The Cummins/Onan QSX15-G9 is a 15 L 6-cylinder turbocharged and air-to-air after-cooled engine rated at 1800 rpm, producing up to 24.1 kW. It powers generator sets from Cummins/Onan, Katolight and MQ Power, including the 350DFEG, C450D6, DFE and D500FJZ4. It holds 83.3 L (22.0 gal) of oil and 24 L (6.3 gal) of coolant.
Also known as: Cummins QSX15-G9, QSX15 G-9
Part of the Cummins/Onan QSX15 engine family — 7 variants share parts & fitment.
| Oil capacity | 83.3 L |
|---|---|
| Coolant capacity | 24.0 L |
| Displacement | 15.0 L |
| Cylinders | 6 |
| Aspiration | Turbocharged and air-to-air after-cooled |
| Rated speed | 1800 rpm |
| Gross power | 24 kW |
Shared across brands: Cummins/Onan, Katolight, MQ Power
How to read your Cummins/Onan engine serial & model number →
Compiled from service & troubleshooting documentation across every generator set that uses the Cummins/Onan QSX15-G9.
| Item | Action | Hours | Months | Notes |
|---|---|---|---|---|
| Air cleaner | Check | 250 hr | 6 mo | X1; replace as necessary; refer to QSX15 engine manual |
| All hardware (fittings, clamps, fasteners, etc.) | Check | 100 hr | Daily or after 8 hours | |
| Anti-freeze and DCA concentration | Check | 250 hr | 6 mo | X1; refer to QSX15 engine manual |
| Coolant heater(s) | Check | 100 hr | Daily or after 8 hours | |
| Drive belt | Check | 250 hr | 6 mo | X1; refer to Cummins QSX15 Series Engine Operation and Maintenance Manual for interval/procedure |
| Engine oil level | Check | 8 hr | Daily or after 8 hours | |
| Fuel filter(s) | Drain | 250 hr | 6 mo | X1; refer to QSX15 engine manual |
| Genset | Inspect | 8 hr | Daily; check for oil, fuel, cooling and exhaust system leaks | |
| Radiator hoses for wear and cracks | Check | 250 hr | Daily or after 8 hours | |
| Charge Air Piping | Check | 50 hr | Weekly | |
| Coolant heater | Check | 50 hr | Weekly or after 50 hours | |
| Coolant level | Check | 50 hr | Weekly or after 50 hours | |
| Exhaust condensate trap | Drain | 100 hr | Drain water to prevent it flowing back into the engine | |
| Fuel level | Check | 50 hr | Weekly or after 50 hours | |
| Oil level | Check | 50 hr | Weekly or after 50 hours | |
| Air cleaner | Clean | 100 hr | Monthly or after 100 hours; clean if required, perform more often in dusty conditions | |
| Battery charging system | Check | 100 hr | Monthly or after 100 hours | |
| Battery electrolyte level | Check | 200 hr | Monthly or After 100 Hrs | |
| Fuel tank water and sediment | Drain | 100 hr | Monthly or after 100 hours | |
| General set inspection | Inspect | 100 hr | Monthly or after 100 hours (Table 5-1, footnote X2): check for oil, fuel, cooling and exhaust system leaks; check exhaust system audibly and visually with set running | |
| Generator air outlet | Check | 100 hr | Monthly or After 100 Hrs | |
| Radiator hoses | Check | 500 hr | 12 mo | Monthly or After 100 Hrs; check for wear and cracks |
| Starting batteries | Check | 100 hr | Check condition and terminals | |
| Air cleaner | Replace | 250 hr | Check air cleaner; replace as necessary. Refer to QSX15 manual. | |
| Crankcase oil and filter | Change | 250 hr | 12 mo | Prime power: every 6 months or 250 hours; standby: every 12 months or 250 hours, whichever comes first |
| Drive belt tension | Check | 250 hr | 6 mo | Visually check belt for wear or slippage; replace if hard or brittle |
| Engine oil and filter | Replace | 250 hr | 6 mo | X1; 6 Months or After 250 Hrs; refer to QSX15 engine manual |
| Radiator Hoses | Inspect | 250 hr | 6 mo | Check for wear & cracks |
| Water coolant filter | Replace | 250 hr | 6 mo | X1; 6 Months or After 250 Hrs |
| Air cleaner element | Change | 500 hr | 12 mo | Yearly or after 500 hours; clean if required more often |
| Coolant filter | Change | 500 hr | 12 mo | Yearly or after 500 hours; refer to engine operation and maintenance manual |
| Cooling system | Clean | 500 hr | 12 mo | Yearly or after 500 hours; drain and replace coolant mixture |
| Crankcase breather | Clean | 500 hr | 12 mo | Yearly or after 500 hours |
| Engine oil and filter | Change | 500 hr | 12 mo | Table 5-1, footnote X1 |
| Fuel filter | Change | 500 hr | 12 mo | Table 5-1, footnote X1 |
| Fuel filters | Change | 500 hr | 12 mo | Yearly or after 500 hours |
| Generator insulation resistance | Test | 500 hr | 12 mo | Follow periodically throughout life of set or if generator has set idle with no heaters; contact authorized service center |
| Water coolant filter | Change | 500 hr | 12 mo | Table 5-1, footnote X1 |
| Cooling systems | Clean | 500 hr | 12 mo | X1; 1 Year |
| Fuel filter | Replace | 12 mo | X1; 1 Year |
Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.
