Service parts for the DFE
Grouped by system, with how many of each the parts manual calls for.
Air intake
1 requiredPrices captured from merchant listings; some links are affiliate links. Confirm against your serial number before ordering.
Specifications
| Fuel | Diesel |
|---|---|
| Frequency | 60.0 Hz |
| Standby power | 500 kW |
| Standby kVA | 563 |
| Prime power | 455 kW |
| Emissions | EPA NSPS Stationary Emergency Tier 2 |
| Controller | HMI320, PowerCommand, PowerCommand (2100); PowerCommand (3200) available, PowerCommand 2.3, PowerCommand 2.3 (PCC 2300), PowerCommand 2100, PowerCommand 2100 (PCC), PowerCommand 3100 (PCC), PowerCommand 3200, PowerCommand 3200 (PCC) |
| Oil capacity | 45.0 L |
| Alternator | Stamford/AvK HC |
| Voltage options | 24 V |
| Phase | 3 |
| Rated current | 753 A |
| Power factor | 0.8 |
| Circuit breaker | 800 A |
| Battery group | 8D |
| Battery cranking | 1400 CCA |
| Battery voltage | 24 V |
| Battery quantity | 2 |
| Coolant capacity | 91 L |
| Max ambient | 40 °C |
| Dimensions (L×W×H) | 3864×1524×1812 mm |
| Dry weight | 4098 kg |
| Wet weight | 4461 kg |
| Sound level | 76.0 dBA @ 7 m |
| Fuel tank | 3218.0 L |
| Tank runtime | 25 hr |
Engine
| Oil capacity | 45.0 L |
|---|---|
| Coolant capacity | 91.0 L |
| Displacement | 18.7 L |
| Rated speed | 1800 rpm |
Filters for the Cummins/Onan KTA19
8Engine-mounted filters the filter manufacturers list for this engine family. These come from the engine, not from this generator set’s own parts list, so confirm against your serial number before ordering.
| System | Filter | Description | Cross-references | |
|---|---|---|---|---|
| Oil filter | P550777 | Lube Filter, Spin-On Bypass | CUMMINS 3021658, CUMMINS 33004232, NAPA 1749, BALDWIN B7577 | FridayParts $43.56 |
| Oil filter | P551670 | Lube Filter, Spin-On Full Flow | CUMMINS 298670, CUMMINS 299670, NAPA 1970, CARBOCOL 0026 | FridayParts $26.68 |
| Fuel filter | P550105 | Fuel Filter, Spin-On Primary | CUMMINS 154700, CUMMINS 154710, NAPA 3109, NAPA 3405 | buy |
| Fuel filter | P550104 | Fuel Filter, Spin-On | CUMMINS 127674, CUMMINS 136517, NAPA 3107, NAPA 3405 | FridayParts $143.60 |
| Fuel / water separator | P550106 | Fuel Filter, Water Separator Spin-On | CUMMINS 154789, CUMMINS 156164, NAPA 3405, BALDWIN BF957-D | FridayParts $285.60 |
| Fuel / water separator | P558000 | Fuel Filter, Water Separator Spin-On Twist&Drain | CUMMINS 3308638, CUMMINS 3308683, NAPA 3405, NAPA 3693 | KuduParts $24.00 FridayParts $25.66 |
| Coolant filter | P554071 | Coolant Filter, Spin-On | CUMMINS 209604, CUMMINS 209606, NAPA 4071, WALGAHN-MOTORENTECHN 00811412 | FridayParts $397.60 |
| Coolant filter | P554073 | Coolant Filter, Spin-On | CUMMINS 209605, CUMMINS 209607, NAPA 4073, VERSATILE 00104040 | KuduParts $40.00 |
Maintenance & consumables
for the Cummins/Onan KTA19| Item | Spec | Capacity | Part # | Interval | |
|---|---|---|---|---|---|
| Air filter | L028-2 | 500 hr | eBay | ||
| Fuel filter | New o-ring seal supplied with the new filter. For Biodiesel applications use gasket pack 3950445 S (green) and change with every filter change. | — | 500 hr | ||
| Oil filter | 885 hrs 5/13/25 | — | 500 hr | ||
| Battery | 2 8D batteries | — | 200 hr | ||
| Belt | — | 500 hr | |||
| Coolant | -35 | 90.0 | — | 500 hr | |
| Coolant filter | — | 500 hr | |||
| Oil | 88.0 L | — | 500 hr | ||
| Spark plug | — | 500 hr |
Service intervals
40| Item | Action | Hours | Months | Notes |
|---|---|---|---|---|
| Air cleaner | Check | 250 hr | 6 mo | X1; replace as necessary; refer to QSX15 engine manual |
| All hardware (fittings, clamps, fasteners, etc.) | Check | 100 hr | Daily or after 8 hours | |
| Anti-freeze and DCA concentration | Check | 250 hr | 6 mo | X1; refer to QSX15 engine manual |
| Coolant heater(s) | Check | 100 hr | Daily or after 8 hours | |
| Drive belt | Check | 250 hr | 6 mo | X1; refer to Cummins QSX15 Series Engine Operation and Maintenance Manual for interval/procedure |
| Engine oil level | Check | 8 hr | Daily or after 8 hours | |
| Fuel filter(s) | Drain | 250 hr | 6 mo | X1; refer to QSX15 engine manual |
| Genset | Inspect | 8 hr | Daily; check for oil, fuel, cooling and exhaust system leaks | |
| Radiator hoses for wear and cracks | Check | 250 hr | Daily or after 8 hours | |
| Charge Air Piping | Check | 50 hr | Weekly | |
| Coolant heater | Check | 50 hr | Weekly or after 50 hours | |
| Coolant level | Check | 50 hr | Weekly or after 50 hours | |
| Exhaust condensate trap | Drain | 100 hr | Drain water to prevent it flowing back into the engine | |
| Fuel level | Check | 50 hr | Weekly or after 50 hours | |
| Oil level | Check | 50 hr | Weekly or after 50 hours | |
| Air cleaner | Clean | 100 hr | Monthly or after 100 hours; clean if required, perform more often in dusty conditions | |
| Battery charging system | Check | 100 hr | Monthly or after 100 hours | |
| Battery electrolyte level | Check | 200 hr | Monthly or After 100 Hrs | |
| Fuel tank water and sediment | Drain | 100 hr | Monthly or after 100 hours | |
