Cummins/Onan V-10 WSG-1068 Engine

The Cummins/Onan V-10 WSG-1068 is an engine. It powers generator sets from Cummins/Onan, including the GGHE, GGHF, GGHG and GGHH. It holds 6.2 L (1.6 gal) of oil and 33.1 L (8.7 gal) of coolant.

Also known as: Onan Modified Ford V-10 WSG-1068

Part of the Cummins/Onan V10 engine family — 2 variants share parts & fitment.

6.2 L
Oil capacity

Engine specifications

Oil capacity6.2 L
Coolant capacity33.1 L

Common problems

15
  • The engine does not crank in Run mode
    Cause: The Emergency Stop switch has been used. (The switch button is lit.)
    Fix: Pull the Emergency Switch button. To reset the engine control, push the Run-Stop-Remote switch to Stop and the Reset switch to Reset. Then push the Run-Stop-Remote switch to Run to start the genset.
  • The engine cranks but does not start
    Cause: The engine is not getting fuel.
    Fix: Open any closed fuel shutoff valve. (Valves closed for maintenance or new installations may require several crank cycles to get fuel to genset); Fill the propane supply tank; For natural gas fueled sets, check with the gas utility; Check fuel pressure at regulator (refer to Fuel Pressure in Section 6.) (High fuel pressure will prevent solenoid from opening); Check fuel solenoid (VDC present at K1+ lead during cranking); Duel Fuel Sets Only: Check relay K99. Refer to wiring diagrams in Section 7; Check pressure switch wiring. Propane − normally closed connected to common. Natural gas − normally open connected to common; Check pressure switch function (@ 3.5 inch H2O or less, should switch from natural gas to LPG); Check S14 vacuum switch (optional) for proper operation.
  • No output voltage
    Cause: The line circuit breaker is OFF.
    Fix: Find out why the circuit breaker was turned OFF, make sure it is safe to reconnect power, and then throw the circuit breaker ON.
  • The engine lacks power or is unstable
    Cause: Current ambient conditions cause a derate, limiting power to less than rated power.
    Fix: Determine proper derates for ambient conditions. Refer to specification sheet for site derating factors.
  • The field circuit breaker keeps tripping
    Cause: The rotating rectifier assembly (diodes CR1 through CR6) is faulty
    Fix: Shut down the set and check each diode according to Section 7; Service as necessary
  • The engine does not crank in Remote mode
    Cause: The Run-Stop-Remote switch is at Stop. (The Switch-Off light will be flashing.)
    Fix: Push the Run-Stop-Remote switch to Remote.
  • Output voltage is too high or too low
    Cause: Engine speed is unstable
    Fix: Troubleshoot according to the chart, The Engine Lacks Power or is Unstable
  • Engine will not crank.
    Cause: Fault lamp on
    Fix: Correct fault and reset control.
  • The phase currents are unbalanced
    Cause: The connected loads are distributed unevenly among the phases
    Fix: Shut down the set and redistribute the loads as evenly as possible
  • Battery completely discharged
    Cause: Poor battery terminal connection
    Fix: Clean connections, replace and tighten.
  • Battery low charge
    Cause: Poor battery connection
    Fix: Clean connections, reconnect and tighten securely.
  • Output voltage is unstable
    Cause: The voltage has been adjusted improperly
    Fix: Adjust output voltage according to Section 2, AC Control
  • The FAULT 1 or FAULT 2 fault lamp lights. Engine shuts down immediately, engine runs for several seconds and then shuts down, or engine continues to run. FAULT 1
    Cause: The standard undesignated fault functions are programmed to shut down the set when a fault is sensed. Fault 1 is time delayed while Fault 2 is immediate. The nature of the fault is an optional selection that is determined when the set installation is designed. The undesignated fault functions may also be programmed for non-shutdown or non-time delay.
  • Over Current 1477
  • Battery overcharged
    Cause: Charge alternator fault
    Fix: Contact your nearest Cummins Power Generation distributor.

Compiled from service & troubleshooting documentation across every generator set that uses the Cummins/Onan V-10 WSG-1068.

Maintenance schedule

ItemSpecCapacityPart #Interval
Air filter—500 hr
Fuel filter—
Oil filter—250 hr
BatteryGround416-0823200 hr Amazon
Belt—
Coolant33.1—
Coolant filter—500 hr
Oil6.5 Qts (L)—250 hr
Spark plug—1000 hr

Pooled from every document that names this exact engine — confirm the interval and part number against your unit's serial number.

