| Clearance | Exhaust pipe clearance from combustible wall or partition | 12 | inches (305 mm) | minimum |
| Clearance | Exhaust pipe clearance to combustible wall/partition | 12 | inches (305 mm) | |
| Clearance | Float switch assembly float lift clearance below C-clip stop | 1/8 | inch (3 mm) | use a feeler gauge |
| Clearance | Fuel line clearance from electrical wiring | 1/2 | inch (12.7 mm) | |
| Clearance | Fuel line clearance from hot exhaust parts | 2 | inch (51 mm) | |
| Clearance | Generator mount pre-load steel spacer thickness | 1 3/4 | inch | two spacers under both stator foot brackets |
| Clearance | Generator-to-engine angular alignment (T.I.R.) | .001 in. per inch of radius (center of shaft to indicator axis), maximum | in | 750 kW gensets and larger |
| Clearance | MPU installation gap adjustment | back out 1/4 turn after touching gear tooth | turn | |
| Clearance | Vibration isolator base elevation difference | 0.25 | inch (6 mm) | shimmed or grouted within this of each other |
| Clearance | Vibration isolator clearance | 0.25 | inch (6 mm) | |
| Clearance | Vibration isolator nominal clearance (leveling bolt) | 0.25 | inch (6 mm) | minimum, or greater |
| Gap | Coolant level below radiator cap lower sealing surface | 3/4 inch (18 mm) | inch (mm) | |
| Other | AVR Droop setting | 5 | % at full load, 0 PF | |
| Other | AVR voltage regulation (load regulation) | approximately ±0.5 | % RMS | |
| Other | Ambient temperature below which coolant heaters recommended (NFPA 110) | 40 | °F | |
| Other | Battery CCA (minimum) | 1400 | CCA | Cold Soak @ 0° F (-18° C) |
| Other | Battery specific gravity (fully charged) | 1.26 | specific gravity | at 80 F (27 C) |
| Other | Battery specific gravity (high ambient, above 95F/35C) | 1.225 | | recommended to reduce electrolyte loss |
| Other | Battery specific gravity (recharge threshold) | below 1.260 | | |
| Other | Battery specific gravity charge threshold | 1.215 | corrected | charge battery if reading below |
| Other | Battery specific gravity fully charged | 1.260 | corrected | add 0.004 per 10 F above 80 F (27 C) |
| Other | Battery terminal cleaning solution | 1/4 pound baking soda to 1 quart water | | |
| Other | CAN datalink main trunk maximum length | 40 | meters | no more than 30 devices |
| Other | CAN datalink stub maximum length | 1 | meter | stub from main trunk to each module |
| Other | CAN datalink transmission speed | 250 | KBaud | |
| Other | Charge battery if specific gravity below | 1.215 | specific gravity | |
| Other | Fully charged battery corrected specific gravity | 1.260 | specific gravity | corrected reading @ 80 F (27 C) |
| Other | GOV GAIN default value for paralleling applications | 70 | % | |
| Other | Mounting bolt size | 5/8 | inch or 16 mm | |
| Other | Mounting bolts | 5/8 inch or 16 mm | inch / mm | anchored mounting bolts |
| Other | Output frequency adjustment (PCC) | +/- 5 | % | set running under normal parameters |
| Other | Over current warning threshold | 110 | % of rated | |
| Other | Over/Under Frequency Sensor Module - Over Hz Set, 50 Hz nominal | 55 | Hz | reset 53 Hz |
| Other | Over/Under Frequency Sensor Module - Over Hz Set, 60 Hz nominal | 65 | Hz | reset 63 Hz |
| Other | Over/Under Frequency Sensor Module - Under Hz Set, 50 Hz nominal | 45 | Hz | reset 47 Hz |
| Other | Over/Under Frequency Sensor Module - Under Hz Set, 60 Hz nominal | 55 | Hz | reset 57 Hz |
| Other | Over/Under Voltage Sensor Module time delay | typically 25 percent, approximately 2.5 | seconds | |
| Other | Overcrank cranking limit | 75 | seconds | three 15-second cranking cycles with two 15-second rest periods |
| Other | REG VHZ (underfrequency roll-off) adjustable range | 1 through 50; normal range 7 through 21 | | |
| Other | Short circuit shutdown threshold | 175 | % of rated current | |
| Other | Specific gravity correction | 0.004 | gravity point per 10 F above 80 F (27 C) | |
| Other | Start delay adjustment range | 0 to 300 | seconds | |
| Other | Start delay adjustment range (PCC) | 0 to 300 | seconds | Auto mode remote starting |
| Other | Stop delay adjustment range | 0 to 600 | seconds | |
| Other | Stop delay adjustment range (PCC) | 0 to 600 | seconds | Auto mode remote stopping |
| Other | Under Frequency Roll Off (UFRO) knee point, 50 Hz units | 48 to 49 | Hz | |
| Other | Under Frequency Roll Off (UFRO) knee point, 60 Hz units | 58 to 59 | Hz | |
| Pressure | Air cleaner element cleaning compressed air pressure | 30 | psi (207 kPa) | nozzle held at least 1 inch (25 mm) away |
| Pressure | Engine oil pressure (displayed example) | 75 | PSI | |
| Pressure | Engine oil pressure - K19 normal | 50-70 | psi (345-482 kPa) | run mode |
| Pressure | Engine oil pressure - K38 normal | 45-65 | psi (310-448 kPa) | run mode |
| Pressure | Engine oil pressure - K50 normal | 50-70 | psi (345-482 kPa) | run mode |
| Pressure | Engine oil pressure - L10/M11 normal | 30-50 | psi (207-345 kPa) | run mode |
| Pressure | Engine oil pressure - NTA 855 normal | 35-50 | psi (241-345 kPa) | run mode |
| Pressure | Engine oil pressure - V28 normal | 50-90 | psi (345-620 kPa) | run mode |
| Pressure | Engine oil pressure shutdown limit - L10/M11 | 20 | psi (138 kPa) | run mode value |
| Pressure | Engine oil pressure shutdown limit - L10/M11 | 8 | psi (55 kPa) | idle mode value |
| Pressure | Engine oil pressure warning limit - L10/M11 | 12 | psi (83 kPa) | idle mode value |
| Pressure | Engine oil pressure warning limit - L10/M11 | 25 | psi (172 kPa) | run mode value |
| Pressure | Fuel transfer pump maximum inlet restriction capability | 16 | inch Hg | approximately equivalent to 20 feet of diesel |