| General set inspection | Inspect | 100 hr | Monthly or after 100 hours (Table 5-1, footnote X2): check for oil, fuel, cooling and exhaust system leaks; check exhaust system audibly and visually with set running | |
| Generator air outlet | Check | 100 hr | Monthly or After 100 Hrs | |
| Radiator hoses | Check | 500 hr | 12 mo | Monthly or After 100 Hrs; check for wear and cracks |
| Starting batteries | Check | 100 hr | Check condition and terminals | |
| Air cleaner | Replace | 250 hr | Check air cleaner; replace as necessary. Refer to QSX15 manual. | |
| Crankcase oil and filter | Change | 250 hr | 12 mo | Prime power: every 6 months or 250 hours; standby: every 12 months or 250 hours, whichever comes first |
| Drive belt tension | Check | 250 hr | 6 mo | Visually check belt for wear or slippage; replace if hard or brittle |
| Engine oil and filter | Replace | 250 hr | 6 mo | X1; 6 Months or After 250 Hrs; refer to QSX15 engine manual |
| Radiator Hoses | Inspect | 250 hr | 6 mo | Check for wear & cracks |
| Water coolant filter | Replace | 250 hr | 6 mo | X1; 6 Months or After 250 Hrs |
| Air cleaner element | Change | 500 hr | 12 mo | Yearly or after 500 hours; clean if required more often |
| Coolant filter | Change | 500 hr | 12 mo | Yearly or after 500 hours; refer to engine operation and maintenance manual |
| Cooling system | Clean | 500 hr | 12 mo | Yearly or after 500 hours; drain and replace coolant mixture |
| Crankcase breather | Clean | 500 hr | 12 mo | Yearly or after 500 hours |
| Engine oil and filter | Change | 500 hr | 12 mo | Table 5-1, footnote X1 |
| Fuel filter | Change | 500 hr | 12 mo | Table 5-1, footnote X1 |
| Fuel filters | Change | 500 hr | 12 mo | Yearly or after 500 hours |
| Generator insulation resistance | Test | 500 hr | 12 mo | Follow periodically throughout life of set or if generator has set idle with no heaters; contact authorized service center |
| Water coolant filter | Change | 500 hr | 12 mo | Table 5-1, footnote X1 |
| Cooling systems | Clean | 500 hr | 12 mo | X1; 1 Year |
| Fuel filter | Replace | 12 mo | X1; 1 Year |
Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.
Service specifications
60| Type | Item | Value | Unit | Condition |
|---|---|---|---|---|
| Clearance | Angular alignment maximum T.I.R. | 0.001 | inch per inch of radius (center of shaft to indicator axis) | measuring deflection to bolt heads |
| Clearance | Exhaust pipe clearance from combustible wall or partition | 12 | inches (305 mm) | minimum |
| Clearance | Exhaust pipe clearance to combustible wall/partition | 12 | inches (305 mm) | |
| Clearance | Float switch assembly float lift clearance below C-clip stop | 1/8 | inch (3 mm) | use a feeler gauge |
| Clearance | Fuel line clearance from electrical wiring | 1/2 | inch (12.7 mm) | |
| Clearance | Fuel line clearance from hot exhaust parts | 2 | inch (51 mm) | |
| Clearance | Generator mount pre-load steel spacer thickness | 1 3/4 | inch | two spacers under both stator foot brackets |
| Clearance | Generator-to-engine angular alignment (T.I.R.) | .001 in. per inch of radius (center of shaft to indicator axis), maximum | in | 750 kW gensets and larger |
| Clearance | MPU installation gap adjustment | back out 1/4 turn after touching gear tooth | turn | |
| Clearance | Vibration isolator base elevation difference | 0.25 | inch (6 mm) | shimmed or grouted within this of each other |
| Clearance | Vibration isolator clearance | 0.25 | inch (6 mm) | |
| Clearance | Vibration isolator nominal clearance (leveling bolt) | 0.25 | inch (6 mm) | minimum, or greater |
| Gap | Coolant level below radiator cap lower sealing surface | 3/4 inch (18 mm) | inch (mm) | |
| Gap | MPU sensor to flywheel ring gear tooth | back it out one quarter turn | turn | sensor threaded in until it just touches gear tooth |
| Other | AVR Droop setting | 5 | % at full load, 0 PF | |
| Other | AVR voltage regulation (load regulation) | approximately ±0.5 | % RMS | |
| Other | Ambient temperature below which coolant heaters recommended (NFPA 110) | 40 | °F | |
| Other | Angular alignment maximum T.I.R. | .001 inches per inch of radius | in/in | center of shaft to indicator axis |
| Other | Battery CCA (minimum) | 1400 | CCA | Cold Soak @ 0° F (-18° C) |
| Other | Battery charging alternator output | 35 | Amps | |
| Other | Battery specific gravity (fully charged) | 1.26 | specific gravity | at 80 F (27 C) |
| Other | Battery specific gravity (high ambient, above 95F/35C) | 1.225 | recommended to reduce electrolyte loss | |
| Other | Battery specific gravity (recharge threshold) | below 1.260 | ||
| Other | Battery specific gravity charge threshold | 1.215 | corrected | charge battery if reading below |
| Other | Battery specific gravity fully charged | 1.260 | corrected | add 0.004 per 10 F above 80 F (27 C) |
| Other | Battery specific gravity, fully charged | approximately 1.260 | specific gravity | at 80 F (27 C) |
| Other | Battery terminal cleaning solution | 1/4 pound baking soda to 1 quart water | ||
| Other | CAN datalink main trunk maximum length | 40 | meters | no more than 30 devices |
| Other | CAN datalink stub maximum length | 1 | meter | stub from main trunk to each module |
