Cummins/Onan V-10 WSG-1068 Engine

The Cummins/Onan V-10 WSG-1068 is an engine. It powers generator sets from Cummins/Onan, including the GGHE, GGHF, GGHG and GGHH. It holds 6.2 L (1.6 gal) of oil and 33.1 L (8.7 gal) of coolant.

Also known as: Onan Modified Ford V-10 WSG-1068

Part of the Cummins/Onan V-10 engine family — 2 variants share parts & fitment.

6.2 L
Oil capacity

Engine specifications

Oil capacity6.2 L
Coolant capacity33.1 L

Common problems

15
  • Over Current 1471
  • Low Coolant Level 197
  • Weak Battery Code 1442
    Fix: Indicates that during cranking, the battery voltage is at or below the weak battery warning trip point for a time greater than or equal to the weak battery set time. See code 441 for corrective action.
  • Under Frequency Code 1448
    Fix: Indicates possible fuel system problem or overload condition. 1. Check for dirty or plugged air filter and replace if necessary (see Maintenance section). 2. Check operation by disconnecting load and restarting generator set. 3. Fuel system requires adjustment. Contact an authorized service center for service. 4. Fuel delivery to the set is inadequate. Contact an authorized service center for service. 5. Reset the control and restart after correcting the problem.
  • Too Long in Idle Code 2342
    Fix: Indicates the generator set has been in Idle mode too long (10 minutes maximum).
  • Fail To Crank Code 1438
    Fix: Indicates possible fault with control, speed sensing or starting system. See code 441 for corrective action.
  • Emergency Stop Code 1433
    Fix: Indicates local Emergency Stop. To reset the local/remote Emergency Stop button: 1. Pull the button out. 2. Move the O/Manual/Auto switch to O. 3. Press the front panel Fault Acknowledge/Reset button. 4. Select Manual or Auto, as required.
  • Battery Failed Code 1443
    Fix: Dead battery - engine will not start. See code 441 for corrective action.
  • There is no remote circuit signal (12 VDC at auxiliary relay board A28-TB1-6) because the remote circuit is not functioning properly.
    Fix: Apply 12 VDC to A28-TB1-6. If the engine cranks, find and repair the fault in the remote control circuit. See Section 7 for remote connections.
  • There is no remote circuit signal (12 VDC at auxiliary relay board A28-TB1-6) because fuse F3 on the ECM has blown. a
    Fix: A. Replace the fuse with one of the same type and amp rating (15 A).<br>b. If fuse F3 blows again, find and repair the fault in the remote control circuit, such as a loose wire that may be shorting to ground or a shorted relay coil or other component. See Section 7 for remote connections.
  • The starter disconnects normally but neither the panel nor the remote Run indicator lamps light
    Cause: AC (K10) starter disconnect circuit is not working
  • The Run-Stop-Remote switch is at Stop. (The Switch-Off light will be flashing.)
    Fix: Push the Run-Stop-Remote switch to Remote.
  • The magnetic speed pick-up is defective or requires adjustment. 9
    Fix: Refer to Magnetic Speed Pickup Unit Adjustment in Section 6.
  • The grounding strap between the control box and the battery negative (−) terminal or the ground wire between the control and engine ground is loose, damaged or missing
    Fix: Check for continuity (zero ohms) between the grounding stud on the bottom of the control box and the battery negative (−) terminal. If there is no continuity or the grounding strap is loose or damaged, repair as necessary.
  • The engine runs until fault shutdown.
    Fix: 1. The OVERSPEED lamp comes on and the engine shuts down. a. Reset the ECM by pushing the Run-Stop-Remote switch to Stop and the Reset switch to Reset and restart the set, monitoring engine speed. b. Adjust the governor for Type A fuel system/check operation of Type B integrated governor (see Section 6). c. Type A: If the governor cannot be adjusted to prevent shutdown due to overspeed, check for binding in the linkage. Repair and adjust the linkage as necessary. d. Type A and B: If the set still shuts down due to overspeed, re-install the magnetic speed pick-up unit to make sure the clearance with the flywheel gear teeth is correct (see Section 6). Replace the speed-pickup unit if output voltage at cranking speed is less than 1.5 VAC. (Intermittent open on magnetic speed pick-up lead can also cause an overspeed condition.) e. Replace the governor controller board (Type A) or integrated governor assembly (Type B) if the set still shuts down due to overspeed. 2a. The OVERSPEED lamp comes on and the engine shuts down within 1 to 5 seconds (no over-speed condition detected). (V6 Spec A & B, V10 Spec A−C) a. Remove K5-30 lead from K5. Start genset. If set shuts down and overspeed light is on, replace ECM (A11). b. Remove K5-30 lead from K5 and check lead continuity to ground. If ground present, replace ignition module. c. Connect K5-30. Remove lead K5-87 and check lead continuity to ground. If ground present, replace K5 relay. d. Remove K5-87 lead from K5 and start genset. If set shuts down and OVERSPEED lamp comes on, replace ECM (A11). e. Check Ford engine harness oil pressure lead for proper ground to intake manifold. Must be grounded to prevent false ignition module fault. 2b. The OVERSPEED lamp comes on and the engine shuts down within 1 to 5 seconds (no over-speed condition detected). (V6 Spec C) f. Remove connector from J2 of the ECM (A11) board and check pin J2-6 continuity to ground. If ground present, replace ignition module. g. Check Ford engine harness oil pressure lead for proper ground to intake manifold. Must be grounded to prevent false ignition module fault.

