Specifications
| Fuel | Diesel |
|---|---|
| Frequency | 60.0 Hz |
| Standby power | 230 kW |
| Standby kVA | 288 |
| Prime power | 209 kW |
| Emissions | EPA Tier 3 |
| Controller | PowerCommand 2100, PowerCommand 2100 (PCC) |
| Oil capacity | 26.5 L |
| Alternator | Stamford/AvK UCDI274K |
| Voltage options | 120/208 V, 120/240 V, 127/220 V, 139/240 V, 220/380 V, 240/416 V, 254/440 V, 277/480 V, 347/600 V, 120/241 V |
| Phase | 3 |
| Rated current | 346 A |
| Power factor | 0.8 |
| Circuit breaker | 400 A |
| Battery voltage | 12 V |
| Coolant capacity | 29.5 L |
| Max ambient | 52 °C |
| Dimensions (L×W×H) | 2667×1016×1372 mm |
| Wet weight | 1561 kg |
| Sound level | 96.0 dBA @ 7 m |
| Tank runtime | 24 hr |
Engine
| Oil capacity | 26.5 L |
|---|---|
| Coolant capacity | 29.5 L |
| Displacement | 8.9 L |
| Aspiration | Turbocharged and CAC |
| Rated speed | 1800 rpm |
Maintenance & consumables
for the Cummins/Onan QSL9-G2 NR3| Item | Spec | Capacity | Part # | Interval | |
|---|---|---|---|---|---|
| Air filter | Dry replaceable element | — | |||
| Fuel filter | Single element, 10 micron filtration, spin-on fuel filter with water separator | — | |||
| Oil filter | Last changed 1/8/26, 45HRS | — | |||
| Battery | group 24 | ×2 | — | ||
| Coolant | -40 | 29.5 | — | ||
| Oil | 26.5 L | — |
Service specifications
60| Type | Item | Value | Unit | Condition |
|---|---|---|---|---|
| Other | Alternator cooling air flow | 41.3 | m3/min | |
| Other | Alternator excitation current - full load | 2.2 | amps | |
| Other | Alternator excitation current - no load | 0.5 | amps | |
| Other | BMEP at set rated load (Prime) | 1816 | kPa (263 psi) | prime rating |
| Other | BMEP at set rated load (Standby) | 1979 | kPa (287 psi) | standby rating |
| Other | Combustion air flow - standby | 20.9 | m3/min | standby rating |
| Other | Compression ratio | 16.8:1 | ||
| Other | Cooling system air flow | 248 | m3/min | standard set-mounted radiator |
| Other | Cycle cranking - number of starting cycles | 1 to 7 | cycles | |
| Other | Exhaust flow at set rated load - standby | 33.3 | m3/min | standby rating |
| Other | Fault current regulation (max output current on any phase under fault) | 3 | times rated current | single and three phase faults |
| Other | Frequency regulation | Isochronous | ||
| Other | Full load acceptance - frequency dip / recovery time | 12.6% / 3.7 | % / seconds | NFPA 110 single step load |
| Other | Full load acceptance - voltage dip / recovery time | 29.1% / 3.2 | % / seconds | NFPA 110 single step load |
| Other | Full load rejection - frequency rise / recovery time | 3.9% / 2.9 | % / seconds | load rejection |
| Other | Full load rejection - voltage rise / recovery time | 18.4% / 1.5 | % / seconds | load rejection |
| Other | Governor regulation class | ISO 8528 Part 1 Class G3 | ||
| Other | Ground fault warning (optional) sensing range | 100-1200 | amps, time delay 0-1 s | 600 VAC class, solid ground |
| Other | Maximum surge power | 233 | kW | PTS test |
| Other | Motor starting kVA at 90% sustained voltage - PMG excitation | 920 | kVA | PTS test |
| Other | Motor starting kVA at 90% sustained voltage - shunt excitation | 770 | kVA | PTS test |
| Other | Over current shutdown (51) | >110 and <175 | % of rating | |
| Other | Over current warning | >110 for >60 s, or >400 for >1 s | % of rating | |
| Other | Over frequency shutdown/warning (81o) | 0-10 | Hz above nominal, 0-20 s time delay | default disabled |
| Other | Over load (kW) warning default | 105 | % of rated kW, 60 s delay | range 50-140%, 0-120 s |
| Other | Random frequency variation | ± 0.25 | % | |
| Other | Reverse Var shutdown default | 0.2 | per unit, 10 s delay | threshold 0.15-0.50, delay 10-60 s |
| Other | Reverse power shutdown (32) default | 10 | % of standby kW rating, 3 s delay | range 5-20%, delay 1-15 s |
| Other | Short circuit shutdown | >175 | % of rating | |
| Other | Time delay start | 0-300 | seconds | default 0 s |
| Other | Time delay stop (cool down) | 0-600 | seconds | default 0 s |
| Other | Total heat rejection - standby | 7.8 | MJ/min | standby rating |
| Other | Under frequency shutdown (81u) default | 6 | Hz below nominal, 10 s time delay | adjustable 0-10 Hz, 0-20 s |