| Other | CAN datalink transmission speed | 250 | KBaud | |
| Other | Charge battery if specific gravity below | 1.215 | specific gravity | |
| Other | Compression ratio | 17.0:1 | ||
| Other | Frequency regulation | Isochronous | ||
| Other | Fuel lift height limit | 6 | feet | (1.8 meters) between fuel lift pump and bottom of dip tube |
| Other | Fully charged battery corrected specific gravity | 1.260 | specific gravity | corrected reading @ 80 F (27 C) |
| Other | GOV GAIN default value for paralleling applications | 70 | % | |
| Other | Maximum cranking voltage drop | 2 | volts | difference between battery and starter terminals while cranking |
| Other | Mounting bolt size | 5/8 | inch or 16 mm | |
| Other | Mounting bolts | 5/8 inch or 16 mm | inch / mm | anchored mounting bolts |
| Other | Optional run/alarm relay contact rating | 10 amps at 28 VDC or 120 VAC, 80%PF; 6 amps at 240 VAC, 80%PF; 3 amps at 480/600 VAC, 80%PF | amps | |
| Other | Output frequency adjustment (PCC) | +/- 5 | % | set running under normal parameters |
| Other | Over current warning threshold | 110 | % of rated | |
| Other | Over/Under Frequency Sensor Module - Over Hz Set, 50 Hz nominal | 55 | Hz | reset 53 Hz |
| Other | Over/Under Frequency Sensor Module - Over Hz Set, 60 Hz nominal | 65 | Hz | reset 63 Hz |
| Other | Over/Under Frequency Sensor Module - Under Hz Set, 50 Hz nominal | 45 | Hz | reset 47 Hz |
| Other | Over/Under Frequency Sensor Module - Under Hz Set, 60 Hz nominal | 55 | Hz | reset 57 Hz |
| Other | Over/Under Voltage Sensor Module time delay | typically 25 percent, approximately 2.5 | seconds | |
| Other | Overcrank cranking limit | 75 | seconds | three 15-second cranking cycles with two 15-second rest periods |
| Other | Overspeed limit | 2150 ± 50 | rpm | |
| Other | REG VHZ (underfrequency roll-off) adjustable range | 1 through 50; normal range 7 through 21 | ||
| Other | Random frequency variation | ± 0.25 | % | |
| Other | Short circuit shutdown threshold | 175 | % of rated current | |
| Other | Specific gravity correction | 0.004 | gravity point per 10 F above 80 F (27 C) | |
| Other | Start delay adjustment range | 0 to 300 | seconds | |
| Other | Start delay adjustment range (PCC) | 0 to 300 | seconds | Auto mode remote starting |
| Other | Stop delay adjustment range | 0 to 600 | seconds | |
| Other | Stop delay adjustment range (PCC) | 0 to 600 | seconds | Auto mode remote stopping |
| Other | Under Frequency Roll Off (UFRO) knee point, 50 Hz units | 48 to 49 | Hz | |
| Other | Under Frequency Roll Off (UFRO) knee point, 60 Hz units | 58 to 59 | Hz | |
| Other | Under-frequency roll-off threshold (UFRO) | typically 59 Hz for 60 Hz applications and 49 Hz for 50 Hz applications | Hz | AVR UFRO pot preset |
Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.
Recommended fluids
| Fluid | Grade | Standard | Ambient | Capacity | Notes |
|---|---|---|---|---|---|
| Coolant | Refer to Cummins QSX15 Series Engines Operation and Maintenance Manual for coolant recommendations/specifications | 58.0 L | Cooling System (Capacity Std. Radiator) printed as 15.3 Gal (58 L); check anti-freeze and DCA concentration | ||
| Coolant | Balanced coolant mixture of water and antifreeze | Refer to Cummins engine Operation and Maintenance Manual | 90.0 L | Capacity with standard radiator 24 Gal (90 L); drain and replace mixture every year or after 500 hours; add until 3/4 inch (18 mm) below radiator cap lower sealing surface | |
| Coolant | soft water / E.G. / DCA mixture | Cooling system to be filled with soft water/E.G./DCA mixture (on-site review checklist). | |||
| Engine oil | Refer to Cummins QSX15 Series Engines Operation and Maintenance Manual for lubricating oil classification/viscosity | 58.0 L | Oil Cap. w/Filters printed as 26 Gallons (58 L); gense is shipped filled with correct type and quantity of oil | ||
| Fuel | ASTM D975 No. 2-D | Cetane number 40-50, 300-500 ppm Sulfur | Diesel fuel specifications | ||
| Fuel | ASTM No. 2 diesel | Cummins engines normally use ASTM No. 2 diesel fuel. | |||
| Fuel | Diesel | Day tank fuel transfer pump maintains reservoir of diesel fuel in the day tank. | |||
| Fuel | diesel | Refer to Cummins QSX15 Series Engines Operation and Maintenance Manual for fuel recommendations; do not use zinc coated or copper fuel lines with diesel fuel; keep fuel supply tanks as full as possible | |||
| Grease | Lithium based grease | Mobilux No. 2 or Shell Alvania R3 | 2.74 oz (81 ml) | Generator end bearing. Temperature range -22F to +248F (-30C to +120C). Grease should be equally divided between the bearing, bearing cap cavity, and bearing cartridge cavity. | |
| Grease | Lithium based grease, Mobilux No. 2 or Shell Alvania R3 | -30°C to 120°C | 2.74 oz (81 ml) | End bearing lubricant; grease equally divided between bearing, bearing cap cavity and bearing cartridge cavity. | |
| Other | Donaldsons D1400 solvent | Soak air cleaner filter element at least 15 minutes in water and D1400 solvent to remove soot, carbon and dirt |
Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.