Compiled from service & troubleshooting documentation across every generator set that uses the Cummins/Onan V-10 WSG-1068.

Maintenance schedule

ItemSpecCapacityPart #Interval
Air filter500 hr
Fuel filter
Oil filter250 hr
BatteryGround416-0823200 hr Amazon eBay $100.39
Belt
Coolant33.1
Coolant filter500 hr
Oil6.5 Qts (L)250 hr
Spark plug1000 hr

Pooled from every document that names this exact engine — confirm the interval and part number against your unit's serial number.

Service intervals

40
ItemActionHoursMonthsNotes
Air cleanerCheck100 hrReplace as necessary; perform more often in extremely dusty conditions.
All exhaust components and hardware (fittings, clamps, fasteners)Check8 hrDaily; audibly and visually with generator set running
All hardware (fittings, clamps, fasteners, etc.)Check100 hr1 moDaily or after 8 hours.
Bedframe fluid containment (where fitted)Drain8 hrDaily; drain if necessary
Coolant heater(s)Check24 hrStandby power schedule. Daily or after 8 hours.
Coolant levelCheck24 hrStandby power schedule. Daily or after 8 hours.
Coolant level of radiator(s) (water jacket & LTA)Check8 hrDaily
Cooling fan bladesCheck8 hrVisual inspection required daily
Drive belt condition and tensionCheck8 hrVisually check belt for wear or slippage; replace if hard or brittle (Service Engineer)
Engine oil levelCheck24 hrStandby power schedule. Daily or after 8 hours.
Fuel level in tankCheck8 hrDaily or after 8 hours
Fuel lines and hosesCheck8 hrDaily; check for oil, fuel, coolant and exhaust system leaks (Table 5 note 1)
General setInspect8 hrCheck for oil, fuel, cooling and exhaust system leaks; inspect exhaust audibly/visually with set running and repair leaks immediately.
General set inspectionInspect8 hrDaily/after 8 hours (X1). Check for oil, fuel, cooling and exhaust system leaks; check exhaust audibly and visually with set running.
Generator air outletCheck100 hr1 moStandby power schedule. Daily or after 8 hours.
Generator set (general)Inspect24 hrStandby power schedule. Daily or after 8 hours. Footnote 1: Check for oil, fuel, cooling and exhaust system leaks; check exhaust system audibly and visually with set running.
Crankcase oilChange50 hrFirst service — Drain and replace crankcase oil after the first 50 hours of operation on new generator sets (break-in).
Crankcase oilDrain50 hrFirst service — Drain and replace crankcase oil after first 50 hours of operation on new generator sets.
Engine oil and filterChange250 hr6 moFirst service — Replace after the initial running-in period of 50 hours; contact your authorized distributor (Table 5 note 5)
Engine oil and filterDrain50 hrFirst service — Break-in: drain and replace crankcase oil after first 50 hours of operation on new generator sets.
Air cleaner (heavy duty filter)Check100 hrPrime power schedule. 100 hours. Footnote 2: Perform more often in extremely dusty conditions. Footnote 3: Replace element every 2000 hours.
Air cleaner (normal duty filter)Check100 hrX2 perform more often in extremely dusty conditions; X3 replace element after 500 hours
Battery electrolyte levelCheck100 hr1 moStandby power schedule. Monthly or after 100 hours.
Drive beltCheck500 hr12 moX5 visually check belt for evidence of wear or slippage; replace if hard or brittle
Governor linkageCheck100 hr1 moPerform more often in extremely dusty conditions.
Hardware (fittings, clamps, fasteners)Check100 hrStandby power schedule. Monthly or after 100 hours.
All hardware (fittings, clamps, fasteners)Check250 hr6 mo
Engine coolant port capsCheck250 hr6 moReplace after 4 years or 1000 hours.
Engine oil and filter (heavy duty filter)Change250 hrPrime power schedule. 250 hours. Footnote 2: Perform more often in extremely dusty conditions.
Engine oil and filter (normal duty filter)Change250 hr12 moX2 perform more often in extremely dusty conditions; X9 perform at least once a year
Exterior of radiatorInspect250 hr6 moInspect for obstructions.
Radiator exteriorInspect250 hr6 moInspect for obstructions.
Radiator hosesCheck500 hr12 moCheck for wear and cracks; replace if hard or brittle.
Radiator hoses for wear and cracksCheck250 hr6 moReplace if hard or brittle.
AC generator and controlsCheck500 hr12 moYearly.
Anti-freezeCheck500 hr12 moYearly.
Anti-freeze concentrationCheck500 hr12 moYearly or after 500 hours.
Catalytic converter restrictionTest1000 hr24 moX7 must be performed by a qualified mechanic; X8 replace every 8 years or 2000 hours
Cooling systemsClean500 hr12 moYearly.
Oxygen sensorInspect1000 hr24 moX6,7 inspect or replace; replace every 1,000 hours; must be performed by a qualified mechanic