| Type | Item | Value | Unit | Condition |
|---|---|---|---|---|
| Clearance | Exhaust pipe clearance from combustible wall or partition | 12 | inches (305 mm) | minimum |
| Clearance | Exhaust pipe clearance to combustible wall or partition | 305 | mm | |
| Clearance | Exhaust pipe clearance to combustible wall/partition | 12 | inches (305 mm) | |
| Clearance | Float switch assembly float lift clearance below C-clip stop | 1/8 | inch (3 mm) | use a feeler gauge |
| Clearance | Fuel line clearance from electrical wiring | 1/2 | inch (12.7 mm) | |
| Clearance | Fuel line clearance from hot exhaust parts | 2 | inch (51 mm) | |
| Clearance | Fuel lines - minimum clearance from electrical wiring | 12.7 | mm | |
| Clearance | Fuel lines - minimum clearance from hot exhaust parts | 51 | mm | |
| Clearance | Generator mount pre-load steel spacer thickness | 1 3/4 | inch | two spacers under both stator foot brackets |
| Clearance | Generator-to-engine angular alignment (T.I.R.) | .001 in. per inch of radius (center of shaft to indicator axis), maximum | in | 750 kW gensets and larger |
| Clearance | MPU installation gap adjustment | back out 1/4 turn after touching gear tooth | turn | |
| Clearance | Minimum clearance of fuel lines from electrical wiring | 12.7 | mm (1/2 inch) | |
| Clearance | Minimum clearance of fuel lines from hot exhaust parts | 51 | mm (2 inch) | |
| Clearance | Service/maintenance access clearance around generator set | 1 | meter | |
| Clearance | Vibration isolator base elevation difference | 0.25 | inch (6 mm) | shimmed or grouted within this of each other |
| Clearance | Vibration isolator clearance | 0.25 | inch (6 mm) | |
| Clearance | Vibration isolator nominal clearance (leveling bolt) | 0.25 | inch (6 mm) | minimum, or greater |
| Gap | Coolant level below radiator cap lower sealing surface | 3/4 inch (18 mm) | inch (mm) | |
| Other | AVR Droop setting | 5 | % at full load, 0 PF | |
| Other | AVR voltage regulation (load regulation) | approximately ±0.5 | % RMS | |
| Other | Ambient temperature below which coolant heaters recommended (NFPA 110) | 40 | °F | |
| Other | Battery CCA (minimum) | 1400 | CCA | Cold Soak @ 0° F (-18° C) |
| Other | Battery specific gravity (fully charged) | 1.26 | specific gravity | at 80 F (27 C) |
| Other | Battery specific gravity (high ambient, above 95F/35C) | 1.225 | recommended to reduce electrolyte loss | |
| Other | Battery specific gravity (recharge threshold) | below 1.260 | ||
| Other | Battery specific gravity charge threshold | 1.215 | corrected | charge battery if reading below |
| Other | Battery specific gravity fully charged | 1.260 | corrected | add 0.004 per 10 F above 80 F (27 C) |
| Other | Battery terminal cleaning solution | 1/4 pound baking soda to 1 quart water | ||