Fault codes
80| Code | Name | Meaning | Severity | Action |
|---|---|---|---|---|
| 101 | IDLE MODE | Indicates that the engine is operating in idle mode. Grounding the engine idle input causes generator build-up to be inhibited and the engine to be governed at 800 RPM. | Warning | Remove ground from engine idle input to return to normal speed and voltage. |
| 102 | EMERGENCY STOP | Local or remote Emergency Stop; engine shuts down and will not crank | Shutdown | Turn the switch clockwise and allow it to pop out (local only); move the Run/Off/Auto switch to Off; press the Reset switch; select Run or Auto as required. Can be reset only at the PCC front panel. |
| 111 | Internal ECM error | Internal ECM error | Shutdown | |
| 1118 | Prelube relay driver | Warning | ||
| 112 | Actuator not responding | Category A | Shutdown | |
| 1121 | Failed to Disconnect | Warning | ||
| 1122 | Rated/Idle Trans | Info | ||
| 1123 | Shutdown After Battle Short | A shutdown fault occurred while Battle Short was enabled and Battle Short transitioned from enabled to disabled | Warning | Review the Fault History and perform corrective action |
| 1124 | Delayed Shutdown | Provides advanced warning of an impending generator set shutdown to loads which cannot handle sudden power loss | Warning | A shutdown fault is present; review fault history |
| 113 | Actuator sensor fault | Category B | Warning | |
| 1131 | Battle Short Active | Battle short mode has been activated | Warning | Battle short function enabled |
| 115 | No speed signal | No speed signal | Shutdown | |
| 116 | Time press sensor high | Time press sensor high | Shutdown | |
| 117 | Time press sensor low | Time press sensor low | Shutdown | |
| 118 | Pump press sensor high | Pump press sensor high | Warning | |
| 119 | Pump press sensor low | Pump press sensor low | Warning | |
| 121 | Speed Signal Lost | No engine speed signal | Warning | |
| 1219 | Utility CB tripped | Warning | ||
| 122 | Manifold air press sensor | Manifold air press sensor | Warning | |
| 1222 | Power transfer not in auto | Warning | ||
| 1223 | Utility frequency sensor | Warning | ||
| 1224 | Gen over voltage sensor | Warning | ||
| 1225 | Gen under voltage sensor | Warning | ||
| 1226 | genset frequency sensor | Warning | ||
| 123 | Manifold air press sensor | Manifold air press sensor | Warning | |
| 1245 | CAN - Engine Shutdown | The PCC received a shutdown message from the ECM | Shutdown | Refer to the E-Controls service tool and the engine service manual |
| 1246 | CAN - Unknown Engine Fault | The PCC received an unknown message from the ECM | Warning | Refer to the E-Controls service tool and the engine service manual |
| 1247 | CAN - Engine Unannounced Fault | The PCC received an unknown message from the ECM | Warning | Refer to the E-Controls service tool and the engine service manual |
| 1248 | CAN - Engine Warning Fault | The PCC received an unknown message from the ECM | Warning | Refer to the E-Controls service tool and the engine service manual |
| 1311 | Customer input #1 | Optional customer-selected fault, e.g. Low Fuel Day Tank, Water In Fuel, Ground Fault, Low Starting Hydraulic/Air Pressure | Programmable via service tool: enable/disable, status/warning/shutdown, active closed/open, custom display name | |
| 1311, 1312, 1317, 1318 | Customer Input | Nature of the fault is an optional customer selection | Disconnect signal lead from TB1 (CUST_IN1 TB1-4, CUST_IN2 TB1-5, CUST_IN3 TB1-6, CUST_IN4 TB1-7) and reset the control; if the message clears, external wiring has a short/open or the active input selection (closed/open) is not correct | |
| 1312 | Customer input #2 | Optional customer-selected fault | Customer defined fault; message editable by the customer; can be programmed to initiate a shutdown or warning. | |
| 1313 | Network Fault 1 thru 4 | Network Fault 1 | Customer defined fault; message editable by the customer; can be programmed to initiate a shutdown or warning. | |
| 1313-1316 | Network Fault 1 Through 4 | Indicates network input (#1-#4) is in an active state | Each fault function can be programmed (using the service tool) as Status, Warning, or Shutdown; change display name using up to 19 characters | |
| 1314 | Network Fault 2 | Network Fault 2 | Customer defined fault; message editable by the customer; can be programmed to initiate a shutdown or warning. | |
| 1315 | Network Fault 3 | Network Fault 3 | Customer defined fault; message editable by the customer; can be programmed to initiate a shutdown or warning. | |
| 1316 | Network Fault 4 | Network Fault 4 | Customer defined fault; message editable by the customer; can be programmed to initiate a shutdown or warning. | |
| 1317 | Customer input #3 | Customer input #3 | Customer defined fault; message editable by the customer; can be programmed to initiate a shutdown or warning. | |
| 1318 | Customer input #4 | Customer input #4 | Customer defined fault; message editable by the customer; can be programmed to initiate a shutdown or warning. | |
| 1319 | High alternator temp | High alternator temp | Warning | |
| 1321 | Common warning driver | Common warning driver | Warning | |
| 1322 | Load gov kW setpoint oor hi | Load gov kW setpoint oor hi | Shutdown | |
| 1323 | Load gov kW setpoint oor lo | Load gov kW setpoint oor lo | Shutdown | |
| 1324 | Load gov kVAR oor hi | Load gov kVAR oor hi | Warning | |
| 1325 | Load gov kVAR oor lo | Load gov kVAR oor lo | Warning | |
| 1326 | Backup starter disconnect | Category B | Warning | |