Service intervals

40
ItemActionHoursMonthsNotes
Air cleanerCheck100 hrReplace as necessary; perform more often in extremely dusty conditions.
All exhaust components and hardware (fittings, clamps, fasteners)Check8 hrDaily; audibly and visually with generator set running
All hardware (fittings, clamps, fasteners, etc.)Check100 hr1 moDaily or after 8 hours.
Bedframe fluid containment (where fitted)Drain8 hrDaily; drain if necessary
Coolant heater(s)Check24 hrStandby power schedule. Daily or after 8 hours.
Coolant levelCheck24 hrStandby power schedule. Daily or after 8 hours.
Coolant level of radiator(s) (water jacket & LTA)Check8 hrDaily
Cooling fan bladesCheck8 hrVisual inspection required daily
Drive belt condition and tensionCheck8 hrVisually check belt for wear or slippage; replace if hard or brittle (Service Engineer)
Engine oil levelCheck24 hrStandby power schedule. Daily or after 8 hours.
Fuel level in tankCheck8 hrDaily or after 8 hours
Fuel lines and hosesCheck8 hrDaily; check for oil, fuel, coolant and exhaust system leaks (Table 5 note 1)
General setInspect8 hrCheck for oil, fuel, cooling and exhaust system leaks; inspect exhaust audibly/visually with set running and repair leaks immediately.
General set inspectionInspect8 hrDaily/after 8 hours (X1). Check for oil, fuel, cooling and exhaust system leaks; check exhaust audibly and visually with set running.
Generator air outletCheck100 hr1 moStandby power schedule. Daily or after 8 hours.
Generator set (general)Inspect24 hrStandby power schedule. Daily or after 8 hours. Footnote 1: Check for oil, fuel, cooling and exhaust system leaks; check exhaust system audibly and visually with set running.
Crankcase oilChange50 hrFirst service — Drain and replace crankcase oil after the first 50 hours of operation on new generator sets (break-in).
Crankcase oilDrain50 hrFirst service — Drain and replace crankcase oil after first 50 hours of operation on new generator sets.
Engine oil and filterChange250 hr6 moFirst service — Replace after the initial running-in period of 50 hours; contact your authorized distributor (Table 5 note 5)
Engine oil and filterDrain50 hrFirst service — Break-in: drain and replace crankcase oil after first 50 hours of operation on new generator sets.
Air cleaner (heavy duty filter)Check100 hrPrime power schedule. 100 hours. Footnote 2: Perform more often in extremely dusty conditions. Footnote 3: Replace element every 2000 hours.
Air cleaner (normal duty filter)Check100 hrX2 perform more often in extremely dusty conditions; X3 replace element after 500 hours
Battery electrolyte levelCheck100 hr1 moStandby power schedule. Monthly or after 100 hours.
Drive beltCheck500 hr12 moX5 visually check belt for evidence of wear or slippage; replace if hard or brittle
Governor linkageCheck100 hr1 moPerform more often in extremely dusty conditions.
Hardware (fittings, clamps, fasteners)Check100 hrStandby power schedule. Monthly or after 100 hours.
All hardware (fittings, clamps, fasteners)Check250 hr6 mo
Engine coolant port capsCheck250 hr6 moReplace after 4 years or 1000 hours.
Engine oil and filter (heavy duty filter)Change250 hrPrime power schedule. 250 hours. Footnote 2: Perform more often in extremely dusty conditions.
Engine oil and filter (normal duty filter)Change250 hr12 moX2 perform more often in extremely dusty conditions; X9 perform at least once a year
Exterior of radiatorInspect250 hr6 moInspect for obstructions.
Radiator exteriorInspect250 hr6 moInspect for obstructions.
Radiator hosesCheck500 hr12 moCheck for wear and cracks; replace if hard or brittle.
Radiator hoses for wear and cracksCheck250 hr6 moReplace if hard or brittle.
AC generator and controlsCheck500 hr12 moYearly.
Anti-freezeCheck500 hr12 moYearly.
Anti-freeze concentrationCheck500 hr12 moYearly or after 500 hours.
Catalytic converter restrictionTest1000 hr24 moX7 must be performed by a qualified mechanic; X8 replace every 8 years or 2000 hours
Cooling systemsClean500 hr12 moYearly.
Oxygen sensorInspect1000 hr24 moX6,7 inspect or replace; replace every 1,000 hours; must be performed by a qualified mechanic