| Other | CAN datalink main trunk maximum length | 40 | meters | no more than 30 devices |
| Other | CAN datalink stub maximum length | 1 | meter | stub from main trunk to each module |
| Other | CAN datalink transmission speed | 250 | KBaud | |
| Other | Charge battery if specific gravity below | 1.215 | specific gravity | |
| Other | Exhaust flow at rated load | 2900 | cfm (1370 L/s) | 1500 RPM |
| Other | Exhaust flow at rated load | 3200 | cfm (1510 L/s) | 1800 RPM |
| Other | Exhaust outlet size | 4 | in. NPD | |
| Other | Fully charged battery corrected specific gravity | 1.260 | specific gravity | corrected reading @ 80 F (27 C) |
| Other | GOV GAIN default value for paralleling applications | 70 | % | |
| Other | Mounting bolt size | 5/8 | inch or 16 mm | |
| Other | Mounting bolt size securing bedframe to base | 16 | mm | |
| Other | Mounting bolts | 5/8 inch or 16 mm | inch / mm | anchored mounting bolts |
| Other | Output frequency adjustment (PCC) | +/- 5 | % | set running under normal parameters |
| Other | Over current warning threshold | 110 | % of rated | |
| Other | Over/Under Frequency Sensor Module - Over Hz Set, 50 Hz nominal | 55 | Hz | reset 53 Hz |
| Other | Over/Under Frequency Sensor Module - Over Hz Set, 60 Hz nominal | 65 | Hz | reset 63 Hz |
| Other | Over/Under Frequency Sensor Module - Under Hz Set, 50 Hz nominal | 45 | Hz | reset 47 Hz |
| Other | Over/Under Frequency Sensor Module - Under Hz Set, 60 Hz nominal | 55 | Hz | reset 57 Hz |
| Other | Over/Under Voltage Sensor Module time delay | typically 25 percent, approximately 2.5 | seconds | |
| Other | Overcrank cranking limit | 75 | seconds | three 15-second cranking cycles with two 15-second rest periods |
| Other | REG VHZ (underfrequency roll-off) adjustable range | 1 through 50; normal range 7 through 21 | ||
| Other | Short circuit shutdown threshold | 175 | % of rated current | |
| Other | Specific gravity correction | 0.004 | gravity point per 10 F above 80 F (27 C) | |
| Other | Start delay adjustment range | 0 to 300 | seconds | |
| Other | Start delay adjustment range (PCC) | 0 to 300 | seconds | Auto mode remote starting |
| Other | Stop delay adjustment range | 0 to 600 | seconds | |
| Other | Stop delay adjustment range (PCC) | 0 to 600 | seconds | Auto mode remote stopping |
| Other | Under Frequency Roll Off (UFRO) knee point, 50 Hz units | 48 to 49 | Hz | |
| Other | Under Frequency Roll Off (UFRO) knee point, 60 Hz units | 58 to 59 | Hz | |
| Pressure | Air cleaner element cleaning compressed air pressure | 30 | psi (207 kPa) | nozzle held at least 1 inch (25 mm) away |
| Pressure | Engine oil pressure (displayed example) | 75 | PSI | |
| Pressure | Engine oil pressure - K19 normal | 50-70 | psi (345-482 kPa) | run mode |
Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.