| 1327 | Load gov kW analog oor | Load gov kW analog oor | Shutdown | |
| 1328 | Genset CB tripped | Genset CB tripped | Warning | |
| 1329 | AVR DC power failure | Category B | Warning | |
| 1331 | AVR driver shorted | Category A | Shutdown | |
| 1332 | Manual switch oor lo | Manual switch oor lo | Shutdown | |
| 1333 | Manual switch oor hi | Manual switch oor hi | Shutdown | |
| 1334 | Critical scaler oor | Critical scaler oor | Shutdown | Correct the feature/calibration entered into the control |
| 1335 | Noncrit Scaler Out Of Range | Non critical scaler oor | Warning | Correct the feature/calibration entered into the control |
| 1336 | Cooldown complete | Cooldown complete | Shutdown | |
| 1337 | No Message | Network wink | Info | |
| 1341 | Load demand stop | Load demand stop | Shutdown | |
| 1342 | Slot 0 card | Slot 0 card | Shutdown | |
| 1343 | Slot 1 card | Slot 1 card | Shutdown | |
| 1344 | Slot 2 card | Category A | Shutdown | |
| 1345 | Slot 3 card | Slot 3 card | Shutdown | |
| 1346 | Slot 4 incorrect | Slot 4 incorrect | Shutdown | |
| 1347 | Slot 5 card | Category A | Shutdown | |
| 1348 | Slot 6 card | Category A | Shutdown | |
| 1349 | Slot 7 card | Category A | Shutdown | |
| 135 | Oil pressure sensor | Oil pressure sensor | Warning | Verify fault simulation not enabled (InPower); inspect sensor and engine harness connector pins; use oil pressure sensor simulator to check control response, replace sensor if it responds; check P7-13, 17, 21 for short (>200k ohms OK) and open (10 ohms or less OK) |
| 1351 | Slot 4 / network enabled | Slot 4 / network enabled | Warning | |
| 141 | Oil pressure sensor | Oil pressure sensor | Warning | Verify fault simulation not enabled; inspect sensor/harness connector pins; use simulator to check control response; check P7-13, 17, 21 short/open |
| 1414 | Run relay contact | Run relay contact | Warning | |
| 1415 | Run relay driver | Run relay driver | Warning | |
| 1416 | Fail to shutdown | Fail to shutdown | Warning | Status - indicates the Fault Bypass mode is enabled (used primarily by service personnel for troubleshooting). The genset ignores the majority of system shutdown faults. |
| 1417 | Powr Down Error | The control has failed to go to sleep | Warning | Possible base board fault |
| 1419 | Fuel rail driver | Fuel rail driver | Warning | |
| 1421 | Timing rail driver #1 | Timing rail driver #1 | Warning | |
| 1422 | Timing rail driver #2 | Timing rail driver #2 | Warning | |
| 1424 | High side driver | High side driver | Warning | |
| 1427 | Overspeed relay driver | Overspeed relay driver | Warning | |
| 1428 | LOP shutdown relay driver | LOP shutdown relay driver | Warning | |
| 143 | Pre-Low Oil Pressure | Low oil pressure | Warning | Verify fault simulation not enabled; check oil level, lines and filters; use oil pressure sensor simulator; check +5 VDC at sensor (E1-A) and at P7-21; use simulator to P7-13 (OP OUT) and P7-17 (OP COMM); isolate to harness or base board |
| 1433 | Emergency stop - local | Local Emergency Stop | Shutdown | Pull the Emergency stop button out; move the O/Manual/Auto switch to O; press the front panel Fault Acknowledge/Reset button; select Manual or Auto as required |
Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.
Procedures
12Aligning Generator with Engine (Angular Alignment) adjustment
⚠ Accidental starting of the generator set during this procedure presents the hazard of severe personal injury or death.
Tools: Dial indicator, Shims
- Disconnect the negative (-) battery cable(s) before beginning.
- Fasten a dial indicator to the generator shaft or cooling fan with the sensing point on the capscrew head or flat surface of the drive disc at the bolt circle diameter.
- Bar the engine over in a clockwise rotation as viewed from engine flywheel; do not allow it to roll back on compression.
- Determine the total indicator reading (T.I.R.) as the sum of the maximum positive and negative dial indicator readings over one revolution.
- Measure the distance from the center of the generator shaft to the indicator measuring point.
- Measure the distance from the generator side of the flex discs to the center of the generator mounting bolt.
- Compare the distances; multiply this ratio times one half the T.I.R. to approximate the amount of shims to remove or add.
Angular Alignment Procedure adjustment
⚠ Accidental starting of the generator set during this procedure presents the hazard of severe personal injury or death. Make sure to disconnect the negative (-) battery cable(s) before beginning.
Tools: Dial indicator, Wooden shims
- Disconnect the negative (-) battery cable(s) before beginning.
- Fasten a dial indicator to the generator shaft or cooling fan with sensing point on capscrew head or flat surface of drive disc at bolt circle diameter.
- Bar the engine over in a clockwise rotation as viewed from engine flywheel; do not allow it to roll back on compression.
- Record maximum positive and negative dial indicator readings as the engine completes one revolution.
- T.I.R. equals the sum of the maximum positive and negative readings.
- Maximum T.I.R. should not be more than .001 inch for each inch of radius.
- Remove equal shims from under both generator mounting feet to lower the generator.
Angular Alignment Procedure (Generator to Engine) adjustment
⚠ Accidental starting during this procedure presents the hazard of severe personal injury or death.
⚠ Do not bar engine over by prying on fan blade.
Tools: dial indicator
- Disconnect the negative (-) battery cable(s) before beginning.