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Service specifications

60
TypeItemValueUnitCondition
ClearanceClearance around generator set for service1meter
ClearanceExhaust pipe clearance to combustible wall or partition305mm
ClearanceIsolator base elevation tolerance between isolators0.25inch (6 mm)
ClearanceVibration isolator top plate to base clearance0.25inch
ClearanceVibration isolator top plate-to-base clearance (nominal)0.25inch (6 mm)
GapSpark Plug Gap0.044in. (1.1 mm)
GapSpark plug gap0.035in (0.9 mm)
GapSpark plug gap0.044 (1.1 mm)in (mm)
OtherAdjust - Frequency Adjust range5% of nominal frequency
OtherAdjust - Voltage Adjust range5% of nominal voltage
OtherAir cleaner bench/paper element cleaningNot recommendedCummins Inc. does not recommend cleaning paper-type air cleaner elements
OtherB+ fused output10amps, 12/24 volt
OtherBattery charger output - 12 Volt15A
OtherBattery charger output - 24 Volt12A
OtherBattery charging alternator (max. rating)37A
OtherBattery electrolyte specific gravity (fully charged, corrected)1.260SGat 25 °C (77 °F)
OtherBattery specific gravity (fully charged, corrected)1.260corrected by adding 0.004 per 10 F above 80 F (27 C)
OtherBattery specific gravity (recharge below)1.215
OtherBattery specific gravity, charge required below1.215specific gravity
OtherBattery specific gravity, fully charged1.260corrected; add 0.004 per 10 F above 80 F (27 C)
OtherBattery specific gravity, fully charged (corrected)1.260specific gravitycorrected to 80°F (27°C)
OtherBattery specific gravity, recharge threshold1.215charge battery if reading is below this value
OtherBattery storage charging - further charge interval6monthsat the normal initial charge rate until voltage ceases to rise
OtherBoost Charge interval (if charger fitted with Boost switch)6monthsnormally around every six months per battery manufacturer
OtherCharge battery if specific gravity below1.215SG
OtherCool-down at idle time delay0-30minutes
OtherCooldown at idle timer0 - 30minutes
OtherCustomer Output relay rating (TB1)2amps at 30 VDCnormally open contacts
OtherExhaust connection3inch NPT
OtherFrequency adjust range+/-5percentnominal frequency
OtherLow Fuel warning (yellow lamp)5inches (127 mm) WC or lessdual or single fuel systems
OtherOutput voltage adjustment range (voltage adjust rheostat, optional)±5% of nominal voltage
OtherOvercrank timed cranking periodapproximately 75seconds, including two rest periods
OtherRated To Idle delay0 - 10secondsdefault = 0; Beginning Version 2.303
OtherRated to idle delay0-10secondsdefault 0; beginning Version 2.303
OtherRelay contact rating (K10/K11/K12)10amps at 600 VAC
OtherSecondary regulator initial adjustment (distance from top of regulator to top of set screw), NG, 60 Hz12.1mm
OtherSecondary regulator initial adjustment, NG, 60 Hz13.35mm
OtherSecondary regulator initial adjustment, NG, 60 Hz15.9mm
OtherSpecific gravity temperature correction0.007SG per 10 °C (18 °F)subtract above 25 °C (77 °F), add below
OtherSpecific gravity, at end of charge, ambient frequently above 32 °C (90 °F)1.240 - 1.260SG
OtherSpecific gravity, at end of charge, ambient normally below 32 °C (90 °F)1.240SG
OtherSpecific gravity, electrolyte for filling new cells, ambient frequently above 32 °C (90 °F)1.270 - 1.290SG
OtherSpecific gravity, electrolyte for filling new cells, ambient normally below 32 °C (90 °F)1.270SG
OtherStart Delay0 - 300secondsdefault = 0
OtherStarting crank/rest cycle defaults3 start cycles of 15 seconds cranking and 15 seconds rest (configurable 1-7)
OtherStarting cycles (crank/rest)3start cyclesdefault: 3 cycles composed of 15 seconds of cranking and 15 seconds of rest
OtherStop Delay0 - 600secondsdefault = 0
OtherSwitched B+ fused output5amps, 12/24 voltactivated on run command
OtherTime Delay To Stop0 - 600seconds
OtherTime delay to start0-300secondsdefault 0
OtherTime delay to stop0-600secondsdefault 0
OtherVoltage adjust range+/-5percentnominal voltage
OtherWarm-up at idle time delay0 - 300seconds
OtherWarm-up at idle time delay0-300seconds
PressureConcrete compressive strength for seismic anchors4000PSI
PressureExhaust Backpressure (Max. Allowed)25inch H2O (6.25 kPa)maximum
PressureExhaust Backpressure (max allowed)20inch H2O (5.0 kPa)
PressureExhaust backpressure (max. allowed)20inch H2O (5.0 kPa)
PressureExhaust backpressure maximum allowed20inch H2O (5.0 kPa)