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Service specifications

60
TypeItemValueUnitCondition
ClearanceClearance around generator set for service1meter
ClearanceExhaust pipe clearance to combustible wall or partition305mm
ClearanceIsolator base elevation tolerance between isolators0.25inch (6 mm)
ClearanceVibration isolator top plate to base clearance0.25inch
ClearanceVibration isolator top plate-to-base clearance (nominal)0.25inch (6 mm)
GapSpark Plug Gap0.030inch (0.762 mm)
GapSpark Plug Gap0.044in. (1.1 mm)
GapSpark plug gap0.035in (0.9 mm)
GapSpark plug gap0.044 (1.1 mm)in (mm)
OtherAdjust - Frequency Adjust range5% of nominal frequency
OtherAdjust - Voltage Adjust range5% of nominal voltage
OtherAir cleaner bench/paper element cleaningNot recommendedCummins Inc. does not recommend cleaning paper-type air cleaner elements
OtherB+ fused output10amps, 12/24 volt
OtherBattery charger output - 12 Volt15A
OtherBattery charger output - 24 Volt12A
OtherBattery charging alternator (max. rating)37A
OtherBattery electrolyte specific gravity (fully charged, corrected)1.260SGat 25 °C (77 °F)
OtherBattery specific gravity (fully charged, corrected)1.260corrected by adding 0.004 per 10 F above 80 F (27 C)
OtherBattery specific gravity (recharge below)1.215
OtherBattery specific gravity, charge required below1.215specific gravity
OtherBattery specific gravity, fully charged1.260corrected; add 0.004 per 10 F above 80 F (27 C)
OtherBattery specific gravity, fully charged (corrected)1.260specific gravitycorrected to 80°F (27°C)
OtherBattery specific gravity, recharge threshold1.215charge battery if reading is below this value
OtherBattery storage charging - further charge interval6monthsat the normal initial charge rate until voltage ceases to rise
OtherBoost Charge interval (if charger fitted with Boost switch)6monthsnormally around every six months per battery manufacturer
OtherCharge battery if specific gravity below1.215SG
OtherCool-down at idle time delay0-30minutes
OtherCooldown at idle timer0 - 30minutes
OtherCustomer Output relay rating (TB1)2amps at 30 VDCnormally open contacts
OtherExhaust connection3inch NPT
OtherFrequency adjust range+/-5percentnominal frequency
OtherLow Fuel warning (yellow lamp)5inches (127 mm) WC or lessdual or single fuel systems
OtherOutput voltage adjustment range (voltage adjust rheostat, optional)±5% of nominal voltage
OtherOvercrank timed cranking periodapproximately 75seconds, including two rest periods
OtherRated To Idle delay0 - 10secondsdefault = 0; Beginning Version 2.303
OtherRated to idle delay0-10secondsdefault 0; beginning Version 2.303
OtherRelay contact rating (K10/K11/K12)10amps at 600 VAC
OtherSecondary regulator initial adjustment (distance from top of regulator to top of set screw), NG, 60 Hz12.1mm
OtherSecondary regulator initial adjustment, NG, 60 Hz13.35mm
OtherSecondary regulator initial adjustment, NG, 60 Hz15.9mm
OtherSpecific gravity temperature correction0.007SG per 10 °C (18 °F)subtract above 25 °C (77 °F), add below
OtherSpecific gravity, at end of charge, ambient frequently above 32 °C (90 °F)1.240 - 1.260SG
OtherSpecific gravity, at end of charge, ambient normally below 32 °C (90 °F)1.240SG
OtherSpecific gravity, electrolyte for filling new cells, ambient frequently above 32 °C (90 °F)1.270 - 1.290SG
OtherSpecific gravity, electrolyte for filling new cells, ambient normally below 32 °C (90 °F)1.270SG
OtherStart Delay0 - 300secondsdefault = 0
OtherStarting crank/rest cycle defaults3 start cycles of 15 seconds cranking and 15 seconds rest (configurable 1-7)
OtherStarting cycles (crank/rest)3start cyclesdefault: 3 cycles composed of 15 seconds of cranking and 15 seconds of rest
OtherStop Delay0 - 600secondsdefault = 0
OtherSwitched B+ fused output5amps, 12/24 voltactivated on run command
OtherTime Delay To Stop0 - 600seconds
OtherTime delay to start0-300secondsdefault 0
OtherTime delay to stop0-600secondsdefault 0
OtherVoltage adjust range+/-5percentnominal voltage
OtherWarm-up at idle time delay0 - 300seconds
OtherWarm-up at idle time delay0-300seconds
PressureConcrete compressive strength for seismic anchors4000PSI
PressureExhaust Backpressure (Max. Allowed)25inch H2O (6.25 kPa)maximum
PressureExhaust Backpressure (max allowed)20inch H2O (5.0 kPa)
PressureExhaust backpressure (max. allowed)20inch H2O (5.0 kPa)

