| 27 | Low AC voltage shutdown | Voltage on any phase has dropped below a preset value; adjustable 50-95% of reference, delay 2-20 seconds; default 85% for 10 seconds | Shutdown | Genset shut down on low AC output voltage |
| 32 | Reverse power shutdown | Adjustment range 5-20% of standby kW rating, delay 1-15 seconds; default 10%, 3 seconds | Shutdown | Genset shut down on reverse power |
| 59 | High AC voltage shutdown | Output voltage on any phase exceeds preset values; adjustable 105-125% of nominal, time delay 0.1-10 seconds; default 110% for 10 seconds | Shutdown | Genset shut down on high AC output voltage |
| 81 o | Over frequency shutdown/warning | Generator set is operating at a potentially damaging frequency level; 2-10 Hz above nominal, 1-20 second delay; default 6 Hz, 20 seconds, disabled | Shutdown | Shutdown/warning on over frequency |
| 81 u | Under frequency shutdown | Generator set output frequency cannot be maintained; 2-10 Hz below reference, 5-20 second delay; default 6 Hz, 10 seconds | Shutdown | Genset shut down on under frequency |
| 101 | IDLE MODE | Indicates that the engine is operating in idle mode (governed at 800 RPM, generator build-up inhibited). | Warning | Remove ground from engine idle input to return to normal speed and voltage. |
| 102 | EMERGENCY STOP | Indicates local or remote Emergency Stop. | Shutdown | Turn the switch clockwise and allow it to pop out (local only). Move the Run/Off/Auto switch to Off. Press the Reset switch. Select Run or Auto, as required. |
| 111 | Internal ECM error | Category A | Shutdown | |
| 112 | Actuator not responding | Category A | Shutdown | |
| 113 | Actuator sensor fault | Category B | Warning | |
| 115 | No speed signal | Category A | Shutdown | |
| 116 | Time press sensor high | Category A | Shutdown | |
| 117 | Time press sensor low | Category A | Shutdown | |
| 118 | Pump press sensor high | Category B | Warning | |
| 119 | Pump press sensor low | Category B | Warning | |
| 121 | No engine speed signal | Category C | Warning | |
| 122 | Manifold air press sensor | Category B | Warning | |
| 123 | Manifold air press sensor | Category B | Warning | |
| 135 | Oil Pressure Sensor High | Engine oil pressure sensor is shorted high | Warning | Verify fault simulation not enabled (InPower); inspect sensor and engine harness connector pins; use oil pressure sensor simulator to check control response, replace sensor if it responds; check P7-13, 17, 21 for short (>200k ohms OK) and open (10 ohms or less OK) |
| 141 | Oil Pressure Sensor Low | Engine oil pressure sensor is shorted low | Warning | Verify fault simulation not enabled; inspect sensor/harness connector pins; use simulator to check control response; check P7-13, 17, 21 short/open |
| 143 | Pre-Low Oil Pres | Engine oil pressure has dropped below the warning trip point | Warning | If powering critical loads, wait until next shutdown period then follow code 415 procedure |
| 144 | Coolant Temperature Sensor High | Coolant temperature sensor signal is shorted high | Warning | Verify fault simulation not enabled; inspect sensor/harness pins; use resistive sensor simulator, replace sensor if control responds; check P7-30 (IH20) and P7-34 (IH20 COM) for short to ground and pin-to-pin (>200k ohms OK); compare sensor resistance between pins |
| 145 | Coolant Temperature Sensor Low | Coolant temperature sensor signal is shorted low | Warning | Verify fault simulation not enabled; inspect sensor/harness pins; use resistive sensor simulator; check P7-30 and P7-34 for short circuits and compare resistance |
| 146 | Pre-High Coolant Temp | Engine operating near cooling system capacity | Warning | Review 151 correction list |
| 151 | High Coolant Temp | Coolant temperature has risen above the shutdown trip point | Shutdown | Check coolant level/leaks, airflow obstructions, fan belt, blower fan/circulation pumps; reset and restart |
| 152 | Low coolant temp | Category D | Warning | Warning occurs when jacket water coolant temperature is 70 F (21 C) or lower. Check coolant heater power supply (blown fuse or disconnected heater cord); check jacket water coolant level and replenish; look for coolant leakage and repair. In applications where ambient is below 40 F (4 C) Low Coolant Temp may be indicated even though the heaters operate. |
| 153 | Manifold air temp sensor | Category C | Warning | |
| 154 | Manifold air temp sensor | Category C | Warning | |
| 155 | Manifold air temp alarm | Category A | Shutdown | |
| 197 | Low Coolant Level | Coolant level below warning trip point (optional) | Warning | Follow code 235 procedure at next shutdown |
| 200 | LOW OIL PRESSURE | Indicates engine oil pressure has dropped to an unacceptable level. | Warning | If generator is powering critical loads and cannot be shut down, wait until next shutdown period and then follow 201-SHUTDOWN procedure. Access the Oil Pressure menu prior to clearing the fault. |