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Recommended fluids

FluidGradeStandardAmbientCapacityNotes
Coolant50% Ethylene Glycol and waterFleetguard® Compleat ES low-silicate antifreeze, or equivalentStandard concentration 50% Ethylene Glycol and water; must be maintained. Fill cooling system to the bottom of the fill neck in the radiator or expansion tank. Some radiators have two fill necks, both must be filled.
Coolant50/50 coolant solution (50% pure water, 50% antifreeze)32.2 LCapacity with standard radiator 8.5 Gal (32.2 L). If temperatures below -37°F (-38°C) possible, use 65% antifreeze / 35% water. Do not use antifreeze with anti-leak additives. Use soft, low-mineral water.
Coolant50/50 coolant solution (50% pure water, 50% antifreeze); 65% antifreeze/35% water if below -37°F (-38°C)33.1 LCooling system capacity with standard radiator 8.8 Gal (33.1 L). Use clean, low-mineral soft water free of chloride, sulfate or acid. Do not use antifreeze containing anti-leak additives.
Coolant50/50 water/antifreeze (65% antifreeze/35% water below -37F/-38C); no anti-leak additivesabove -38°C8.8 Gal (33.1 L)Use soft water low in mineral content.
Coolant50/50 coolant solution (50% pure water and 50% anti-freeze)above -37°C32.2 LCooling system capacity with standard radiator 8.5 Gal (32.2 L). If temperatures below -37 deg F (-38 deg C) are possible, use 65% antifreeze / 35% water. Do not use an antifreeze containing anti-leak additives. Use clean soft water low in mineral content.
Coolant50/50 coolant solution (50% pure water and 50% antifreeze)Do not use antifreeze containing anti-leak additives; use soft, low-mineral waterabove -37°C33.1 LIf temperatures below -37 F (-38 C) are possible use 65% antifreeze and 35% water. Cooling system capacity with standard radiator 8.8 Gal (33.1 L).
Engine oilHigh-quality multi-viscosity lubricating oil such as Cummins Premium Blue® or its equivalentConsult your authorized distributor for correct lubricating oil specifications for your operating conditions. Special running-in oils are not recommended.
Engine oilRefer to oil viscosity chart (Figure 5-1)API SJ or SJ/CD6.2 LSelect grade right for the lowest ambient temperature expected.
Engine oilSAE 10W30, 5W30, 15W40API classification SJ, SH or SL6.2 LOil capacity with filters 6.5 Qts (6.2 L). Select viscosity grade for lowest expected temperature; if ambient is consistently below -13°F (-25°C), use a SAE 5W synthetic oil. Do not use oil that is too thick.
Engine oilSAE 10W30, SAE 5W30, SAE 15W40API classification SJ, SH or SL6.2 LStandby Power oil capacity 6.5 Qts (6.2 L) with normal oil filter; Prime Power 11 Qts (10.4 L) with heavy duty oil filter. If ambient temperature is consistently below -13 deg F (-25 deg C), use a SAE5W synthetic oil. Select grade for the lowest expected temperature.
Engine oilSAE 5W synthetic (if ambient consistently below -13°F/-25°C)API classification SJ or SJ/CD6.2 LSelect viscosity grade per ambient temperature chart (Figure 5-1); oil capacity with filters 6.5 Qts (6.2 L).
Engine oilAPI SJ, SH or SL; SAE 10W30, 5W30 or 15W40 per ambient temperature chartAPIabove -25°C6.5 Qts (6.2 L)Use SAE5W synthetic oil if ambient temperature is consistently below -13F (-25C).
Engine oilSAE 5W syntheticAPI SJ or SJ/CDabove -25°C6.2 LUse SAE 5W synthetic if ambient temperature is consistently below -13 F (-25 C). Pick viscosity grade for lowest temperature expected. Oil capacity with filters 6.5 Qts (6.2 L).
FuelNatural Gas and/or Propane (LPG, liquid or vapor withdrawal)Combination natural gas/LPG sets have separate shutoff solenoid valves and a fuel pressure switch for automatic changeover.
FuelNatural Gas and/or Propane (LPG, liquid or vapor)Gaseous fuel; engine has a gas mixer serving both fuels with separate shutoff solenoid valves and pressure switch for automatic changeover.
FuelNatural Gas and/or Propane (Liquid or Vapor)Fuel inlet pressure min 7.0 inch H2O NG/LPG; max 13.6 inch H2O NG/LPG vapor withdrawal, 312 psi LPG liquid withdrawal
FuelPropane (Liquid or Vapor); Natural Gas
FuelPropane (liquid or vapor) / Natural GasFuel flow inlet pressure min 7.0 inch H2O (1.7 kPa) NG/LPG; max 13.6 inch H2O (3.4 kPa) NG/LPG vapor withdrawal; max 312 psi (2,153 kPa) LPG liquid withdrawal.

