HomeControllersPowerCommand 3100 (PCC)

PowerCommand 3100 (PCC) Controller

The PowerCommand 3100 (PCC) is a generator-set controller. It is used on generator sets from Cummins/Onan, including the 3100 Series, DFAA, DFAB and DFAC.

27
Generator sets
Cummins/Onan
Brand
275–1500 kW
Power range
Diesel
Fuel

Troubleshooting

60

Fault codes

CodeMeaningCauseRemedy
-23HIGH COOLANT TEMP
101Engine continues to operate at reduced RPM.
101IDLE MODE Warning
102EMERGENCY STOP Shutdown
102Engine shuts down and will not crank.Indicates local or remote Emergency Stop.To reset the local Emergency Stop button : Pull the button out or turn the switch clockwise (button with arrow) and allow it to pop out. Move the Run/Off/Auto switch to Off. Press the Reset switch. Select Run or Auto, as required.
1123A shutdown occurs immediately after moving the customer installed Battle Short switch to OFF with an active but overridden shutdown fault or a shutdown fault that was overridden at any time.
1123Shutdown After Battle Short
1124Delayed Shutdown
1131Battle Short Active
1131Battle Short mode is enabled.
121Speed Signal Lost
121Speed Signal Lost fault.
1244Engine Normal Shutdown
1245CAN - Engine Shutdown
1246CAN - Unknown Engine Fault
1247CAN - Engine Unannounced Fault
1248CAN - Engine Warning Fault
1311Customer Inputs #1
1312Customer Inputs #2
1317Customer Inputs #3
1318Customer Inputs #4
1334Crit Scaler OR
1335Non-Crit Scaler OR
135Oil Pressure Sensor High
141Oil Pressure Sensor Low
1416An overridden shutdown fault occurs, but the genset does not shut down.
1416Fail To Shut Down
1416Fail to Shutdown
1417Power Down Failure
143Pre-Low Oil Pressure Sensor
1433Emergency Stop
1433Emergency Stop fault.
1434Remote Emergency Stop
1434Remote Emergency Stop fault.
1435Low Coolant Temperature
1438Fail to Crank
144Coolant Temperature Sensor High
1442Weak Battery
1443Battery Failed
1444KW Overload
1445Short Circuit
1446High AC Voltage
1447Low AC Voltage
1448Under Frequency
1449Over Frequency
145Coolant Temperature Sensor Low
146HIGH COOLANT TEMP WARNINGA. Reduce load if possible by turning off non-critical loads. b. Check air inlets and outlets and remove any obstructions to airflow. If engine can be stopped, follow 151 High Coolant Temp Alarm procedure.
146Pre-High Cool Temp
1461Loss of Field
1466Modem Failure
1468Network Error
1469Speed/Hz Match
1471Over Current
1472Over Current
151HIGH COOLANT TEMP ALARMA. Check jacket water coolant level and replenish if low. Look for coolant leakage and repair if necessary. b. Check for obstructions to cooling airflow and correct as necessary. c. Check fan belt and repair if necessary. d. Reset control and restart after locating and correcting problem.
151High Coolant Temp
152LOW COOLANT TEMPA. Coolant heater not connected to power supply. Check for blown fuse or disconnected heater cord and correct as required. b. Check for low jacket water coolant level and replenish if required. Look for possible coolant leakage points and repair as required.
197COOLANT LEVEL WARNINGA. Check jacket water coolant level and replenish if low. Look for possible coolant leakage points and repair if necessary. b. Reset control and restart after locating and correcting problem.
197Low Coolant Level
200Indicates engine oil pressure has dropped to an unacceptable level.If generator is powering critical loads and cannot be shut down, wait until next shutdown period then follow 201 Low Oil Pressure procedure. If engine can be stopped, follow 201 procedure. To check oil pressure, access Oil Pressure menu prior to clearing the fault.

Fault codes and symptom→remedy steps extracted from this controller’s service/owner documentation; verify against the official manual before servicing. Aggregated from the service documentation of generator sets built on this controller.