| Fluid | Grade | Standard | Ambient | Capacity | Notes |
|---|---|---|---|---|---|
| Coolant | Refer to Cummins QSX15 Series Engines Operation and Maintenance Manual for coolant recommendations/specifications | 58.0 L | Cooling System (Capacity Std. Radiator) printed as 15.3 Gal (58 L); check anti-freeze and DCA concentration | ||
| Coolant | Balanced coolant mixture of water and antifreeze | Refer to Cummins engine Operation and Maintenance Manual | 90.0 L | Capacity with standard radiator 24 Gal (90 L); drain and replace mixture every year or after 500 hours; add until 3/4 inch (18 mm) below radiator cap lower sealing surface | |
| Coolant | soft water / E.G. / DCA mixture | Cooling system to be filled with soft water/E.G./DCA mixture (on-site review checklist). | |||
| Engine oil | Refer to Cummins QSX15 Series Engines Operation and Maintenance Manual for lubricating oil classification/viscosity | 58.0 L | Oil Cap. w/Filters printed as 26 Gallons (58 L); gense is shipped filled with correct type and quantity of oil | ||
| Fuel | ASTM No. 2 diesel | Cummins engines normally use ASTM No. 2 diesel fuel. | |||
| Fuel | Diesel | Day tank fuel transfer pump maintains reservoir of diesel fuel in the day tank. | |||
| Fuel | Diesel fuel specified to ASTM No. 2 or BS EN 590:2000, Automotive fuels | ASTM No. 2 / BS EN 590:2000 | An electric solenoid valve in the supply line is recommended for all installations and required for indoor automatic or remote starting installations. Never use galvanized or copper fuel lines, fittings or fuel tanks. | ||
| Fuel | diesel | ASTM No. 2 or BS EN 590:2000 | Cummins engines normally use a diesel fuel specified to ASTM No. 2 or BS EN 590:2000; alternate diesel fuels within the specifications shown in the Generator Set Operator Manual (0908-0219) | ||
| Grease | Lithium based grease, Mobilux No. 2 or Shell Alvania R3 | -30°C to 120°C | 2.74 oz (81 ml) | End bearing lubricant; grease equally divided between bearing, bearing cap cavity and bearing cartridge cavity. | |
| Other | Donaldsons D1400 solvent | Soak air cleaner filter element at least 15 minutes in water and D1400 solvent to remove soot, carbon and dirt |
Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.
| Code | Name | Meaning | Severity | Action |
|---|---|---|---|---|
| 101 | IDLE MODE | Indicates that the engine is operating in idle mode. Grounding the engine idle input causes generator build-up to be inhibited and the engine to be governed at 800 RPM. | Warning | Remove ground from engine idle input to return to normal speed and voltage. |
| 102 | EMERGENCY STOP | Local or remote Emergency Stop; engine shuts down and will not crank | Shutdown | Turn the switch clockwise and allow it to pop out (local only). Move the Run/Off/Auto switch to Off. Press the Reset switch. Select Run or Auto, as required. |
| 111 | Internal ECM error | Internal ECM error | Shutdown | |
| 1118 | Prelube relay driver | Warning | ||
| 112 | Actuator not responding | Category A | Shutdown | |
| 1121 | Failed to Disconnect | Warning | ||
| 1122 | Rated/Idle Trans | Info | ||
| 1123 | Shutdown After Battle Short | A shutdown fault occurred while Battle Short was enabled and Battle Short transitioned from enabled to disabled | Warning | Review the Fault History and perform corrective action |
| 1124 | Delayed Shutdown | Provides advanced warning of an impending generator set shutdown to loads which cannot handle sudden power loss | Warning | A shutdown fault is present; review fault history |
| 113 | Actuator sensor fault | Category B | Warning | |
| 1131 | Battle Short Active | Battle short mode has been activated | Warning | Battle short function enabled |
| 115 | No speed signal | No speed signal | Shutdown | |
| 116 | Time press sensor high | Time press sensor high | Shutdown | |
| 117 | Time press sensor low | Time press sensor low | Shutdown | |
| 118 | Pump press sensor high | Pump press sensor high | Warning | |
| 119 | Pump press sensor low | Pump press sensor low | Warning | |
| 121 | Speed Signal Lost | No engine speed signal | Warning | |
| 1219 | Utility CB tripped | Warning | ||
| 122 | Manifold air press sensor | Manifold air press sensor | Warning | |