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Fault codes

80
CodeNameMeaningSeverityAction
1123Shutdown After BSShutdown After Battle ShortShutdown
1124Delayed ShutdownDelayed ShutdownWarning
1131Battle Sh ActiveCategory EWarning
121Speed Signal LostSpeed Signal LostShutdown
1311Customer Input #1Optional customer selection (example: Low Fuel Day Tank, Water In Fuel, Ground Fault, Low Starting Hydraulic Pressure, Low Starting Air Pressure). Default display name Customer Fault 1; default status None.WarningProgrammable via InPower service tool: enable/disable, status (warning/shutdown/none), active open/closed, and display name.
1312Customer Input #2Optional customer selection. Default display name Ground Fault; default Warning.WarningProgrammable via InPower service tool: enable/disable, status (warning/shutdown/none), active open/closed, and display name.
1313-1316Network Fault 1 thru 4Network Fault 1 through 4Warning
1317Customer Input #3Optional customer selection. Default display name Low Fuel; default Warning.WarningProgrammable via InPower service tool: enable/disable, status (warning/shutdown/none), active open/closed, and display name.
1318Service Engine (begin spec J)Warning lamp. Emissions criteria might not be met due to engine running in open loop, lean mixture, rich mixture, or a failed fuel system component.WarningIndicates emissions criteria might not be met: engine running in open loop, lean mixture, rich mixture, or failed fuel system component.
1334Crit Scaler ORCritical Scaler Out of RangeShutdown
1335Noncrit Scaler ORNon-critical Scaler Out of RangeWarning
135Oil Pressure Sensor HOil Pressure Sensor HWarning
141Oil Pressure Sensor LOil Pressure Sensor LWarning
1416Fail to ShutdownFail to ShutdownWarning
1417Pwr Down ErrorWarning lamp. The controller cannot power down because of some unknown condition; possible drain on battery.WarningIndicates controller cannot power down because of unknown condition; possible battery drain. Contact an authorized service center.
143Pre-Low Oil PresWarning lamp. Indicates engine oil pressure has dropped to an unacceptable level.WarningIf the generator is powering critical loads and cannot be shut down, wait until the next shutdown period and then follow code 415 procedure.
1433Emergency StopShutdown lamp. Indicates local Emergency Stop.ShutdownTo reset: pull the button out; move the O/Manual/Auto switch to O; press the front panel Fault Acknowledge/Reset button; select Manual or Auto as required.
1434Remote E-stopShutdown lamp. Indicates remote Emergency Stop.ShutdownSee code 1433 to reset.
1435Low Coolant TempWarning lamp. Set is not operating; warning occurs when engine coolant temperature is 70 deg F (21 deg C) or lower.WarningIndicates engine coolant heater is not operating or is not circulating coolant. Check coolant heater power supply (blown fuse or disconnected heater cord). Check for low coolant level and replenish; look for coolant leakage points and repair.
1438Fail to CrankShutdown lamp. Possible fault with control, speed sensing or starting system.ShutdownSee code 441 for corrective action.
144Coolant Sensor HighCoolant Sensor HighWarning
1442Weak BatteryWarning lamp. During cranking, battery voltage is at or below the weak battery warning trip point for a time greater than or equal to the weak battery set time.WarningSee code 441 for corrective action.
1443Battery FailedShutdown lamp. Dead battery - engine will not start.ShutdownSee code 441 for corrective action.
1444kW OverloadkW OverloadWarning
1445Short CircuitShort CircuitShutdown
1446High AC VoltageHigh AC VoltageShutdown
1447Low AC VoltageLow AC VoltageShutdown
1448Under FrequencyShutdown lamp. Possible fuel system problem or overload condition.WarningCheck for dirty/plugged air filter and replace; check by disconnecting load and restarting; fuel system may require adjustment; check gaseous fuel delivery; reset and restart.
1449Over FrequencyOver FrequencyWarning
145Coolant Sensor LowCoolant Sensor LowWarning
1452Gen CB Not CloseGenerator circuit breaker not closeWarning
1453Gen CB Not OpenGenerator circuit breaker not openWarning
1459Reverse PowerReverse PowerShutdown
146Pre-High Coolant TempWarning lamp. Engine has begun to overheat (coolant temperature has risen to an unacceptable level).WarningReduce load if possible by turning off non-critical loads; check air inlets/outlets for obstructions. If engine can be stopped, follow code 151 procedure.
1461Loss of FieldLoss of FieldWarning
1466Modem FailureModem FailureWarning
1468Network ErrorNetwork ErrorWarning
1469Speed/Hz MatchSpeed/Hz MatchWarning
1471Over CurrentCategory BWarning
1472Over CurrentOver CurrentShutdown
1477Over CurrentOver CurrentShutdown
151High Coolant TempShutdown lamp. Engine has overheated (coolant temperature above the shutdown trip point).ShutdownAllow engine to cool. Check coolant level and leakage points, obstructions to cooling airflow, fan belt, blower fan/circulation pumps; reset control and restart.