| 201 | LOW OIL PRESSURE | Indicates engine oil pressure has dropped below the shutdown trip point. | Shutdown | Check oil level, lines and filters. If oil system is OK but oil level is low, replenish. Reset control and restart. Oil pressure limits are listed in Table 4-3. |
| 204 | OIL PRES SENDER | Indicates that the control has sensed that the engine oil pressure sender is out of its working range. | Warning | Check that the engine oil pressure sender is properly connected. |
| 210 | LOW COOLANT TEMP | Set is not operating. Warning occurs when engine coolant temperature is 70° F (21° C) or lower. | Warning | Indicates engine coolant heater is not operating or is not circulating coolant. Check coolant heater power supply, low coolant level, and heater element current draw. |
| 211 | HIGH COOLANT TEMP | Indicates the engine coolant temperature is getting close to the recommended maximum temperature limit: 215° F (102° C) − standby or 207° F (97° C) − primary. | Warning | Reduce load if possible by turning off non-critical loads. Check air inlets and outlets and remove any obstructions to airflow. If engine can be stopped, follow 212-SHUTDOWN procedure. |
| 212 | HIGH COOLANT TEMP | Indicates engine has overheated (coolant temperature above 215° F (102° C) − standby or 207° F (97° C) − primary). | Shutdown | Allow engine to cool down completely. Check for obstructions to cooling airflow; check fan belt; check coolant mixture; check blower fan and circulation pumps on remote radiator installations. Reset control and restart. |
| 213 | COOLANT SENDER | Indicates that the resistance of the coolant temperature sender is out of range. | Warning | Check the resistance of the sender. Resistance should be 500 to 2k ohms. |
| 214 | LOW COOLANT LVL | Indicates engine coolant level has fallen below the trip point. | Warning | Allow engine to cool down completely. Check coolant level in both radiator and coolant recovery bottle and replenish if low. Look for coolant leakage points and repair if necessary. |
| 215 | LOW COOLANT LVL | Indicates engine coolant level has fallen below the trip point. | Shutdown | Allow engine to cool down completely. Check coolant level in both radiator and coolant recovery bottle and replenish if low. Reset control and restart after correcting problem. Shutdown will not occur if genset is in Idle mode (low coolant warning only). |
| 220 | MAG PICKUP | Indicates mag pickup speed indication is not being sensed or does not match generator set output frequency. | Shutdown | Restart and check RPM on the digital display. |
| 221 | FAIL TO CRANK | Indicates possible fault with control or starting system. | Shutdown | Check fuse F3 on the Engine Interface board. Check for poor battery cable connections; clean battery cable terminals and tighten. Recharge or replace a discharged or defective battery. |
| 222 | OVERCRANK | Indicates possible fuel system problem. | Shutdown | Check for empty fuel tank, fuel leaks, or plugged fuel lines. Check for dirty fuel filter and replace if necessary. Check for dirty or plugged air filter and replace if necessary. Reset the control and restart after correcting the problem. |
| 223 | OVERSPEED | Engine has exceeded normal operating speed (115% ±1% of nominal). | Shutdown | Check mechanical fuel linkage and actuator; check governor output module (A38) and digital board (A32). |
| 224 | FAIL TO SYNCHRONIZE | Generator set has not synchronized to the system bus within the allowable time frame. | Warning | Check governor system stability; adjust governing and synchronizer parameters; check fuel system. |
| 226 | FAIL TO CLOSE | Paralleling breaker has been given a signal to close, but has not closed properly. | Shutdown | Verify breaker charging mechanism; check close signal; verify auxiliary contact signals. |
| 228 | Low coolant pressure | Category A | Shutdown | |
| 230 | LOW DC VOLTAGE | Indicates battery voltage is below 10 VDC. | Warning | Recharge or replace the battery; check the battery charger fuse. Clean and tighten battery cable connections. Check engine DC alternator; replace if normal charging voltage is not obtained. Check float level if applicable. |
| 231 | HIGH DC VOLTAGE | Indicates battery voltage exceeds 32 VDC. | Warning | Check float level on battery charger if applicable (lower float level). Check engine DC alternator; replace if normal battery charging voltage is not obtained. |
| 232 | WEAK BATTERY | Indicates battery voltage drops below 60% of nominal for two seconds, during starting. | Warning | Discharged or defective battery. See Warning message 230, LOW DC VOLTAGE. |
| 233 | Coolant pressure warning | Category A | Warning | |
