HomeEnginesCummins/Onan KTTA50

Cummins/Onan KTTA50 Engine

The Cummins/Onan KTTA50 is an engine. It powers generator sets from Cummins/Onan, including the DFLC and DFLE. It holds 169 L (44.6 gal) of oil and 386 L (102.0 gal) of coolant.

Also known as: Cummins KTTA50

Part of the Cummins/Onan KTTA50 engine family — 2 variants share parts & fitment.

169.0 L
Oil capacity

Engine specifications

Oil capacity169.0 L
Coolant capacity386.0 L

Common problems

15
  • Warning Status Indicator: This yellow lamp is lit whenever the control detects a warning condition.
    Fix: After the condition is corrected, warning indicators can be reset by pressing the Reset switch. (It is not necessary to stop the generator set.) In auto mode, warning indicators can also be reset by cycling the remote reset input after the condition is corrected.
  • Warning lamp lights. 210
    Fix: Indicates set is in standby mode but is not operating. Warning occurs when engine coolant temperature is 70 F (21 C) or lower. NOTE: In applications where the ambient temperature falls below 40F (4C), Low Engine Temp may be indicated even though the coolant heaters are operating. Indicates engine coolant heater is not operating or is not circulating coolant. Check for the following conditions: a. Coolant heater not connected to power supply. Check for blown fuse or disconnected heater cord and correct as required. b. Check for low coolant level and replenish if required. Look for possible coolant leakage points and repair as required. c. Contact an authorized service center if none of the above.
  • Shutdown Status Indicator: This red lamp is lit whenever the control detects a shutdown condition.
    Fix: After the condition is corrected, shutdown indicators can be reset by turning
  • Shutdown lamp lights. 200
    Fix: Indicates engine oil pressure has dropped to an unacceptable level. If generator is powering critical loads and cannot be shut down, wait until next shutdown period then follow 201 Low Oil Pressure procedure. If engine can be stopped, follow 201 procedure. To check oil pressure, access Oil Pressure menu prior to clearing the fault.
  • PCC memory error. Data corruption of noncritical operating parameters. Warning lamp lights. 251
    Fix: Contact an authorized service center.
  • PCC memory error. Data corruption of critical operating parameters. Shutdown lamp lights. 250
    Fix: Contact an authorized service center.
  • One or more of the phase voltages has exceeded 130% of nominal, or has exceeded 110% of nominal for 10 seconds. Shutdown lamp lights. 301
    Fix: Contact an authorized service center.
  • Non-Automatic lamp flashes.
    Fix: Indicates Run/Off/Auto switch is not in the Auto position. This will prevent automatic starting if an automatic transfer switch is used. Move the Run/Off/Auto switch to the Auto position for automatic operation.
  • Indicates engine coolant level has fallen below the trip point. Shutdown lamp lights. 220
    Fix: A. Check coolant level and replenish if low. Look for possible coolant leakage points and repair if necessary. b. Reset control and restart after locating and correcting problem. Contact an authorized service center.
  • Fuel supply is running low. Warning lamp lights. 241
    Fix: Check fuel supply and replenish as required.
  • Engine will not crank. Shutdown lamp lights. 221
    Fix: A. Poor battery cable connections. Clean the battery cable terminals and tighten all connections. b. Discharged or defective battery. Recharge or replace the battery. c. Contact an authorized service center for service of starter and starting system.
  • Engine stops cranking. Shutdown lamp lights. 222
    Fix: A. Check for empty fuel tank, fuel leaks, or plugged fuel lines and correct as required. b. Check for dirty fuel filter and replace if necessary. c. Check for dirty or plugged air filter and replace if necessary. d. Reset the control and restart after correcting the problem. Contact an authorized service center if none of the above.
  • Engine shuts down and will not crank. 102
    Fix: Indicates local or remote Emergency Stop. To reset the local Emergency Stop button: Pull the button out or turn the switch clockwise (button with arrow) and allow it to pop out. Move the Run/Off/Auto switch to Off. Press the Reset switch. Select Run or Auto, as required.
  • Engine runs and then shuts down. Shutdown lamp lights. 223
    Fix: Contact an authorized service center.
  • Engine continues to operate at reduced RPM. 101

Compiled from service & troubleshooting documentation across every generator set that uses the Cummins/Onan KTTA50.