| 1222 | Power transfer not in auto | Warning | ||
| 1223 | Utility frequency sensor | Warning | ||
| 1224 | Gen over voltage sensor | Warning | ||
| 1225 | Gen under voltage sensor | Warning | ||
| 1226 | genset frequency sensor | Warning | ||
| 123 | Manifold air press sensor | Manifold air press sensor | Warning | |
| 1245 | CAN - Engine Shutdown | The PCC received a shutdown message from the ECM | Shutdown | Refer to the E-Controls service tool and the engine service manual |
| 1246 | CAN - Unknown Engine Fault | The PCC received an unknown message from the ECM | Warning | Refer to the E-Controls service tool and the engine service manual |
| 1247 | CAN - Engine Unannounced Fault | The PCC received an unknown message from the ECM | Warning | Refer to the E-Controls service tool and the engine service manual |
| 1248 | CAN - Engine Warning Fault | The PCC received an unknown message from the ECM | Warning | Refer to the E-Controls service tool and the engine service manual |
| 1311 | Customer input #1 | Optional customer-selected fault, e.g. Low Fuel Day Tank, Water In Fuel, Ground Fault, Low Starting Hydraulic/Air Pressure | Programmable via service tool: enable/disable, status/warning/shutdown, active closed/open, custom display name | |
| 1311, 1312, 1317, 1318 | Customer Input | Nature of the fault is an optional customer selection | Disconnect signal lead from TB1 (CUST_IN1 TB1-4, CUST_IN2 TB1-5, CUST_IN3 TB1-6, CUST_IN4 TB1-7) and reset the control; if the message clears, external wiring has a short/open or the active input selection (closed/open) is not correct | |
| 1312 | Customer input #2 | Optional customer-selected fault | Customer defined fault; message editable by the customer; can be programmed to initiate a shutdown or warning. | |
| 1313 | Network Fault 1 thru 4 | Network Fault 1 | Customer defined fault; message editable by the customer; can be programmed to initiate a shutdown or warning. | |
| 1313-1316 | Network Fault 1 Through 4 | Indicates network input (#1-#4) is in an active state | Each fault function can be programmed (using the service tool) as Status, Warning, or Shutdown; change display name using up to 19 characters | |
| 1314 | Network Fault 2 | Network Fault 2 | Customer defined fault; message editable by the customer; can be programmed to initiate a shutdown or warning. | |
| 1315 | Network Fault 3 | Network Fault 3 | Customer defined fault; message editable by the customer; can be programmed to initiate a shutdown or warning. | |
| 1316 | Network Fault 4 | Network Fault 4 | Customer defined fault; message editable by the customer; can be programmed to initiate a shutdown or warning. | |
| 1317 | Customer input #3 | Customer input #3 | Customer defined fault; message editable by the customer; can be programmed to initiate a shutdown or warning. | |
| 1318 | Customer input #4 | Customer input #4 | Customer defined fault; message editable by the customer; can be programmed to initiate a shutdown or warning. | |
| 1319 | High alternator temp | High alternator temp | Warning | |
| 1321 | Common warning driver | Common warning driver | Warning | |
| 1322 | Load gov kW setpoint oor hi | Load gov kW setpoint oor hi | Shutdown | |
| 1323 | Load gov kW setpoint oor lo | Load gov kW setpoint oor lo | Shutdown | |
| 1324 | Load gov kVAR oor hi | Load gov kVAR oor hi | Warning | |
| 1325 | Load gov kVAR oor lo | Load gov kVAR oor lo | Warning | |
| 1326 | Backup starter disconnect | Category B | Warning | |
| 1327 | Load gov kW analog oor | Load gov kW analog oor | Shutdown | |
| 1328 | Genset CB tripped | Genset CB tripped | Warning | |
| 1329 | AVR DC power failure | Category B | Warning | |
| 1331 | AVR driver shorted | Category A | Shutdown | |
| 1332 | Manual switch oor lo | Manual switch oor lo | Shutdown | |
| 1333 | Manual switch oor hi | Manual switch oor hi | Shutdown | |
| 1334 | Critical scaler oor | Critical scaler oor | Shutdown | Correct the feature/calibration entered into the control |
| 1335 | Noncrit Scaler Out Of Range | Non critical scaler oor | Warning | Correct the feature/calibration entered into the control |
| 1336 | Cooldown complete | Cooldown complete | Shutdown | |
| 1337 | No Message | Network wink | Info | |
