|
| 0300-4623-05 | DFAA (600V) | 1 | Current transformer | Amazon eBay |
| 0300-4623-06 | DFAB (600V) | 1 | Current transformer | Amazon eBay $153.95 |
| 0300-4623-07 | DFAC (600V) | 1 | Current transformer | Amazon eBay |
| 0300-4623-17 | DFAA BR (0-480V) | 1 | Current transformer | Amazon eBay $165.95 |
| 0300-4623-19 | DFAB BR (0-480V) | 1 | Current transformer | Amazon eBay |
| 0300-4623-21 | DFAC BR (0-480V) | 1 | Current transformer | Amazon eBay |
| 960-0167 | Battery, Group Number: 8D, CCA (minimum): 1400, Cold Soak® -40°F (-40°C) | 2 | Battery | Amazon eBay |
| A40-TB1-2 | SWITCHED B+ | Belt | Amazon eBay | |
| A40-TB1-4 | GROUND | Belt | Amazon eBay | |
| A40-TB1-7 | COMMON ALARM | Belt | Amazon eBay | |
| A40-TB1-8 | JUMPER WIRE | Belt | Amazon eBay | |
| LF3000 | Lube, Spin-On | 1 | Oil filter | Amazon eBay $76.00 NAPA $66.59 |
Service, wear & replacement parts referenced for this model and its engine — confirm the exact part for your serial number. See the full parts catalog to search and cross-reference.
Fuel consumption
| Rating | Load | L/h | gal/h |
|---|---|---|---|
| Prime | 25% | 19.0 | 4.9 |
| Prime | 50% | 30.0 | 8.0 |
| Prime | 75% | 42.0 | 11.2 |
| Prime | 100% | 54.0 | 14.3 |
| Standby | 25% | 20.0 | 5.2 |
| Standby | 50% | 33.0 | 8.7 |
| Standby | 75% | 46.0 | 12.1 |
| Standby | 100% | 59.0 | 15.6 |