197Low Coolant LevelWarning lamp (Optional). Engine coolant level has fallen below the warning trip point.WarningIf the generator is powering critical loads and cannot be shut down, wait until the next shutdown period, then follow code 235 procedure. If the engine can be stopped, follow 235 procedure.
2263Battery TemperatureBattery temperature too high (reaches 55 °C [131 °F]) - battery charger fault messageWarning
2323-2326Network Fault 5 thru 8Network Fault 5 through 8Warning
2327PTC FaultPower Transfer Control FaultWarning
2329Low S1 FrequencyLow S1 FrequencyWarning
2331Low S1 VoltageLow S1 VoltageWarning
2335Excitation FaultExcitation Fault (Loss of Voltage Sense)Shutdown
2336Memory ErrorMemory ErrorShutdown
2337Pwr Tran DisabledPower Transfer DisabledWarning
2338Pwr Tran FailurePower Transfer FailureWarning
2339Pwr Down EnabledPower Down EnabledWarning
234OverspeedOverspeedShutdown
2341High Control TempHigh Control TemperatureWarning
2342Too Long in Idle (10 min)Warning lamp. Genset has been in Idle mode too long (10 minutes maximum).WarningIndicates the generator set has been in Idle mode too long (10 minutes maximum).
235Low Coolant LevelShutdown lamp (Optional). Engine coolant level has fallen below the shutdown trip point.ShutdownAllow engine to cool. Check coolant level and replenish, look for leakage points and repair; reset control and restart.
2358High S1 VoltageHigh S1 VoltageWarning
2396S1 CB Not CloseS1 Circuit Breaker Not CloseWarning
2397S1 CB Not OpenS1 Circuit Breaker Not OpenWarning
2966PTC TimeoutPTC TimeoutWarning
2967Governor FaultGovernor FaultWarning
2968AVR FaultCategory CWarning
2969LON FailureLON FailureWarning
2972Field OverloadField OverloadShutdown
359Fail To StartShutdown lamp. Possible fuel system problem (engine cranks but fails to start).ShutdownOpen any closed fuel shutoff valve; check for dirty/plugged air filter and replace if necessary; check gaseous fuel delivery; reset control and restart.
415Low Oil PressureShutdown lamp. Engine oil pressure has dropped below the shutdown trip point.ShutdownCheck oil level, lines and filters; replenish oil if low; reset control and restart.
441Low Bat VoltageWarning lamp. Battery voltage supply to the control is approaching a low level at which unpredictable operation will occur.WarningCheck/recharge/replace discharged or defective battery; clean and tighten battery cable terminals; check battery charger float level.
442High Bat VoltageWarning lamp. Battery voltage supply to the control is approaching a high level at which damage to the control can occur.WarningCheck the float level on the battery charger if applicable (lower float level).
FAULT 1FAULT 1Red lamp indicates an undedicated fault; may be field programmed as shutdown or non-shutdown and as timed or non-timed (normally set for timed shutdown).ShutdownNature of fault determined when set installation is designed.
FAULT 2FAULT 2Red lamp indicates same features as Fault 1 (normally set for non-timed shutdown).ShutdownNature of fault determined when set installation is designed.
Fault 1Fault 1 (red)Engine shut down because of a system fault; part of a 10-second time-delay shutdown circuit (customer-wired).Shutdown
Fault 2Fault 2 (red)Engine shut down because of a system fault; part of a non-time-delay shutdown circuit (customer-wired).Shutdown
HI ENG TEMPHI ENG TEMPRed lamp indicates engine has shut down because of critically high engine temperature (above 230 F / 110 C).ShutdownAllow engine to cool; check coolant level and airflow; reset control and restart.
High Engine TemperatureHigh Engine Temperature (red)Engine shut down due to excessively high coolant temperature (greater than 230°F / 110°C).Shutdown
LO FUELLO FUELYellow (optional) lamp indicates fuel supply pressure is marginally low (5 inches [127 mm] WC or less).WarningCheck for partially closed shutoff valve or empty propane supply tank; for natural gas check with the gas utility.
LO OIL PRESLO OIL PRESRed lamp indicates engine has shut down because of critically low oil pressure (below 25 psi / 172.4 kPa).ShutdownCheck oil level, lines and filters; replenish if low; reset control and restart.
LOW ENG TEMPLOW ENG TEMPYellow lamp lights if engine temperature is marginally low for starting (70 F / 21 C or lower); may indicate an inoperative coolant heater.WarningCheck coolant heater operation, power supply, fuse/cord and coolant level.
Low Engine TemperatureLow Engine Temperature (yellow)Engine temperature less than 65°F (18°C) or 90°F (32°C); possibility engine might not start.Warning
Low FuelLow Fuel (yellow, optional)Fuel supply pressure is 5 inches (127 mm) WC or less; also indicates operation on secondary fuel supply for dual-fuel sets.Warning