- Fasten a dial indicator to the generator shaft or cooling fan with sensing point resting on the drive disc capscrew head/flat surface at the bolt circle diameter.
- Bar the engine over in a clockwise rotation as viewed from the engine flywheel; do not allow it to roll back on compression at the end of travel of each reading.
- Record the total indicator reading (T.I.R.) as the sum of the maximum positive and negative dial indicator readings over one engine revolution.
- Compare the measured T.I.R. to the maximum allowed (.001 in. per inch of radius from center of shaft to indicator axis); add or remove shims under the generator mounting feet to correct.
Axial Alignment Procedure adjustment
Tools: Dial indicator with holding device (magnetic base or clamp)
- Fasten dial indicator holding device to skid base, engine block, or generator shell with magnetic base or clamp.
- Position so the sensor point rests on the generator shaft hub.
- Bar the engine over clockwise (viewed from engine flywheel) through a couple of rotations.
- Record indicator readings in eight equally spaced points around the shaft diameter to provide a T.I.R.
- To correct an out-of-tolerance T.I.R., remove capscrews connecting drive discs and flywheel.
- Mark the drive discs and flywheel with respect to each other.
- Rotate engine or generator so drive disc holes are repositioned 180 degrees from original location.
- Reinstall drive disc capscrews and retorque; re-check shaft alignment.
- If T.I.R. unchanged, rotate discs to 30, 60, or 90 degrees from original location.
- If T.I.R. does not improve, inspect flywheel pilot and drive disc runouts.
Axial Alignment Procedure (Generator to Engine) adjustment
Tools: dial indicator
- Fasten a dial indicator holding device to the skid base, engine block, or generator shell with the sensor point resting on the generator shaft hub.
- Bar the engine over in a clockwise rotation through a couple of rotations, recording indicator readings at eight equally spaced points around the shaft diameter to obtain axial T.I.R.
- Reduce the measured T.I.R. runout by one half if excessive vibration remains after angular alignment.
Bus Voltage Calibration (C) adjustment
⚠ Contacting hazardous voltage components can cause electrocution, resulting in severe personal injury or death.
⚠ Improper calibration or adjustment of the PowerCommand control can cause equipment malfunction or damage.
Tools: Calibrated RMS multimeter (Fluke models 87 or 8060A)
- Display the Bus Voltage Calibration submenu.
- With all gensets OFF, attach a calibrated voltmeter to TB1-A (L1) and TB1-B (L2) of the bus PT module.
- Start another genset and allow it to reach normal operating speed and voltage; connect to the bus.
- Calibrate the voltage reading for Bus Volts L1 so display matches the calibrated meter.
- Shut the generator set OFF.
- Repeat steps 2 through 5 for Bus Volts L2 and L3.
- Exit menu to Save changes.
Generator Mount Pre-load Adjustment adjustment
⚠ Accidental starting of the generator set during this procedure presents the hazard of severe personal injury or death. Disconnect the negative (-) battery cable(s) before beginning.
Tools: Two 1 3/4" T x 2" W x 6" L steel spacers, Adequate lifting device
- Turn off and disconnect battery charger (if equipped).
- Disconnect the negative (-) battery cable(s) to prevent accidental starting.
- Unscrew bolt (Item 2) from skid but do not remove from either rear engine vibration isolator.
- Loosen the three screws that secure the engine mount brackets to the engine.
- Loosen but do not remove the hex nut (Item 1) from the M20 screw of the generator vibration isolators.
- Lift the generator until mounting feet brackets are high enough to insert a 1 3/4 inch steel spacer under both stator foot brackets.
- Insert spacers and lower the generator so full weight rests on the mounting foot brackets.
- Make sure no gap is present between skid and lower mount of rear engine vibration isolators.
- Tighten the three screws to secure the bracket to the engine to 190-200 ft-lbs (260-270 N-m).
- Lift the generator to remove the two 1 3/4 inch steel spacers.
- Start the threads of the rear engine vibration isolator bolts (Item 2) before lowering.
- Lower the generator and tighten the two rear engine vibration isolator bolts to 270-330 ft-lbs (365-447 N-m).
- Secure the generator foot brackets to the vibration isolators and tighten to 270-330 ft-lbs (365-447 N-m).
Genset Ammeter Display Calibration (B) adjustment
⚠ Contacting hazardous voltage components can cause electrocution, resulting in severe personal injury or death.
⚠ Improper calibration or adjustment of the PowerCommand control can cause equipment malfunction or damage.
Tools: Calibrated RMS multimeter (Fluke models 87 or 8060A)
- Display the Current Calibration submenu.
- With the genset OFF, attach a calibrated ammeter to L1.
- Start the genset and allow it to reach normal operating speed.
- Load the genset to maximum rated kVA at rated voltage.
- Calibrate the reading for L1 current so display agrees with calibrated ammeter.
- Repeat steps 2 through 5 for L2 and L3.
- Exit menu to Save changes.
Genset Voltage Display Calibration (A) adjustment
⚠ Contacting hazardous voltage components can cause electrocution, resulting in severe personal injury or death.
⚠ Improper calibration or adjustment of the PowerCommand control can cause equipment malfunction or damage.
Tools: Calibrated RMS multimeter (Fluke models 87 or 8060A)
- Display the Voltage Calibration submenu.
- With the genset OFF, attach a calibrated voltmeter to the AC output from L1 to L2 (L1 to Neutral for single phase).
- Start the genset and allow it to reach normal operating speed.
- Calibrate voltage reading for L1 so display agrees with the calibrated voltmeter.
- Shut the generator set OFF.
- Repeat steps 2 through 5 for L2 and L3.
- Exit menu to Save changes.
Governor Calibration Checks adjustment
Tools: Frequency meter or tachometer, Jumper wire
- Start the generator set.