| Pressure | BMEP at set rated load - prime | 1816 | kPa | prime rating |
| Pressure | BMEP at set rated load - standby | 1979 | kPa | standby rating |
| Pressure | Maximum air cleaner restriction with clean filter | 3.7 | kPa (15 in H2O) | |
| Pressure | Maximum back pressure | 10.2 | kPa (41.0 in H2O) | |
| Pressure | Maximum cooling air flow static restriction | 0.12 | kPa (0.5 in H2O) | |
| Pressure | Maximum exhaust back pressure | 10.2 | kPa | |
| Pressure | Maximum fuel inlet restriction | 152.4 | mm Hg | |
| Pressure | Maximum fuel return restriction | 254.0 | mm Hg | |
| Pressure | Maximum inlet restriction | 152.4 | mm Hg (6.0 in Hg) | |
| Pressure | Maximum return restriction | 254.0 | mm Hg (10.0 in Hg) | |
| Resistance | Alternator rotor resistance | 2.0 | ohms | at 20 deg C |
| Resistance | Alternator stator resistance | 0.0128 | ohms per phase | at 20 deg C |
| Speed | Alternator maximum speed | 2250 | rpm | |
| Speed | Engine overspeed limit | 2100 +/- 50 | rpm | |
| Speed | Isochronous governing, steady state load no load to full load | +/-0.25 | % | |
| Speed | Over speed shutdown (default setting) | 115 | % of nominal | |
| Speed | Overspeed limit | 2100 ± 50 | rpm | |
| Speed | Overspeed shutdown default | 115 | % of nominal | |
| Speed | Piston speed | 8.7 | m/s (1707.0 ft/min) | 1800 rpm |
| Speed | Random frequency variation (PTS test) | +/-0.25 | % | |
| Speed | Rated speed | 1800 | rpm | |
| Temperature | Battery charger ambient temperature operation at full rated output | -20 to 45 | deg C | full rated output |
| Temperature | Control operating ambient temperature range | -40 to +70 | deg C | |
| Temperature | Cooling system ambient design - prime | 48 | deg C | standard set-mounted radiator, non-seismic |
| Temperature | Cooling system ambient design - standby | 52 | deg C | standard set-mounted radiator, non-seismic |
| Temperature | Exhaust temperature | 600 | °C (1110 °F) | standby at set rated load |
| Temperature | Exhaust temperature (Prime) | 572 | °C (1063.0 °F) | set rated load |
Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.
Recommended fluids
| Fluid | Grade | Standard | Ambient | Capacity | Notes |
|---|---|---|---|---|---|
| Fuel | Number 2 diesel fuel | Direct injection fuel system; fuel filter with water separator |
Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.
Fault codes
7| Code | Name | Meaning | Severity | Action |
|---|---|---|---|---|
| - | Reverse Var shutdown | Shutdown level adjustable: threshold 0.15-0.50 per unit, delay 10-60 seconds. | Shutdown | Defaults 0.20, 10 seconds. |
| 27 | Low AC voltage shutdown | Voltage on any phase has dropped below a preset value; adjustable 50-95% of reference voltage, time delay 2-10 s; default 85% for 10 seconds | Shutdown | Default 85% for 10 seconds; function tracks reference voltage. |
| 32 | Reverse power shutdown | Adjustment range 5-20% of standby kW rating, delay 1-15 seconds; default 10%, 3 seconds | Shutdown | Defaults 10%, 3 seconds. |
| 51 | Over current shutdown | Output current on any phase more than 110%, less than 175% of rating and approaching thermal damage point of alternator. | Shutdown | Control includes algorithms to protect alternator from repeated over current conditions over a short period. |
| 59 | High AC voltage shutdown | Output voltage on any phase exceeds preset values; time to trip inversely proportional to amount above threshold. Adjustable 105-125% of nominal, time delay 0.25-10 s. | Shutdown | Default 110% for 10 seconds. |
| 81o | Over frequency shutdown/warning | Adjustable 0-10 Hz above nominal frequency, time delay 0-20 seconds. | Defaults: disabled. | |
| 81u | Under frequency shutdown | Generator set output frequency cannot be maintained; adjustable 0-10 Hz below nominal governor set point, 0-20 s delay. | Shutdown | Default 6 Hz, 10 seconds. |
Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.
Procedures
1Circuit breaker catalog number lookup operation
⚠ If the first 3 letters are PJP, start the search with PJ only.
⚠ If the catalog number starts with N, skip the N and begin the search with the second letter.
- Locate the circuit breaker feature code or part number.
