| 101 | IDLE MODE | Indicates that the engine is operating in idle mode. Grounding the engine idle input causes generator build-up to be inhibited and the engine to be governed at 800 RPM. | Warning | No corrective action required. When ground is removed from the input, the set returns to normal speed and voltage; oil pressure warning and shutdown trip points are reset automatically. |
| 102 | EMERGENCY STOP | Local or remote Emergency Stop. | Shutdown | Reset only at PCC front panel: pull button out, switch to Off, press Reset. |
| 200 | LOW OIL PRESSURE | Indicates engine oil pressure has dropped to an unacceptable level. | Warning | If generator is powering critical loads and cannot be shut down, wait until next shutdown period then follow 201 Low Oil Pressure procedure. If engine can be stopped, follow 201 procedure. To check oil pressure, access Oil Pressure menu prior to clearing the fault. |
| 201 | LOW OIL PRESSURE | Indicates engine oil pressure has dropped below the shutdown trip point. | Shutdown | Check oil level, lines and filters; replenish if low; reset and restart. Contact service center. |
| 204 | OIL PRES SENDER | Indicates that the engine oil pressure sender is not functioning correctly. | Warning | Check that the engine oil pressure sender is properly connected. Contact an authorized service center. |
| 210 | LOW COOLANT TEMP | Warning occurs when engine coolant temperature is 70 F (21 C) or lower. Below 40F (4C) ambient the warning may occur even though coolant heaters are operating. | Warning | Indicates engine coolant heater is not operating or is not circulating coolant. Check coolant heater power supply (blown fuse or disconnected heater cord), check for low coolant level and replenish, look for coolant leakage points and repair. Contact an authorized service center if none of the above. |
| 211 | HIGH COOLANT TEMP | Indicates engine has begun to overheat and coolant temperature has risen to an unacceptable level: (215 F − standby / 207 F − primary). | Warning | Reduce load if possible; check air inlets/outlets and remove obstructions. |
| 212 | HIGH COOLANT TEMP | Indicates engine has overheated (coolant temperature above shutdown trip point: 223 F − standby / 215 F − primary) or the coolant level is low. | Shutdown | Allow to cool; check coolant level, airflow, fan belt. Reset and restart. Contact service center if unresolved. |
| 213 | ENG COOLANT SENDER | Indicates that the resistance of the coolant temperature sender is out of range. | Warning | Contact an authorized service center. |
| 214 | LOW COOLANT LVL | Indicates engine coolant level has fallen below the trip point. (Shutdown will not occur if generator set is in Idle mode − low coolant warning only.) | Warning | Allow to cool; check and replenish coolant; repair leaks; reset and restart. |
| 215 | LOW COOLANT LVL | Indicates engine coolant level has fallen below the trip point. (Shutdown will not occur if generator set is in Idle mode − low coolant warning only.) | Shutdown | Allow to cool; check and replenish coolant; repair leaks; reset and restart. |
| 220 | MAG PICKUP | Mag pickup speed indication not sensed or does not match genset output frequency. | Shutdown | Restart and check RPM on the digital display. Contact an authorized service center. |
| 221 | FAIL TO CRANK | Possible fault with control or starting system. | Shutdown | Check fuse F3 on the Engine Interface board; clean and tighten battery cable connections; recharge or replace the battery. |
| 222 | OVERCRANK | Possible fuel system problem. | Shutdown | Check fuel tank, leaks, plugged fuel lines; replace dirty fuel or air filters. Reset and restart. |
| 223 | OVERSPEED | Indicates engine has exceeded normal operating speed (115% +/-1% of nominal). | Shutdown | Refer to engine service manual to troubleshoot fuel system; use InSite service tool to troubleshoot CM570 module. |
| 230 | LOW DC VOLTAGE | Indicates battery voltage is below 24 VDC. | Warning | Check the battery charger fuse. Discharged or defective battery: recharge or replace. Check for poor battery cable connections; clean terminals and tighten all connections. Contact an authorized service center if none of the above. |
| 231 | HIGH DC VOLTAGE | Indicates battery voltage exceeds 32 VDC. | Warning | Contact an authorized service center. |
| 232 | WEAK BATTERY | Indicates battery voltage drops below 60% of nominal for two seconds, during starting. | Warning | See Warning message 230, LOW DC VOLTAGE. |
| 240 | LOW FUEL-DAY | Indicates day tank fuel supply is running low. | Warning | Check fuel supply and replenish as required. |
| 241 | LOW FUEL | Indicates fuel supply is running low. | Warning | Check fuel supply and replenish as required. |
| 250 | EEPROM ERROR | PCC memory error; data corruption of critical operating parameters. | Shutdown | Perform the initial start setup procedure; if the genset shuts down on the same EEPROM ERROR message, replace the digital board (A32). |
| 251 | EEPROM ERROR | PCC memory error; data corruption of noncritical operating parameters. | Warning | Perform the adjustment procedures; if same error, perform calibration procedures; if same error, replace digital board (A32). |
| 252 | EEPROM ERROR | PCC memory error; data corruption of noncritical operating parameters. | Warning | Verify values or choices selected and repeat the save operation; if same error, replace digital board (A32). |
| 260 | CUSTOMER FAULT 1 | When this customer defined input is closed to ground, the corresponding fault message is displayed. The nature of the fault is an optional customer selection. (Default message; editable for customer site requirements.) | Warning | These fault functions can be programmed to initiate a shutdown or a warning. Contact an authorized service center. |
| 261 | GROUND FAULT | When this customer defined input is closed to ground, the corresponding fault message is displayed. The nature of the fault is an optional customer selection. (Default message; editable for customer site requirements.) | Warning | These fault functions can be programmed to initiate a shutdown or a warning. Contact an authorized service center. |
| 262 | CM570/ENGINE | Indicates that the engine control module (CM570) is not properly operating. | Warning | Contact an authorized service center. |
| 263 | CM570/ENGINE | Indicates that the engine control module (CM570) is not properly operating. | Shutdown | Contact an authorized service center. |
| 301 | HIGH AC VOLTAGE | One or more phase voltages exceeded 130% of nominal, or 110% of nominal for 10 seconds. | Shutdown | Determine if output voltage the control sees is low or high; isolate regulator module A37, A31, A32, A36, A34, or A33. |
| 303 | LOW AC VOLTAGE | One or more phase voltages dropped below 85% of nominal for 10 seconds. | Shutdown | Contact an authorized service center. |
| 313 | UNDER FREQUENCY | Indicates that engine speed has dropped below 90% of nominal for 10 seconds. Five seconds before shutdown a Load Dump signal is initiated. | Shutdown | Load Dump signal initiated five seconds before shutdown. Contact an authorized service center. |
| 320 | OVERCURRENT | Indicates that generator output current has exceeded 110% of rated for 60 seconds. | Warning | Contact an authorized service center. |
| 321 | OVERCURRENT | Output current exceeded 110% of rated; PCC time/current calculation initiated shutdown. | Shutdown | Contact an authorized service center. |
| 322 | SHORT CIRCUIT | Indicates that generator output current has exceeded 175% of rated. | Shutdown | Contact an authorized service center. |
| 330 | OVERLOAD | Three-phase output exceeds 105% of standby (or 115% of prime) rating. | Warning | Load Dump activated after 5 seconds; OVERLOAD warning after 60 seconds. Contact an authorized service center. |
| 335 | REVERSE POWER | Indicates improper CT or PT phasing. (Non-parallel units only.) | Shutdown | Contact an authorized service center. |