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Recommended fluids

FluidGradeStandardAmbientCapacityNotes
Coolant50% Ethylene Glycol and waterFleetguard® Compleat ES low-silicate antifreeze, or equivalentStandard concentration 50% Ethylene Glycol and water; must be maintained. Fill cooling system to the bottom of the fill neck in the radiator or expansion tank. Some radiators have two fill necks, both must be filled.
Coolant50/50 coolant solution (50% pure water, 50% antifreeze)32.2 LCapacity with standard radiator 8.5 Gal (32.2 L). If temperatures below -37°F (-38°C) possible, use 65% antifreeze / 35% water. Do not use antifreeze with anti-leak additives. Use soft, low-mineral water.
Coolant50/50 coolant solution (50% pure water, 50% antifreeze); 65% antifreeze/35% water if below -37°F (-38°C)33.1 LCooling system capacity with standard radiator 8.8 Gal (33.1 L). Use clean, low-mineral soft water free of chloride, sulfate or acid. Do not use antifreeze containing anti-leak additives.
Coolant50/50 water/antifreeze (65% antifreeze/35% water below -37F/-38C); no anti-leak additivesabove -38°C8.8 Gal (33.1 L)Use soft water low in mineral content.
Coolant50/50 coolant solution (50% pure water and 50% anti-freeze)above -37°C32.2 LCooling system capacity with standard radiator 8.5 Gal (32.2 L). If temperatures below -37 deg F (-38 deg C) are possible, use 65% antifreeze / 35% water. Do not use an antifreeze containing anti-leak additives. Use clean soft water low in mineral content.
Coolant50/50 coolant solution (50% pure water and 50% antifreeze)Do not use antifreeze containing anti-leak additives; use soft, low-mineral waterabove -37°C33.1 LIf temperatures below -37 F (-38 C) are possible use 65% antifreeze and 35% water. Cooling system capacity with standard radiator 8.8 Gal (33.1 L).
Engine oilHigh-quality multi-viscosity lubricating oil such as Cummins Premium Blue® or its equivalentConsult your authorized distributor for correct lubricating oil specifications for your operating conditions. Special running-in oils are not recommended.
Engine oilRefer to oil viscosity chart (Figure 5-1)API SJ or SJ/CD6.2 LSelect grade right for the lowest ambient temperature expected.
Engine oilSAE 10W30, 5W30, 15W40API classification SJ, SH or SL6.2 LOil capacity with filters 6.5 Qts (6.2 L). Select viscosity grade for lowest expected temperature; if ambient is consistently below -13°F (-25°C), use a SAE 5W synthetic oil. Do not use oil that is too thick.
Engine oilSAE 10W30, SAE 5W30, SAE 15W40API classification SJ, SH or SL6.2 LStandby Power oil capacity 6.5 Qts (6.2 L) with normal oil filter; Prime Power 11 Qts (10.4 L) with heavy duty oil filter. If ambient temperature is consistently below -13 deg F (-25 deg C), use a SAE5W synthetic oil. Select grade for the lowest expected temperature.
Engine oilSAE 5W synthetic (if ambient consistently below -13°F/-25°C)API classification SJ or SJ/CD6.2 LSelect viscosity grade per ambient temperature chart (Figure 5-1); oil capacity with filters 6.5 Qts (6.2 L).
Engine oilAPI SJ, SH or SL; SAE 10W30, 5W30 or 15W40 per ambient temperature chartAPIabove -25°C6.5 Qts (6.2 L)Use SAE5W synthetic oil if ambient temperature is consistently below -13F (-25C).
Engine oilSAE 5W syntheticAPI SJ or SJ/CDabove -25°C6.2 LUse SAE 5W synthetic if ambient temperature is consistently below -13 F (-25 C). Pick viscosity grade for lowest temperature expected. Oil capacity with filters 6.5 Qts (6.2 L).
FuelNatural Gas and/or Propane (LPG, liquid or vapor withdrawal)Combination natural gas/LPG sets have separate shutoff solenoid valves and a fuel pressure switch for automatic changeover.
FuelNatural Gas and/or Propane (LPG, liquid or vapor)Gaseous fuel; engine has a gas mixer serving both fuels with separate shutoff solenoid valves and pressure switch for automatic changeover.
FuelNatural Gas and/or Propane (Liquid or Vapor)Fuel inlet pressure min 7.0 inch H2O NG/LPG; max 13.6 inch H2O NG/LPG vapor withdrawal, 312 psi LPG liquid withdrawal
FuelPropane (Liquid or Vapor); Natural Gas
FuelPropane (liquid or vapor) / Natural GasFuel flow inlet pressure min 7.0 inch H2O (1.7 kPa) NG/LPG; max 13.6 inch H2O (3.4 kPa) NG/LPG vapor withdrawal; max 312 psi (2,153 kPa) LPG liquid withdrawal.