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Procedures

12
Gaseous Fuel Adjustments adjustment

⚠ Fuel is highly flammable; do not allow cigarettes, flame, pilot lights, arcing switches or equipment in area or areas sharing ventilation.

Tools: Exhaust gas analyzer (for emission sensitive areas)

  1. Start the engine and let set warm up under partial load (at least 1/4 rated load); start with natural gas if dual fuel.
  2. Connect full rated load and turn power adjust valve to full-rich.
  3. Slowly turn adjust valve towards lean until engine begins to lose speed, then back towards rich until engine carries full load smoothly.
  4. If equipped for natural gas and LPG, switch to LPG by closing manual shutoff valve in the natural gas supply line.
  5. Reconnect full rated load and turn LPG flow adjustment valve clockwise until engine loses speed, then slowly back counterclockwise until engine carries full load smoothly.
Gaseous Fuel System Adjustment adjustment

⚠ Fuel is highly flammable and may cause severe personal injury and property damage. Do not allow cigarettes, flame, pilot lights, arcing switches or equipment in area or areas sharing ventilation.

Tools: Exhaust gas analyzer (for emission sensitive areas)

  1. Start the engine and let the set warm up under a partial load (at least 1/4 rated load); on dual fuel sets start with natural gas.
  2. Connect full rated load and turn the manual fuel valve two turns counterclockwise.
  3. Slowly turn the manual fuel valve clockwise (lean) until the engine begins to lose speed.
  4. Slowly turn it counterclockwise (rich) until the engine carries the full load smoothly.
  5. On dual fuel sets, switch to LPG by closing the manual shutoff valve in the natural gas supply line.
  6. Reconnect full rated load and turn the LPG flow adjustment valve clockwise until the engine begins to lose speed.
  7. Slowly turn it back counterclockwise until the engine carries full load smoothly.
Gaseous Fuel System Adjustments adjustment

⚠ Fuel is highly flammable and may cause severe personal injury and property damage. Do not allow cigarettes, flame, pilot lights, arcing switches or equipment in area or areas sharing ventilation.

Tools: exhaust gas analyzer (for emission sensitive areas)

  1. Start the engine and let the set warm up under a partial load (at least 1/4 rated load). Start with natural gas if dual fuel.
  2. Connect full rated load and turn the power adjust valve two turns counterclockwise.
  3. Slowly turn the manual fuel valve clockwise (lean) until the engine begins to lose speed.
  4. Slowly turn counterclockwise (rich) until the engine carries full load smoothly.
  5. If dual fuel, switch to LPG by closing the manual shutoff valve in the natural gas supply line.
  6. Reconnect full rated load and turn the LPG flow adjustment valve clockwise until the engine begins to lose speed.
  7. Slowly turn it back counterclockwise until the engine carries full load smoothly.
Magnetic Speed Pickup Unit Adjustment adjustment
  1. Measure MPU resistance; replace if not between 1,000 and 1,050 ohms.
  2. With MPU removed, rotate ring gear until a tooth lines up in the center of the mounting hole.
  3. Thread pickup in gently by hand until it just touches the ring gear tooth.
  4. Back the pickup out 1/4 turn and set the locknut.
  5. Verify MPU output voltage at cranking speed is at least 1.5 VAC; replace MPU if less.
Output Voltage Adjustment adjustment
  1. Adjust output voltage plus or minus five percent of nominal voltage using the Voltage Adjust rheostat (optional) on the control panel.
  2. Call your distributor if the required voltage cannot be obtained by this adjustment.
Type A Gaseous Fuel Adjustment (Naturally Aspirated) adjustment

⚠ Gaseous fuels are flammable and explosive

  1. Disconnect all loads, shut down set, and disconnect governor linkage at the carburetor.
  2. Start engine and hold throttle closed by hand to prevent overspeed.
  3. Adjust throttle idle position screw to obtain a frequency of 25-35 Hz.
  4. Turn idle adjusting screw counterclockwise until engine becomes unstable, then clockwise to regain stability.
  5. Reconnect governor linkage.
  6. Connect full rated load and turn main fuel valve to full-rich, then lean until engine loses speed, then back to rich.
  7. If equipped for LPG, switch to LPG and adjust LPG flow valve similarly under full load.
Vibration Isolator Installation and Adjustment Procedure adjustment
  1. Place vibration isolators on the generator set support structure; shim or grout so all isolator bases are within 0.25 inch (6 mm) elevation of each other.
  2. Loosen the side snubber lock nuts so the top plate is free to move vertically and horizontally; verify alignment with base and springs.
  3. Place the generator set onto the isolators while aligning the skid mounting with the threaded isolator hole.
  4. Adjust isolators with the leveling bolt to level the set; nominal clearance between top plate and base is 0.25 inch (6 mm) or greater.
  5. If radiator and engine/alternator are mounted on separate skids, make both skids level for proper fan belt alignment.
  6. If the set is not level, adjust leveling bolts until level with sufficient, roughly equal clearance on all isolators.
  7. Lock the leveling bolt in place with the lock nut.
  8. Leave snubber nuts loose to provide better isolation between the generator set and support structure.
Checking AC Electric System While Running diagnostic

⚠ High voltages are present inside the control box and generator output box when the set is running. Do not open the boxes while the set is running.

  1. Check the frequency meter; generator frequency should be stable and match the nameplate rating.
  2. Turn the phase selector switch to each line-to-line phase selection (L1-L2, L2-L3, L3-L1) and read the AC voltmeter; at no load voltage should match nameplate rating.
  3. Turn the phase selector switch to each phase (L1, L2, L3) and read the AC ammeter; at no load current should be zero.
  4. Push the Reset/Lamp switch; all indicator lamps should light, confirming all bulbs are on.
  5. Have any burned out bulbs replaced.
Verify Overspeed Fault Detection diagnostic

Tools: special tool P/N 420-0604

  1. For Type A sets, move the throttle lever/linkage to increase RPM to the overspeed shutdown range.
  2. For Type B sets, remove the two screws securing the throttle body cover and remove cover.
  3. Use special tool P/N 420-0604 to turn the end of the throttle shaft.
  4. With genset operating at no load, slowly rotate the shaft clockwise until RPM reaches the overspeed limit and shuts down.
  5. Replace the throttle body cover after completing the test.
AC Electrical Connections installation