| 1341 | Load demand stop | Load demand stop | Shutdown | |
| 1342 | Slot 0 card | Slot 0 card | Shutdown | |
| 1343 | Slot 1 card | Slot 1 card | Shutdown | |
| 1344 | Slot 2 card | Category A | Shutdown | |
| 1345 | Slot 3 card | Slot 3 card | Shutdown | |
| 1346 | Slot 4 incorrect | Slot 4 incorrect | Shutdown | |
| 1347 | Slot 5 card | Category A | Shutdown | |
| 1348 | Slot 6 card | Category A | Shutdown | |
| 1349 | Slot 7 card | Category A | Shutdown | |
| 135 | Oil pressure sensor | Oil pressure sensor | Warning | Verify fault simulation not enabled (InPower); inspect sensor and engine harness connector pins; use oil pressure sensor simulator to check control response, replace sensor if it responds; check P7-13, 17, 21 for short (>200k ohms OK) and open (10 ohms or less OK) |
| 1351 | Slot 4 / network enabled | Slot 4 / network enabled | Warning | |
| 141 | Oil pressure sensor | Oil pressure sensor | Warning | Verify fault simulation not enabled; inspect sensor/harness connector pins; use simulator to check control response; check P7-13, 17, 21 short/open |
| 1414 | Run relay contact | Run relay contact | Warning | |
| 1415 | Run relay driver | Run relay driver | Warning | |
| 1416 | Fail to shutdown | Fail to shutdown | Warning | Status - indicates the Fault Bypass mode is enabled (used primarily by service personnel for troubleshooting). The genset ignores the majority of system shutdown faults. |
| 1417 | Powr Down Error | The control has failed to go to sleep | Warning | Possible base board fault |
| 1419 | Fuel rail driver | Fuel rail driver | Warning | |
| 1421 | Timing rail driver #1 | Timing rail driver #1 | Warning | |
| 1422 | Timing rail driver #2 | Timing rail driver #2 | Warning | |
| 1424 | High side driver | High side driver | Warning | |
| 1427 | Overspeed relay driver | Overspeed relay driver | Warning | |
| 1428 | LOP shutdown relay driver | LOP shutdown relay driver | Warning | |
| 143 | Pre-Low Oil Pressure | Low oil pressure | Warning | Verify fault simulation not enabled; check oil level, lines and filters; use oil pressure sensor simulator; check +5 VDC at sensor (E1-A) and at P7-21; use simulator to P7-13 (OP OUT) and P7-17 (OP COMM); isolate to harness or base board |
| 1433 | Emergency stop - local | Local Emergency Stop | Shutdown | Pull the Emergency stop button out; move the O/Manual/Auto switch to O; press the front panel Fault Acknowledge/Reset button; select Manual or Auto as required |
Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.
⚠ Accidental starting of the generator set during this procedure presents the hazard of severe personal injury or death.
Tools: Dial indicator, Shims
⚠ Accidental starting during this procedure presents the hazard of severe personal injury or death.
⚠ Do not bar engine over by prying on fan blade.
Tools: dial indicator
Tools: dial indicator holding device with magnetic base or clamp
Tools: dial indicator
⚠ Accidental starting of the generator set during this procedure presents the hazard of severe personal injury or death.
Tools: two 1 3/4 inch T x 2 inch W x 6 inch L steel spacers, adequate lifting device
Tools: calibrated voltmeter
⚠ Accidental starting can cause severe personal injury or death; disconnect negative (-) battery cable with insulated wrench.
⚠ Set generator set to off mode before disconnecting/connecting harness connectors.
Tools: True RMS meter, Insulated wrench, Jumper leads
⚠ HIGH VOLTAGE. Touching uninsulated high voltage parts inside the control box can result in severe personal injury or death.
Tools: Voltmeter, Jumpers, 12 volt battery
Tools: calibrated ammeter
⚠ Contacting high voltage components can cause electrocution, resulting in severe personal injury or death.
Tools: calibrated RMS multimeter (Fluke 87 or 8060A recommended)
⚠ The windings of medium-voltage (601 through 15,000 volts) generator sets must be dry before the generator is operated.
Tools: Megger or insulation resistance meter, Grounding cluster, High voltage gloves
⚠ Medium-voltage (601 to 15,000 volts) windings must be dry before the generator is operated.
Tools: Megger or Insulation Resistance Meter, Wheatstone bridge or digital ohmmeter, Grounding Cluster
Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.