- Adjust engine no-load speed to the desired allowable speed droop using the Run Speed potentiometer.
- With no load, turn GAIN clockwise slowly until engine speed oscillates.
- Reduce GAIN slowly counterclockwise until engine speed is stable.
- Upset the governor by momentarily shorting terminals 7 and 10 on the governor control.
- Apply and remove loads to check generator set response.
HC4-7 Axial Alignment Procedure adjustment
Tools: Dial indicator with magnetic base or clamp
- Check only when an objectionable vibration is present.
- Fasten dial indicator holding device to skid base, engine block, or generator shell with magnetic base or clamp.
- Position sensor point on the generator shaft hub.
- Bar the engine over in a clockwise rotation as viewed from engine flywheel through a couple of rotations.
- Record indicator readings in eight equally spaced points around the shaft diameter.
- Remove the capscrews connecting drive discs and flywheel and mark discs and flywheel.
- Rotate engine or generator so drive disc holes are repositioned 180 degrees from original location.
- Put capscrews back in and retorque. Recheck shaft alignment.
- If runout unchanged, rotate discs to 30, 60 or 90 degrees from original location.
- If T.I.R. does not improve, inspect flywheel pilot and drive disc runouts.
P7 Axial Alignment Procedure adjustment
- Check only when an objectionable vibration is present.
- Remove the capscrews connecting drive discs and flywheel.
- Mark the drive discs and flywheel with respect to each other.
- Rotate engine or generator so drive discs holes are repositioned two bolt holes from original location.
- Put capscrews back in and retorque. Recheck/record vibration levels.
- Repeat this test until drive disc holes are repositioned 180 degrees from original location.
- Review vibration data and position drive disc in lowest recorded level location.
Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.
Voltage reconnection
| Voltage | Phase | Connection | Leads | Notes |
|---|---|---|---|---|
| 12 lead generator sets | Load wires are routed through the CTs | Reconnectable gensets (12 leads) have dual secondary CTs (3 pins); CT wire 2/3 to pin 2 (high voltage) or pin 3 (low voltage). | ||
| 6 lead generator sets | Generator output leads are routed through the CTs | Non-reconnectable gensets (6 leads) have single secondary CTs (2 pins). | ||
| Cummins PowerCommand generic AC Reconnect Wiring Diagram 625-2755 (Rev. D) and 625-3100 (Rev. F) | Applies to models DFAA, DFAB, DFAC, DFBF, DFCB, DFCC, DFEB, DFEC, DFFB, DFGA, DFGB, DFJA, DFJB, DFJC, DFJD, DFLB, DFLC, DFLD, DFMB (625-2755) and models DFAA-DFMB plus DFCE, DFED, DQAA, DQAB, DQBA, DQBB (625-3100). | |||
| A (U) | CT21 | U load leads (A phase) | CT dot must face the generator; CT terminal 1 connects to metering circuit, terminal 2/3 to ground. | |
| B (V) | CT22 | V load leads (B phase) | CT dot must face the generator; terminal 1 to metering circuit, terminal 2/3 to ground. | |
| C (W) | CT23 | W load leads (C phase) | CT dot must face the generator; terminal 1 to metering circuit, terminal 2/3 to ground. | |
| 110/190 | 3 | 12 | Full load current at Standby rating: 1901 A | |
| 110/220 | 3 | 12 | Full load current at Standby rating: 1642 A | |
| 115/230 | 3 | 12 | Full load current at Standby rating: 1571 A | |
| 120/208 | 3 | 12 | Full load current at Standby rating: 1737 A | |
| 139/240 | 3 | 12 | Full load current at Standby rating: 1505 A | |
| 220/380 | 3 | 12 | Full load current at Standby rating: 951 A | |
| 230/400 | 3 | 12 | Full load current at Standby rating: 903 A | |
| 240/416 | 3 | 12 | Full load current at Standby rating: 868 A | |
| 255/440 | 3 | 12 | Full load current at Standby rating: 821 A | |
| 277/480 | 3 | Wye, 4 Wire | 12 | Full load current at Standby rating: 753 A |
| 277/480 | 3 | Wye, 4 wire | 12 | Alternator 60 Hz, 12 lead, limited range, 125 °C; single phase power may be taken at up to 40% of nameplate kW at unity power factor |
| 347/600 | 3 | 12 | Full load current at Standby rating: 602 A |
Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.
Common questions
What is the power rating of the Cummins/Onan DFE?
The Cummins/Onan DFE is rated 500 kW standby (563.0 kVA).
What engine is in the Cummins/Onan DFE?
The Cummins/Onan DFE is powered by the Cummins/Onan KTA19 engine.
What kind of fuel does the Cummins/Onan DFE run on?
The Cummins/Onan DFE runs on Diesel.
What is the oil capacity of the Cummins/Onan DFE?
The Cummins/Onan KTA19 engine in the Cummins/Onan DFE has an oil capacity of 45.0 liters.
How much coolant does the Cummins/Onan DFE hold?
The Cummins/Onan DFE cooling system holds 91 liters (24.0 US gallons) for the radiator system including the engine, per the manufacturer specification sheet.
What is the continuous rating of the Cummins/Onan DFE?
The Cummins/Onan DFE is rated 455 kW prime (513 kVA), against 500 kW standby.
What is the sound level of the Cummins/Onan DFE?
The Cummins/Onan DFE is rated at 76.0 dBA at 7 m, per the manufacturer specification sheet.
How much does the Cummins/Onan DFE weigh?
The Cummins/Onan DFE has a dry weight of 4098 kg (9034 lb).
How big is the fuel tank on the Cummins/Onan DFE?
The Cummins/Onan DFE has a 3218 liter (850 US gallon) fuel tank, giving about 25 hours of runtime.
What voltages is the Cummins/Onan DFE available in?
The Cummins/Onan DFE is offered in 24 V, 3-phase.