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Fault codes

80
CodeNameMeaningSeverityAction
121Speed Signal LostCategory AShutdown
135Oil Pressure Sensor HCategory CWarning
141Oil Pressure Sensor LCategory CWarning
143Pre-Low Oil PresCategory DWarningIf generator is powering critical loads and cannot be shut down, wait until next shutdown period and then follow code 415 procedure.
144Coolant Sensor HighCategory CWarning
145Coolant Sensor LowCategory CWarning
146Pre-High Coolant TempCategory DWarningReduce load if possible by turning off non-critical loads; check air inlets/outlets for obstructions. If engine can be stopped, follow code 151 procedure.
151High Coolant TempCategory DShutdownAllow engine to cool. Check coolant level and leakage points, obstructions to cooling airflow, fan belt, blower fan/circulation pumps; reset control and restart.
197Low Coolant LevelCategory D (optional)WarningIf generator is powering critical loads and cannot be shut down, wait until next shutdown period, then follow code 235 procedure.
234OverspeedCategory AShutdown
235Low Coolant LevelCategory D (optional)ShutdownAllow engine to cool. Check coolant level and replenish, look for leakage points and repair; reset control and restart.
359Fail To StartCategory DShutdownOpen any closed fuel shutoff valve; check for dirty/plugged air filter and replace if necessary; check gaseous fuel delivery; reset control and restart.
415Low Oil PressureCategory DShutdownCheck oil level, lines and filters; replenish oil if low; reset control and restart.
441Low Bat VoltageCategory DWarningCheck/recharge/replace discharged or defective battery; clean and tighten battery cable terminals; check battery charger float level.
442High Bat VoltageCategory DWarningCheck float level on battery charger if applicable (lower float level).
1123Shutdown After BSCategory AShutdown
1124Delayed ShutdownCategory EWarning
1131Battle Sh ActiveCategory EWarning
1311Customer Input #1Category EProgrammable via InPower service tool: enable/disable, status (warning/shutdown/none), active open/closed, and display name.
1312Customer Input #2Category EProgrammable via InPower service tool: enable/disable, status (warning/shutdown/none), active open/closed, and display name.
1313-1316Network Fault 1 thru 4Category E
1317Customer Input #3Category EProgrammable via InPower service tool: enable/disable, status (warning/shutdown/none), active open/closed, and display name.
1318Service EngineCategory B (begin spec J)WarningIndicates emissions criteria might not be met: engine running in open loop, lean mixture, rich mixture, or failed fuel system component.
1334Crit Scaler ORCategory AShutdown
1335Noncrit Scaler ORCategory BWarning
1416Fail To ShutdownCategory CWarning
1417Powr Down ErrorCategory DWarningIndicates controller cannot power down because of unknown condition; possible battery drain. Contact an authorized service center.
1433Emergency StopCategory DShutdownPull emergency stop button out; move O/Manual/Auto switch to O; press Fault Acknowledge/Reset button; select Manual or Auto as required.
1434Remote E-StopCategory DShutdownSee code 1433 to reset.
1435Low Coolant TempCategory DWarningCheck coolant heater power connection/fuse; check for low coolant level and replenish, repairing leaks as needed.
1438Fail To CrankCategory DShutdownPossible fault with control, speed sensing or starting system. See code 441 for corrective action.
1442Weak BatteryCategory DWarningBattery voltage at/below weak-battery trip point during cranking. See code 441 for corrective action.
1443Battery FailedCategory DShutdownDead battery, engine will not start. See code 441 for corrective action.
1444KW OverloadCategory BWarning
1445Short CircuitCategory AShutdown
1446High AC VoltageCategory AShutdown
1447Low AC VoltageCategory AShutdown
1448Under FrequencyCategory DShutdownCheck for dirty/plugged air filter and replace; check by disconnecting load and restarting; fuel system may require adjustment; check gaseous fuel delivery; reset and restart.
1449Over FrequencyCategory AWarning
1452Gen CB Not CloseCategory AWarning
1453Gen CB Not OpenCategory AWarning
1459Reverse PowerCategory AShutdown
1461Loss Of FieldCategory AShutdown
1466Modem FailureCategory CWarning
1468Network ErrorCategory CWarning
1469Speed/Hz MatchCategory AShutdown
1471Over CurrentCategory BWarning
1472Over CurrentCategory AShutdown
1477Over CurrentOver CurrentShutdown
2263Battery TemperatureBattery temperature too high (reaches 55 °C [131 °F]) - battery charger fault messageWarning
2323-2326Network Fault 5 thru 8Category E
2327PTC FaultCategory BWarning
2329Low S1 FrequencyCategory EWarning
2331Low S1 VoltageCategory EWarning
2335Excitation FaultCategory AShutdown
2336Memory ErrorCategory AShutdown
2337Pwr Tran DisabledCategory CWarning
2338Pwr Tran FailureCategory CWarning
2339Pwr Down EnabledCategory EWarning
2341High Control TempCategory BWarning
2342Too Long In Idle (10 min.)Category EWarningIndicates genset has been in Idle mode too long (10 minutes maximum).
2358High S1 VoltageCategory EWarning
2396S1 CB Not CloseCategory EWarning
2397S1 CB Not OpenCategory EWarning
2966PTC TimeoutCategory CWarning
2967Governor FaultCategory CWarning
2968AVR FaultCategory CWarning
2969LON FailureCategory CWarning
2972Field OverloadCategory AShutdown
Fault 1Fault 1 (red)Engine shut down because of a system fault; part of a 10-second time-delay shutdown circuit (customer-wired).Shutdown
FAULT 1FAULT 1Red lamp indicates an undedicated fault; may be field programmed as shutdown or non-shutdown and as timed or non-timed (normally set for timed shutdown).ShutdownNature of fault determined when set installation is designed.
Fault 2Fault 2 (red)Engine shut down because of a system fault; part of a non-time-delay shutdown circuit (customer-wired).Shutdown
FAULT 2FAULT 2Red lamp indicates same features as Fault 1 (normally set for non-timed shutdown).ShutdownNature of fault determined when set installation is designed.
HI ENG TEMPHI ENG TEMPRed lamp indicates engine has shut down because of critically high engine temperature (above 230 F / 110 C).ShutdownAllow engine to cool; check coolant level and airflow; reset control and restart.
High Engine TemperatureHigh Engine Temperature (red)Engine shut down due to excessively high coolant temperature (greater than 230°F / 110°C).Shutdown
LO FUELLO FUELYellow (optional) lamp indicates fuel supply pressure is marginally low (5 inches [127 mm] WC or less).WarningCheck for partially closed shutoff valve or empty propane supply tank; for natural gas check with the gas utility.
LO OIL PRESLO OIL PRESRed lamp indicates engine has shut down because of critically low oil pressure (below 25 psi / 172.4 kPa).ShutdownCheck oil level, lines and filters; replenish if low; reset control and restart.
LOW ENG TEMPLOW ENG TEMPYellow lamp lights if engine temperature is marginally low for starting (70 F / 21 C or lower); may indicate an inoperative coolant heater.WarningCheck coolant heater operation, power supply, fuse/cord and coolant level.
Low Engine TemperatureLow Engine Temperature (yellow)Engine temperature less than 65°F (18°C) or 90°F (32°C); possibility engine might not start.Warning
Low FuelLow Fuel (yellow, optional)Fuel supply pressure is 5 inches (127 mm) WC or less; also indicates operation on secondary fuel supply for dual-fuel sets.Warning