- Use the charts to find the corresponding manufacturer circuit breaker catalog number.
- Use the first letter of the catalog number to determine the breaker frame (if first letter is N, use the second letter).
- Follow the corresponding website link to find the breaker catalog number description.
- Search the catalog using the first 3 letters and first 5 numbers of the breaker catalog number.
Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.
Voltage reconnection
| Voltage | Phase | Connection | Leads | Notes |
|---|---|---|---|---|
| 120/208 | 3 | three phase reconnectable | 12 | |
| 120/208 thru 139/240 | three phase | Broad range | 12 | 150 deg C rise rating 230 kW / 288 kVA per ADS-212 |
| 120/240 | 1 | single phase non-reconnectable | 4 | Double delta, 4 lead |
| 120/240 | single phase | Double delta | 4 | 125 deg C rise rating 175/219 kW/kVA; 105 deg C rise rating 157/196 kW/kVA |
| 120/241 | 1 | single phase non-reconnectable | ||
| 127/220 | 1 | single phase non-reconnectable | ||
| 139/240 | 1 | single phase non-reconnectable | ||
| 220/380 | 3 | three phase reconnectable | 12 | |
| 240/416 | 3 | three phase reconnectable | 12 | |
| 240/416 thru 277/480 | three phase | Broad range | 12 | 150 deg C rise rating 255 kW / 319 kVA |
| 254/440 | 3 | three phase reconnectable | 12 | |
| 277/480 | 3 | three phase reconnectable | 12 | |
| 347/600 | 3 | three phase reconnectable | 12 | Lower broad range |
| 347/600 | three phase | Upper broad range (LBR) | 6 | 150 deg C rise rating 230 kW / 288 kVA; lower broad range 110/190 thru 120/208, 220/380 thru 240/416 |
Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.
Common questions
What is the power rating of the Cummins/Onan DSHAD?
The Cummins/Onan DSHAD is rated 230 kW standby (288.0 kVA).
Which engine powers the Cummins/Onan DSHAD?
The Cummins/Onan DSHAD is powered by the Cummins/Onan QSL9-G2 NR3 engine.
What kind of fuel does the Cummins/Onan DSHAD run on?
The Cummins/Onan DSHAD runs on Diesel.
What is the oil capacity of the Cummins/Onan DSHAD?
The Cummins/Onan QSL9-G2 NR3 engine in the Cummins/Onan DSHAD has an oil capacity of 26.5 liters.
What is the coolant capacity of the Cummins/Onan DSHAD?
The Cummins/Onan DSHAD cooling system holds 29.5 liters (7.8 US gallons) for the radiator system including the engine, per the manufacturer specification sheet.
What is the continuous rating of the Cummins/Onan DSHAD?
The Cummins/Onan DSHAD is rated 209 kW prime (261 kVA), against 230 kW standby.
How loud is the Cummins/Onan DSHAD?
The Cummins/Onan DSHAD is rated at 96.0 dBA at 7 m, per the manufacturer specification sheet.
What voltages is the Cummins/Onan DSHAD available in?
The Cummins/Onan DSHAD is offered in 120/208 V, 120/240 V, 127/220 V, 139/240 V, 220/380 V, 240/416 V, 3-phase.
What alternator comes on the Cummins/Onan DSHAD?
The Cummins/Onan DSHAD uses a Stamford/AvK UCDI274K alternator.
Troubleshooting
6Fault codes
| Code | Meaning |
|---|---|
| CODE 197/235 | LOW COOLANT LEVEL (WARNING/SHUTDOWN) |
| CODE 427 | CAN DATALINK LOST MESSAGES (WARNING) |
| CODE 441 | LOW BATTERY VOLTAGE (WARNING) |
| CODE 442 | HIGH BATTERY VOLTAGE (WARNING) |
| CODE 781 | CAN DATALINK FAILED (SHUTDOWN) |
| CODE 1245 | CAN ENGINE SHUTDOWN (SHUTDOWN) |
Fault codes and symptom→remedy steps extracted from this model’s service/owner documentation; verify against the official manual before servicing. Full Cummins/Onan DSHAD troubleshooting guide (70 entries) →
Fuel consumption
| Rating | Load | L/h | gal/h |
|---|---|---|---|
| Prime | 25% | 22.0 | 5.8 |
| Prime | 50% | 38.0 | 10.1 |
| Prime | 75% | 52.0 | 13.8 |
| Prime | 100% | 64.0 | 17.0 |
| Standby | 25% | 23.0 | 6.2 |
| Standby | 50% | 41.0 | 10.8 |
| Standby | 75% | 57.0 | 14.7 |
| Standby | 100% | 69.0 | 18.2 |
Available documents
This page was generated from the 5 manufacturer documents above by automated extraction; every figure shown is copied from one of them. How the data is compiled.