| Voltage | Phase | Connection | Leads | Notes |
|---|---|---|---|---|
| 12 lead generator sets | Load wires are routed through the CTs | Reconnectable gensets (12 leads) have dual secondary CTs (3 pins); CT wire 2/3 to pin 2 (high voltage) or pin 3 (low voltage). | ||
| 6 lead generator sets | Generator output leads are routed through the CTs | Non-reconnectable gensets (6 leads) have single secondary CTs (2 pins). | ||
| Cummins PowerCommand generic AC Reconnect Wiring Diagram 625-2755 (Rev. D) and 625-3100 (Rev. F) | Applies to models DFAA, DFAB, DFAC, DFBF, DFCB, DFCC, DFEB, DFEC, DFFB, DFGA, DFGB, DFJA, DFJB, DFJC, DFJD, DFLB, DFLC, DFLD, DFMB (625-2755) and models DFAA-DFMB plus DFCE, DFED, DQAA, DQAB, DQBA, DQBB (625-3100). | |||
| U, V, W, N terminals (U,V,W = L1,L2,L3; N = L0) | Stranded load wires bolted to generator reconnection terminal block or circuit breaker lugs | Generators can be configured to the nameplate voltages as shown on the Reconnection Diagram decal attached to the backside of the control box cover; many voltages require reconfiguration of the generator output leads. | ||
| A (U) | CT21 | U load leads (A phase) | CT dot must face the generator; CT terminal 1 connects to metering circuit, terminal 2/3 to ground. | |
| B (V) | CT22 | V load leads (B phase) | CT dot must face the generator; terminal 1 to metering circuit, terminal 2/3 to ground. | |
| C (W) | CT23 | W load leads (C phase) | CT dot must face the generator; terminal 1 to metering circuit, terminal 2/3 to ground. |
Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.
| Part # | Description | Category |
|---|---|---|
| AF25544 | Recommended air cleaner element - (heavy duty) primary element | air_filter |
| AF25545 | Recommended air cleaner element - (heavy duty) secondary element | air_filter |
| 0908-0101 | Lead Acid Battery | battery |
| 3375044 | Torque Wrench | belt |
| 19802521 | ECM Dataplate | ecm |
| 3331096 | Cummins, Part No. 3331096 | fuel_filter |
| 3376807 | Engine coolant and fuel filter wrench | fuel_filter |
| FS1007 | Fleetguard® Nelson®, Part No. FS1007 | fuel_filter |
| M-4376220 | Juego Junta Superior N. ° de Pieza | gasket |
| M-4376221 | Juego Junta Inferior N. ° de Pieza | gasket |
| 3375049 | Oil Filter Wrench | oil_filter |
| 3406810 | Combination Full-Flow/Bypass Lubricating Oil Filter Cummins Part No. 3406810 | oil_filter |
| 0908-0203 | operator_manual | |
| 0908-0204 | operator_manual | |
| 0908-0230 | Generator Set Operator Manual | operator_manual |
| 0908-0107 | Radiator Information | other_service |
| 0908-0110 | Health and Safety (Diesel Generator Sets) | other_service |
| 0908-0219 | Alarm Module (option) | other_service |
| 17200015 | Engine Shutdown | other_service |
| 17690172 | Engine Braking System | other_service |
| 17800006 | Engine Model | other_service |
| 3163156 | Service cable for InPower™ | other_service |
| 3666423 | other_service | |
| 3822735 | Plastic bead blasting media | other_service |
| 3886301 | InPower™ electronic service tool | other_service |
| 960-0174B | other_service | |
| A035H139 | Switch, Pushbutton | other_service |
| A040U808 | Harness, Control − Door (Includes Items 30 & 31) | other_service |
| A046Y204 | Shield, Wiring | other_service |
| M-3685996 | Intake Valve | other_service |
| M-5473065 | 150mm Kit de Motor M-5473066 | other_service |
| M-5473069 | 152mm Kit de Motor M-5473070 | other_service |
| M-5473074 | Kit de Motor M-5473075 | other_service |
| TB3-5 | Generator Set Control Panel Terminal Block | other_service |
| TB3-6 | Generator Set Control Panel Terminal Block | other_service |
| ol204vt | Torque Peak | other_service |
| M-5473087 | Piston Kit | piston_kit |
| M-5484414 | Piston Pin | piston_pin |
| M-3686661 | Valvula de escape - M-3686661 | valve |
Parts cataloged across all variants of this engine family — verify the exact part fits your specific variant and serial number before ordering.
The Cummins/Onan QSX15-G9 engine has an oil capacity of 83.3 liters.
The Cummins/Onan QSX15-G9 has a displacement of 15.0 liters with 6 cylinders.
The Cummins/Onan QSX15-G9 powers 8 generator set(s), including Cummins/Onan 350DFEG, Cummins/Onan C450D6, Cummins/Onan DFE, Katolight D500FJZ4, Katolight D500FNZ4.
A commonly reported issue on generators using the Cummins/Onan QSX15-G9 is: Over Current.