The PowerCommand 2100 is a generator-set controller. It is used on generator sets from Cummins/Onan, including the 100 GGHH, 1100DFLB, 1120 DFLC and 125 GGHJ.
Also fitted to: Cummins/Onan ESG-642, Cummins/Onan GGHG/GGHH.
| Code | Meaning | Cause | Remedy |
|---|---|---|---|
| 10 | Incorrect main fuel valve adjustment. | Refer to Gaseous Fuel Adjustment (Type A or B) in Section 6. | |
| 101 | Engine continues to operate at reduced RPM. | Indicates that the engine is operating in idle mode. When the set is operating in the RUN mode, grounding the engine idle input causes generator build-up to be inhibited and the engine to be governed at 800 RPM. When ground is removed from this input, the set returns to normal speed and voltage. | |
| 102 | Engine shuts down and will not crank. | Indicates local or remote Emergency Stop. | To reset the local Emergency Stop button: Pull the button out or turn the switch clockwise (button with arrow) and allow it to pop out. Move the Run/Off/Auto switch to Off. Press the Reset switch. Select Run or Auto, as required. |
| 11 | Incorrect secondary regulator adjustment. | Refer to Initial Secondary Regulator Adjustment in Section 6. | |
| 1123 | Shutdown After Battle Short | ||
| 1124 | Delayed Shutdown | ||
| 1131 | Battle Short Active | ||
| 121 | Speed Signal Lost | ||
| 1244 | Engine Normal Shutdown | ||
| 1245 | CAN - Engine Shutdown | ||
| 1246 | CAN - Unknown Engine Fault | ||
| 1247 | CAN - Engine Unannounced Fault | ||
| 1248 | CAN - Engine Warning Fault | ||
| 1311 | Customer Input #1 | ||
| 1311 | Customer Inputs #1 | ||
| 1312 | Customer Input #2 | ||
| 1312 | Customer Inputs #2 | ||
| 1317 | Customer Input #3 | ||
| 1317 | Customer Inputs #3 | ||
| 1318 | Customer Inputs #4 | ||
| 1318 | Service Engine Fault | ||
| 1334 | Crit Scaler OR | ||
| 1335 | Non-Crit Scaler OR | ||
| 135 | Oil Pressure Sensor High | ||
| 141 | Oil Pressure Sensor Low | ||
| 1416 | Fail To Shut Down | ||
| 1416 | Fail to Shutdown | ||
| 1417 | Power Down Failure | ||
| 143 | Pre-Low Oil Pressure Sensor | ||
| 1433 | Emergency Stop | ||
| 1434 | Remote Emergency Stop | ||
| 1435 | Low Coolant Temperature | ||
| 1437 | FAULT HISTORY: 1 OF 24 CNTL HOURS 459 OCCURRENCES 5 ENGINE HOURS 334 | ||
| 1438 | Fail to Crank | ||
| 144 | Coolant Temperature Sensor High | ||
| 1442 | Weak Battery | ||
| 1443 | Battery Failed | ||
| 1444 | KW Overload | ||
| 1445 | Short Circuit | ||
| 1446 | High AC Voltage | ||
| 1447 | Low AC Voltage | ||
| 1448 | Under Frequency | ||
| 1449 | Over Frequency | ||
| 145 | Coolant Temperature Sensor Low | ||
| 146 | HIGH COOLANT TEMP WARNING | A. Reduce load if possible by turning off non-critical loads. b. Check air inlets and outlets and remove any obstructions to airflow. If engine can be stopped, follow 151 High Coolant Temp Alarm procedure. | |
| 146 | Pre-High Cool Temp | ||
| 1461 | Loss of Field | ||
| 1466 | Modem Failure | ||
| 1468 | Network Error | ||
| 1469 | Speed/Hz Match | ||
| 1471 | Over Current | ||
| 1472 | Over Current | ||
| 151 | HIGH COOLANT TEMP ALARM | A. Check jacket water coolant level and replenish if low. Look for coolant leakage and repair if necessary. b. Check for obstructions to cooling airflow and correct as necessary. c. Check fan belt and repair if necessary. d. Reset control and restart after locating and correcting problem. | |
| 151 | High Coolant Temp | ||
| 152 | LOW COOLANT TEMP | A. Coolant heater not connected to power supply. Check for blown fuse or disconnected heater cord and correct as required. b. Check for low jacket water coolant level and replenish if required. Look for possible coolant leakage points and repair as required. | |
| 197 | COOLANT LEVEL WARNING | A. Check jacket water coolant level and replenish if low. Look for possible coolant leakage points and repair if necessary. b. Reset control and restart after locating and correcting problem. | |
| 197 | Low Coolant Level | ||
| 200 | Indicates engine oil pressure has dropped to an unacceptable level. | If generator is powering critical loads and cannot be shut down, wait until next shutdown period then follow 201 Low Oil Pressure procedure. If engine can be stopped, follow 201 procedure. To check oil pressure, access Oil Pressure menu prior to clearing the fault. | |
| 200 | LOW OIL PRESSURE | Shutdown | |
| 201 | Engine oil pressure has dropped below the shutdown trip point. | Check oil level, lines and filters. If oil system is OK but oil level is low, replenish. Reset control and restart. |