| Other | Alternator cooling air flow | 41.3 | m3/min | |
| Other | Alternator excitation current - full load | 2.2 | amps | |
| Other | Alternator excitation current - no load | 0.5 | amps | |
| Other | BMEP at set rated load (Prime) | 1816 | kPa (263 psi) | prime rating |
| Other | BMEP at set rated load (Standby) | 1979 | kPa (287 psi) | standby rating |
| Other | Combustion air flow - standby | 20.9 | m3/min | standby rating |
| Other | Compression ratio | 16.8:1 | | |
| Other | Cooling system air flow | 248 | m3/min | standard set-mounted radiator |
| Other | Cycle cranking - number of starting cycles | 1 to 7 | cycles | |
| Other | Exhaust flow at set rated load - standby | 33.3 | m3/min | standby rating |
| Other | Fault current regulation (max output current on any phase under fault) | 3 | times rated current | single and three phase faults |
| Other | Frequency regulation | Isochronous | | |
| Other | Full load acceptance - frequency dip / recovery time | 12.6% / 3.7 | % / seconds | NFPA 110 single step load |
| Other | Full load acceptance - voltage dip / recovery time | 29.1% / 3.2 | % / seconds | NFPA 110 single step load |
| Other | Full load rejection - frequency rise / recovery time | 3.9% / 2.9 | % / seconds | load rejection |
| Other | Full load rejection - voltage rise / recovery time | 18.4% / 1.5 | % / seconds | load rejection |
| Other | Governor regulation class | ISO 8528 Part 1 Class G3 | | |
| Other | Ground fault warning (optional) sensing range | 100-1200 | amps, time delay 0-1 s | 600 VAC class, solid ground |
| Other | Maximum surge power | 233 | kW | PTS test |
| Other | Motor starting kVA at 90% sustained voltage - PMG excitation | 920 | kVA | PTS test |
| Other | Motor starting kVA at 90% sustained voltage - shunt excitation | 770 | kVA | PTS test |
| Other | Over current shutdown (51) | >110 and <175 | % of rating | |
| Other | Over current warning | >110 for >60 s, or >400 for >1 s | % of rating | |
| Other | Over frequency shutdown/warning (81o) | 0-10 | Hz above nominal, 0-20 s time delay | default disabled |
| Other | Over load (kW) warning default | 105 | % of rated kW, 60 s delay | range 50-140%, 0-120 s |
| Other | Random frequency variation | ± 0.25 | % | |
| Other | Reverse Var shutdown default | 0.2 | per unit, 10 s delay | threshold 0.15-0.50, delay 10-60 s |
| Other | Reverse power shutdown (32) default | 10 | % of standby kW rating, 3 s delay | range 5-20%, delay 1-15 s |
| Other | Short circuit shutdown | >175 | % of rating | |
| Other | Time delay start | 0-300 | seconds | default 0 s |
| Other | Time delay stop (cool down) | 0-600 | seconds | default 0 s |
| Other | Total heat rejection - standby | 7.8 | MJ/min | standby rating |
| Other | Under frequency shutdown (81u) default | 6 | Hz below nominal, 10 s time delay | adjustable 0-10 Hz, 0-20 s |
| Pressure | BMEP at set rated load - prime | 1816 | kPa | prime rating |
| Pressure | BMEP at set rated load - standby | 1979 | kPa | standby rating |
| Pressure | Maximum air cleaner restriction with clean filter | 3.7 | kPa (15 in H2O) | |
| Pressure | Maximum back pressure | 10.2 | kPa (41.0 in H2O) | |
| Pressure | Maximum cooling air flow static restriction | 0.12 | kPa (0.5 in H2O) | |
| Pressure | Maximum exhaust back pressure | 10.2 | kPa | |
| Pressure | Maximum fuel inlet restriction | 152.4 | mm Hg | |
| Pressure | Maximum fuel return restriction | 254.0 | mm Hg | |
| Pressure | Maximum inlet restriction | 152.4 | mm Hg (6.0 in Hg) | |
| Pressure | Maximum return restriction | 254.0 | mm Hg (10.0 in Hg) | |
| Resistance | Alternator rotor resistance | 2.0 | ohms | at 20 deg C |
| Resistance | Alternator stator resistance | 0.0128 | ohms per phase | at 20 deg C |
| Speed | Alternator maximum speed | 2250 | rpm | |
| Speed | Engine overspeed limit | 2100 +/- 50 | rpm | |
| Speed | Isochronous governing, steady state load no load to full load | +/-0.25 | % | |
| Speed | Over speed shutdown (default setting) | 115 | % of nominal | |
| Speed | Overspeed limit | 2100 ± 50 | rpm | |
| Speed | Overspeed shutdown default | 115 | % of nominal | |
| Speed | Piston speed | 8.7 | m/s (1707.0 ft/min) | 1800 rpm |
| Speed | Random frequency variation (PTS test) | +/-0.25 | % | |
| Speed | Rated speed | 1800 | rpm | |
| Temperature | Battery charger ambient temperature operation at full rated output | -20 to 45 | deg C | full rated output |
| Temperature | Control operating ambient temperature range | -40 to +70 | deg C | |
| Temperature | Cooling system ambient design - prime | 48 | deg C | standard set-mounted radiator, non-seismic |
| Temperature | Cooling system ambient design - standby | 52 | deg C | standard set-mounted radiator, non-seismic |
| Temperature | Exhaust temperature | 600 | °C (1110 °F) | standby at set rated load |
| Temperature | Exhaust temperature (Prime) | 572 | °C (1063.0 °F) | set rated load |