What battery does the Cummins/Onan DFE use?
The Cummins/Onan DFE uses 2 batteryies, 24 V each, 1400 CCA, group 8D, per the manufacturer specification sheet.
What alternator does the Cummins/Onan DFE use?
The Cummins/Onan DFE uses a Stamford/AvK HC alternator.
What air filter does the Cummins/Onan DFE use?
The Cummins/Onan DFE uses air filter part number L028-2.
Troubleshooting
6Fault codes
| Code | Meaning | Cause | Remedy |
|---|---|---|---|
| 212 | Shutdown lamp lights. | Indicates engine has overheated (coolant temperature has risen above the shutdown trip point: 223° F – standby / 215° F – primary) or the coolant level is low. Allow engine to cool down completely before proceeding with the following checks: | A. Check coolant level and replenish if low. Look for coolant leakage and repair if necessary. b. Check for obstructions to cooling airflow and correct as necessary. c. Check fan belt and repair or tighten if necessary. d. Reset control and restart after locating and correcting problem. Contact an authorized service center if none of the above. |
Symptoms & remedies
| Symptom | Cause | Remedy |
|---|---|---|
| Warning lamp lights. | LOW COOLANT TEMP 210 – WARNING | Set is in standby mode but is not operating. Warning occurs when engine coolant temperature is 70° F (21° C) or lower. NOTE: In applications where the ambient temperature falls below 40°F (4°C), Low Engine Temp may be indicated even though the coolant heaters are operating. |
| Engine starts from generator control panel but will not start automatically or from a remote panel. (Note: The Run/Off/Auto switch must be in the Auto position for automatic or remote starting). | Check the control wiring between the remote switch and the PCC. Contact an authorized service center. | |
| No AC output voltage. | Contact an authorized service center. | |
| Control does not power up when the Run/Off/Auto switch is set to Run or the Self Test switch is pressed. | There is no DC power to the control. | A. Check for battery disconnected, discharged, or improperly connected. b. Fuse F1 (20A/32V, Type 3AG) may be open. Replace with the same type. |
| Warning, Shutdown, and Non-Automatic lamps are not lit. Digital display shows main menu or selected menu. | Indicates all engine systems are normal. No corrective action required |
Fault codes and symptom→remedy steps extracted from this model’s service/owner documentation; verify against the official manual before servicing. Full Cummins/Onan DFE troubleshooting guide (91 entries) →
Repair guides
55- Automatic Starting from ATS (PCC)
- Axial Alignment Procedure
- Axial Alignment Procedure
- Bearing Removal
- Bus Voltage Calibration (C)
- Bus Voltage Calibration (C)
- Checking Electrolyte Level
- Checking Specific Gravity
- Current Transformer (CT) Installation Requirements
- Current Transformer Installation Requirements
- Day Tank / Fuel Transfer Pump Operation
- Emergency Stop (Code 1434) Reset
- Engine Does Not Crank in Manual Mode - Diagnosis and Repair
- Enter Password (Adjust Submenu)
- Entering Password
- Entering Password
- Entering Password
- Entering the Password (Adjust Submenu)
- Exercise Start
- Fuel Transfer Pump Motor Connection (Replacement)
Step-by-step procedures compiled from the Cummins/Onan service manual for this model.
Parts
12| Part # | Description | Qty | System | |
|---|---|---|---|---|
| 0179-3536 | Coolant heater (Revision E) | Service part / kit | eBay | |
| 0402-0222 | Vibration isolator (non-seismic rated, does not carry IBC/OSHPD certification) | Service part / kit | eBay | |
| 0402-0234 | Vibration isolator (non-seismic rated, does not carry IBC/OSHPD certification) | Service part / kit | eBay | |
| 0402-0246 | Vibration isolator (non-seismic rated, does not carry IBC/OSHPD certification) | Service part / kit | eBay | |
| 0402-0427 | Vibration isolator (non-seismic rated, does not carry IBC/OSHPD certification) | Service part / kit | eBay $86.02 | |
| A035H139 | Switch, Pushbutton | 1 | Service part / kit | eBay |
| A040U808 | Harness, Control − Door (Includes Items 30 & 31) | 1 | Service part / kit | eBay |
| A046Y204 | Shield, Wiring | 1 | Service part / kit | eBay |
| CC2609 | Fleetguard Water-Check H2O 3-Way Test Strips | 1 | Service part / kit | Amazon eBay |
| D1400 | DONALDSONS D1400 SOLVENT | Service part / kit | Amazon eBay FridayParts $48.99 | |
| TB3-5 | Generator Set Control Panel Terminal Block | 1 | Service part / kit | Amazon eBay FridayParts $399.75 |
| TB3-6 | Generator Set Control Panel Terminal Block | 1 | Service part / kit | Amazon eBay FridayParts $65.10 |
Service, wear & replacement parts referenced for this model and its engine — confirm the exact part for your serial number. See the full parts catalog to search and cross-reference.
Fuel consumption
| Rating | Load | L/h | gal/h |
|---|---|---|---|
| Prime | 105.0 | 27.7 | |
| Prime | 3% | 83.0 | 21.9 |
| Prime | 25% | 41.0 | 10.9 |
| Prime | 50% | 67.0 | 17.6 |
| Prime | 75% | 90.0 | 23.7 |
| Prime | 100% | 115.0 | 30.4 |
| Standby | 114.0 | 30.1 | |
| Standby | 3% | 89.0 | 23.4 |
| Standby | 25% | 44.0 | 11.6 |
| Standby | 50% | 71.0 | 18.8 |
| Standby | 75% | 97.0 | 25.7 |
| Standby | 100% | 91.0 | 24.1 |
Available documents
This page was generated from the 43 manufacturer documents above by automated extraction; every figure shown is copied from one of them. How the data is compiled.