Showing the first 80 of 93 codes.

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Procedures

12
Adjusting Values/Parameters (Adjust Menu) adjustment

Tools: InPower Service Tool

  1. Press the button next to the arrow symbol until the + and - symbols are displayed.
  2. If necessary, press the button next to the symbols to move to the numeric character to change.
  3. Press + to increase the value or select parameter; press - to decrease or select parameter.
  4. Press the arrow symbol to save changes (cursor on last numeric character when adjusting values).
Gaseous Fuel Adjustments adjustment

⚠ Fuel is highly flammable; do not allow cigarettes, flame, pilot lights, arcing switches or equipment in area or areas sharing ventilation.

Tools: Exhaust gas analyzer (for emission sensitive areas)

  1. Start the engine and let set warm up under partial load (at least 1/4 rated load); start with natural gas if dual fuel.
  2. Connect full rated load and turn power adjust valve to full-rich.
  3. Slowly turn adjust valve towards lean until engine begins to lose speed, then back towards rich until engine carries full load smoothly.
  4. If equipped for natural gas and LPG, switch to LPG by closing manual shutoff valve in the natural gas supply line.
  5. Reconnect full rated load and turn LPG flow adjustment valve clockwise until engine loses speed, then slowly back counterclockwise until engine carries full load smoothly.
Gaseous Fuel System Adjustment adjustment

⚠ Fuel is highly flammable and may cause severe personal injury and property damage. Do not allow cigarettes, flame, pilot lights, arcing switches or equipment in area or areas sharing ventilation.

Tools: Exhaust gas analyzer (for emission sensitive areas)

  1. Start the engine and let the set warm up under a partial load (at least 1/4 rated load); on dual fuel sets start with natural gas.
  2. Connect full rated load and turn the manual fuel valve two turns counterclockwise.
  3. Slowly turn the manual fuel valve clockwise (lean) until the engine begins to lose speed.
  4. Slowly turn it counterclockwise (rich) until the engine carries the full load smoothly.
  5. On dual fuel sets, switch to LPG by closing the manual shutoff valve in the natural gas supply line.
  6. Reconnect full rated load and turn the LPG flow adjustment valve clockwise until the engine begins to lose speed.
  7. Slowly turn it back counterclockwise until the engine carries full load smoothly.
Gaseous Fuel System Adjustments adjustment

⚠ Fuel is highly flammable and may cause severe personal injury and property damage. Do not allow cigarettes, flame, pilot lights, arcing switches or equipment in area or areas sharing ventilation.