| 234 | Overspeed | Engine speed signal indicates engine speed greater than the shutdown threshold | Shutdown | Cold engine: clear fault and restart; large block load removal: clear and restart; verify fault simulation not enabled; reset threshold via InPower; monitor engine RPM; check electronic governor actuator for binding |
| 235 | Low Coolant Level | Coolant level below shutdown trip point (optional) | Shutdown | Check coolant level and leaks; reset and restart |
| 236 | Position sensor | Category A | Shutdown | |
| 240 | LOW FUEL−DAY | Indicates day tank fuel supply is running low. | Warning | Check fuel supply and replenish as required. |
| 241 | LOW FUEL | Indicates day tank fuel supply is running low. | Warning | Check fuel supply and replenish as required. |
| 250 | EEPROM ERROR | PCC memory error; data corruption of critical operating parameters. | Shutdown | Perform initial start setup procedure; replace digital board (A32) if fault repeats. |
| 251 | EEPROM ERROR | PCC memory error; data corruption of noncritical operating parameters. | Warning | Perform adjustment and calibration procedures; replace digital board (A32) if fault repeats. |
| 252 | EEPROM ERROR | PCC memory error; data corruption of noncritical operating parameters. | Warning | Verify selected values; repeat save operation; replace digital board (A32) if fault repeats. |
| 253 | Oil level alarm | Category D | Shutdown | |
| 254 | Fuel shutoff valve | Category A | Shutdown | |
| 259 | Fuel shutoff valve | Category C | Warning | |
| 260 | CUSTOMER FAULT 1 | When a customer defined input is closed to ground, the corresponding fault message is displayed. Default message; editable for customer site requirements. | Warning | Fault functions can be programmed to initiate a shutdown or a warning. |
| 261 | GROUND FAULT | When a customer defined input is closed to ground, the corresponding fault message is displayed. Default message; editable for customer site requirements. | Warning | Fault functions can be programmed to initiate a shutdown or a warning. |
| 262 | RUPTURE BASIN | When a customer defined input is closed to ground, the corresponding fault message is displayed. Default message; editable for customer site requirements. | Warning | Fault functions can be programmed to initiate a shutdown or a warning. |
| 263 | HIGH GEN TEMP | When a customer defined input is closed to ground, the corresponding fault message is displayed. Default message; editable for customer site requirements. | Warning | Fault functions can be programmed to initiate a shutdown or a warning. |
| 265 | Fuel temperature sensor | Category C | Warning | |
| 266 | Fuel temperature | Category A | Shutdown | |
| 270 | PHASE ROTATION | The phase relationship between the generator set and the system bus is not matched. | Shutdown | Verify genset phase rotation matches bus; verify control wiring to bus PT module. |
| 272 | FIRST START | PowerCommand control is not receiving a proper signal from the system master first start sensor. | Warning | Verify Master First Start Sensor and interconnection wiring. |
| 301 | HIGH AC VOLTAGE | One or more phase voltages exceeded 130% of nominal, or exceeded 110% of nominal for 10 seconds. | Shutdown | Check PCC, alternator, excitation circuit, and PT/CT module wiring. |
| 303 | LOW AC VOLTAGE | One or more phase voltages dropped below 85% of nominal for 10 seconds. | Shutdown | Check PMG/field wiring, rotating rectifier, load and connectors. |
| 313 | UNDER FREQUENCY | Indicates that engine speed has dropped below 90% of nominal for 10 seconds. Five seconds before shutdown, a Load Dump signal is initiated. | Shutdown | Check fuel supply, intake air supply and load. |
| 316 | Fuel supply pump | Category B | Warning | |
| 318 | Fuel supply pump | Category B | Warning | |
| 320 | OVERCURRENT | Indicates that generator output current has exceeded 110% of rated for 60 seconds. | Warning | Check load and load lead connections. |
| 321 | OVERCURRENT | Indicates that generator output current has exceeded 110% of rated, and that a PCC time/current calculation has initiated an overcurrent shutdown. | Shutdown | Check load and load lead connections. |
| 322 | SHORT CIRCUIT | Indicates that generator output current has exceeded 175% of rated. | Shutdown | Check load and load lead connections. |
| 326 | Oil level warning | Category D | Warning | |
| 330 | OVERLOAD | Indicates that three-phase power output exceeds 105% of standby (or 115% of prime) rating. After five seconds, the Load Dump output is activated. After 60 seconds, the OVERLOAD warning is activated. | Warning | Check load and load lead connections. |
| 335 | REVERSE POWER | Indicates improper CT or PT phasing. (Non-parallel units only.) | Shutdown | Check CT / PT wiring. Refer to CT Installation in Section 5. |