⚠ Do not connect generator set directly to any building electrical system

⚠ Reconfiguring to different voltages can damage generator or windings; consult distributor

  1. Place the control panel run switch in OFF position; remove AC power from battery charger; remove negative battery cable.
  2. Install transfer switch for standby service applications.
  3. Reconfigure generator output leads on connection terminal block per Reconnection Diagram as needed for nameplate voltage.
  4. Bolt stranded load wires to the appropriate U/V/W/N terminals.
  5. Balance loads so current flow from each line terminal is within 10 percent of median value.
  6. Install current transformers (CT21/CT22/CT23) per Reconnection Diagram with dot facing toward the generator.
  7. Ground the genset to earth in one location only.
AC Voltage Reconnection installation

⚠ Reconfiguring to higher voltages can exceed winding voltage capability and damage generator

⚠ Reconfiguring to lower voltages can increase line current beyond breaker rating

  1. Check available generator output voltages and maximum current ratings on generator nameplate.
  2. Reconfigure generator output leads per Reconnection Diagram on control housing side access cover if required.
  3. Check stator lead terminal block connections and perform necessary reconnect to obtain required voltage.
  4. Route current transformers (CT1, CT2, CT3) per Reconnection Diagram, dot facing generator, current flowing into dot.
Battery Connections (Prestart Preparation) installation

⚠ Accidental starting can cause severe personal injury or death.

⚠ Ignition of explosive battery gases can cause severe personal injury or death.

⚠ Ventilate battery area before working on or near battery. Arcing, flames, pilot lights and sparks can ignite battery gas.

  1. Make sure the Run/Off/Auto switch on the control panel is set to Off before connecting battery cables.
  2. Connect the positive battery cable before connecting the negative battery cable to prevent arcing.
  3. Connect the negative (–) battery cable last to prevent arcing.
  4. Service the battery as necessary; connect a separate battery charger if an ATS without built-in charge circuit is installed.

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Voltage reconnection

VoltagePhaseConnectionLeadsNotes
Current Transformer routing: CT1-U load leads (A phase), CT2-V load leads (B phase), CT3-W load leads (C phase)CT1, CT2, CT3Dot on CT must face toward generator; dual secondaries post 2 (high voltage) or post 3 (low voltage)
Generator reconnection terminal block, terminals U/V/W/N correspond to L1/L2/L3/L0U, V, W, NLoad balancing within 10 percent of median line current
Line 0 or NeutralN / N / NLoad terminal line designations
Line 1L1 / A / ULoad terminal line designations
Line 2L2 / B / VLoad terminal line designations
Line 3L3 / C / WLoad terminal line designations
TB1 Customer Faults1=Customer Fault 1, 2=Ground Fault, 3=Low Fuel, 4=Rupture Basin FaultDefault settings, beginning spec J customer input #4 not available
TB1 Customer Relays1=Common Warning, 2=Common Shutdown, 3=Not in Auto, 4=Ready to LoadDefault settings; NO contacts rated 2 amps at 30 VDC
U, V, W, N terminals correspond to L1, L2, L3, L0U=A phase (CT21), V=B phase (CT22), W=C phase (CT23)Reconnection Diagram located on upper side cover of control housing

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Parts cataloged across the Cummins/Onan V-10 family

16
Part #DescriptionCategory
A034V218Filter, Air (14" x 3")air_filter
A034V042Alternatoralternator
A034V046Tensionerbelt
A034V077Belt, V-10belt
191-2213Starter, Electricgasket
123-2248Separater, Oiloil_filter
123-2176Separator, Oilother_service
928-0617PowerCommand 2100 Controllerother_service
A034V213Turbochargerpump
193-0499Sensor, Oxygensensor
A028X493Sender, Oil Pressuresensor
A034V076Sensor, Map - Turbosensor
A034V246Sensor, Oxygensensor
167-1639Plug, Spark (Ford Part Number AGSF-22-FM1) (.035 Gap)spark_plug
A034V055Plug, Sparkspark_plug
130-5258Thermostat (85°C) (Must Purchase F1VY-8255-A O-ring seal from Ford)thermostat

Parts cataloged across all variants of this engine family — verify the exact part fits your specific variant and serial number before ordering.

Common questions

What is the oil capacity of the Cummins/Onan V-10 WSG-1068?

The Cummins/Onan V-10 WSG-1068 engine has an oil capacity of 6.2 liters.

Which generators use the Cummins/Onan V-10 WSG-1068 engine?

The Cummins/Onan V-10 WSG-1068 powers 4 generator set(s), including Cummins/Onan GGHE, Cummins/Onan GGHF, Cummins/Onan GGHG, Cummins/Onan GGHH.

How often should you change the oil in the Cummins/Onan V-10 WSG-1068?

The Cummins/Onan V-10 WSG-1068 oil change interval is every 250 hours.

What is a common problem with the Cummins/Onan V-10 WSG-1068 engine?

A commonly reported issue on generators using the Cummins/Onan V-10 WSG-1068 is: Over Current.