Tools: exhaust gas analyzer (for emission sensitive areas)

  1. Start the engine and let the set warm up under a partial load (at least 1/4 rated load). Start with natural gas if dual fuel.
  2. Connect full rated load and turn the power adjust valve two turns counterclockwise.
  3. Slowly turn the manual fuel valve clockwise (lean) until the engine begins to lose speed.
  4. Slowly turn counterclockwise (rich) until the engine carries full load smoothly.
  5. If dual fuel, switch to LPG by closing the manual shutoff valve in the natural gas supply line.
  6. Reconnect full rated load and turn the LPG flow adjustment valve clockwise until the engine begins to lose speed.
  7. Slowly turn it back counterclockwise until the engine carries full load smoothly.
Magnetic Speed Pickup Unit Adjustment adjustment
  1. Measure MPU resistance; replace if not between 1,000 and 1,050 ohms.
  2. With MPU removed, rotate ring gear until a tooth lines up in the center of the mounting hole.
  3. Thread pickup in gently by hand until it just touches the ring gear tooth.
  4. Back the pickup out 1/4 turn and set the locknut.
  5. Verify MPU output voltage at cranking speed is at least 1.5 VAC; replace MPU if less.
Output Voltage Adjustment adjustment
  1. Adjust output voltage plus or minus five percent of nominal voltage using the Voltage Adjust rheostat (optional) on the control panel.
  2. Call your distributor if the required voltage cannot be obtained by this adjustment.
Type A Gaseous Fuel Adjustment (Naturally Aspirated) adjustment

⚠ Gaseous fuels are flammable and explosive

  1. Disconnect all loads, shut down set, and disconnect governor linkage at the carburetor.
  2. Start engine and hold throttle closed by hand to prevent overspeed.
  3. Adjust throttle idle position screw to obtain a frequency of 25-35 Hz.
  4. Turn idle adjusting screw counterclockwise until engine becomes unstable, then clockwise to regain stability.
  5. Reconnect governor linkage.
  6. Connect full rated load and turn main fuel valve to full-rich, then lean until engine loses speed, then back to rich.
  7. If equipped for LPG, switch to LPG and adjust LPG flow valve similarly under full load.
Vibration Isolator Installation and Adjustment Procedure adjustment
  1. Place vibration isolators on the generator set support structure; shim or grout so all isolator bases are within 0.25 inch (6 mm) elevation of each other.
  2. Loosen the side snubber lock nuts so the top plate is free to move vertically and horizontally; verify alignment with base and springs.
  3. Place the generator set onto the isolators while aligning the skid mounting with the threaded isolator hole.
  4. Adjust isolators with the leveling bolt to level the set; nominal clearance between top plate and base is 0.25 inch (6 mm) or greater.
  5. If radiator and engine/alternator are mounted on separate skids, make both skids level for proper fan belt alignment.
  6. If the set is not level, adjust leveling bolts until level with sufficient, roughly equal clearance on all isolators.
  7. Lock the leveling bolt in place with the lock nut.
  8. Leave snubber nuts loose to provide better isolation between the generator set and support structure.
Checking AC Electric System While Running diagnostic

⚠ High voltages are present inside the control box and generator output box when the set is running. Do not open the boxes while the set is running.

  1. Check the frequency meter; generator frequency should be stable and match the nameplate rating.
  2. Turn the phase selector switch to each line-to-line phase selection (L1-L2, L2-L3, L3-L1) and read the AC voltmeter; at no load voltage should match nameplate rating.
  3. Turn the phase selector switch to each phase (L1, L2, L3) and read the AC ammeter; at no load current should be zero.
  4. Push the Reset/Lamp switch; all indicator lamps should light, confirming all bulbs are on.
  5. Have any burned out bulbs replaced.
Verify Overspeed Fault Detection diagnostic

Tools: special tool P/N 420-0604

  1. For Type A sets, move the throttle lever/linkage to increase RPM to the overspeed shutdown range.
  2. For Type B sets, remove the two screws securing the throttle body cover and remove cover.
  3. Use special tool P/N 420-0604 to turn the end of the throttle shaft.
  4. With genset operating at no load, slowly rotate the shaft clockwise until RPM reaches the overspeed limit and shuts down.
  5. Replace the throttle body cover after completing the test.
AC Electrical Connections installation

⚠ Do not connect generator set directly to any building electrical system

⚠ Reconfiguring to different voltages can damage generator or windings; consult distributor

  1. Place the control panel run switch in OFF position; remove AC power from battery charger; remove negative battery cable.
  2. Install transfer switch for standby service applications.
  3. Reconfigure generator output leads on connection terminal block per Reconnection Diagram as needed for nameplate voltage.
  4. Bolt stranded load wires to the appropriate U/V/W/N terminals.
  5. Balance loads so current flow from each line terminal is within 10 percent of median value.
  6. Install current transformers (CT21/CT22/CT23) per Reconnection Diagram with dot facing toward the generator.
  7. Ground the genset to earth in one location only.
AC Voltage Reconnection installation

⚠ Reconfiguring to higher voltages can exceed winding voltage capability and damage generator

⚠ Reconfiguring to lower voltages can increase line current beyond breaker rating

  1. Check available generator output voltages and maximum current ratings on generator nameplate.
  2. Reconfigure generator output leads per Reconnection Diagram on control housing side access cover if required.
  3. Check stator lead terminal block connections and perform necessary reconnect to obtain required voltage.
  4. Route current transformers (CT1, CT2, CT3) per Reconnection Diagram, dot facing generator, current flowing into dot.

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Voltage reconnection

VoltagePhaseConnectionLeadsNotes
Current Transformer routing: CT1-U load leads (A phase), CT2-V load leads (B phase), CT3-W load leads (C phase)CT1, CT2, CT3Dot on CT must face toward generator; dual secondaries post 2 (high voltage) or post 3 (low voltage)
Generator reconnection terminal block, terminals U/V/W/N correspond to L1/L2/L3/L0U, V, W, NLoad balancing within 10 percent of median line current
Line 0 or NeutralN / N / NLoad terminal line designations
Line 1L1 / A / ULoad terminal line designations
Line 2L2 / B / VLoad terminal line designations
Line 3L3 / C / WLoad terminal line designations
TB1 Customer Faults1=Customer Fault 1, 2=Ground Fault, 3=Low Fuel, 4=Rupture Basin FaultDefault settings, beginning spec J customer input #4 not available
TB1 Customer Relays1=Common Warning, 2=Common Shutdown, 3=Not in Auto, 4=Ready to LoadDefault settings; NO contacts rated 2 amps at 30 VDC
U, V, W, N terminals correspond to L1, L2, L3, L0U=A phase (CT21), V=B phase (CT22), W=C phase (CT23)Reconnection Diagram located on upper side cover of control housing

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Parts cataloged across the Cummins/Onan V10 family

16
Part #DescriptionCategory
A034V218Filter, Air (14" x 3")Air filter
A034V042AlternatorAlternator
A034V046TensionerBelt
A034V077Belt, V-10Belt
123-2176Separater, OilOil filter
123-2248Separater, OilOil filter
928-0617PowerCommand 2100 ControllerService part / kit
A034V213TurbochargerPump
193-0499Sensor, OxygenSensor
A028X493Sender, Oil PressureSensor
A034V076Sensor, Map - TurboSensor
A034V246Sensor, OxygenSensor
167-1639Plug, Spark (Ford Part Number AGSF-22-FM1) (.035 Gap)Spark plug
A034V055Plug, SparkSpark plug
191-2213Starter (1.4kW)Starter
130-5258Thermostat (85°C) (Must Purchase F1VY-8255-A O-ring seal from Ford)Thermostat

Parts cataloged across all variants of this engine family — verify the exact part fits your specific variant and serial number before ordering.

Common questions

What is the oil capacity of the Cummins/Onan V-10 WSG-1068?

The Cummins/Onan V-10 WSG-1068 engine has an oil capacity of 6.2 liters.

Which generators use the Cummins/Onan V-10 WSG-1068 engine?

The Cummins/Onan V-10 WSG-1068 powers 4 generator set(s), including Cummins/Onan GGHE, Cummins/Onan GGHF, Cummins/Onan GGHG, Cummins/Onan GGHH.

How often should you change the oil in the Cummins/Onan V-10 WSG-1068?

The Cummins/Onan V-10 WSG-1068 oil change interval is every 250 hours.

What is a common problem with the Cummins/Onan V-10 WSG-1068 engine?

A commonly reported issue on generators using the Cummins/Onan V-10 WSG-1068 is: The engine does not crank in Run mode. Cause: The Emergency Stop switch has been used. (The switch button is lit.). Fix: Pull the Emergency Switch button. To reset the engine control, push the Run-Stop-Remote switch to Stop and the Reset switch to Reset. Then push the Run-Stop-Remote switch to Run to start the genset..