Service intervals

8
ItemActionHoursMonthsNotes
crankcase oilChange50 hrFirst service — Drain and replace the crankcase oil after the first 50 hours of operation on new generator sets
Check Electrolyte Level (batteries)Check200 hrAt least every 200 hours of operation
Change Crankcase Oil and FilterChange250 hr12 moIf used for standby applications, change oil every 12 months or 250 hours, whichever comes first (footnote X6)
Crankcase oil and filterChange250 hr12 moStandby applications: change oil every 12 months or 250 hours, whichever comes first
Grease generator bearing (P7)Lubricate4000 hrTable 5-2 explicit interval; grease type Kluber ASONIC GHY72, 75 grams
Generator bearing (P7 only)Lubricate4500 hrRe-lubrication period 4000-4500 hours; 75 grams Kluber ASONIC GHY72
Exercise generator setTest1 moAt least once a month for a minimum of 30 minutes, under not less than 30 percent of nameplate rating
Rupture basin leak detect switchTest12 moSome areas may require weekly inspections by safety code.

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Service specifications

60
TypeItemValueUnitCondition
ClearanceAir cleaner nozzle distance from element1inch (25 mm) minimumwhen cleaning with compressed air
ClearanceFloat switch assembly float lift clearance below C-clip stop1/8inch (3 mm)use a feeler gauge
ClearanceGenerator-to-engine angular alignment (T.I.R.).001 in. per inch of radius (center of shaft to indicator axis), maximumin750 kW gensets and larger
ClearanceMPU sensor to gear tooth adjustmentback out one quarter turnturnafter contacting gear tooth
GapFloat switch lift to test open1/8inchbelow C-clip stop
OtherAVR Droop setting5% at full load, 0 PF
OtherAVR voltage regulation (load regulation)approximately ±0.5% RMS
OtherB+ output fuse10ampF1, Base board, 12/24 volt
OtherBattery charging current45Amps
OtherBattery specific gravity (high ambient, above 95F/35C)1.225recommended to reduce electrolyte loss
OtherBattery specific gravity (recharge threshold)below 1.260
OtherBattery specific gravity - charge threshold (below this, charge battery)1.215
OtherBattery specific gravity - fully charged (corrected)1.260
OtherContinuous crank without cycle cranking option (PCC)up to 75seconds
OtherCustomer Output relay contact rating2amps at 30 VDCTB1 customer outputs 1-4, normally open
OtherGOV GAIN default value for paralleling applications70%
OtherGround Fault Relay current setting5 to 1200amperesoptional GFR
OtherGround Fault Relay time delay setting0 to 1secondoptional GFR
OtherOptional control relay (K11/K12/K13) contact rating10amps at 600 VAC
OtherOutput frequency adjustment range+/- 5%set running, not in idle mode
OtherOver/Under Frequency Sensor Module - Over Hz Set, 50 Hz nominal55Hzreset 53 Hz
OtherOver/Under Frequency Sensor Module - Over Hz Set, 60 Hz nominal65Hzreset 63 Hz
OtherOver/Under Frequency Sensor Module - Under Hz Set, 50 Hz nominal45Hzreset 47 Hz
OtherOver/Under Frequency Sensor Module - Under Hz Set, 60 Hz nominal55Hzreset 57 Hz
OtherOver/Under Voltage Sensor Module time delaytypically 25 percent, approximately 2.5seconds
OtherOvercrank cranking limit75secondsthree 15-second cranking cycles with two 15-second rest periods
OtherOvercrank cycle cranking (Detector, standard)three 15-second cranking cycles with two 15-second rest periodsseconds
OtherOvercrank cycle cranking (PCC)3, 4, or 5 cycles; crank and rest times 7 to 20seconds
OtherOvercrank limit (Detector, optional)75seconds
OtherREG VHZ (underfrequency roll-off) adjustable range1 through 50; normal range 7 through 21
OtherStart delay (PCC, remote start in Auto)0 to 300seconds
OtherStart delay adjustment range0 to 300seconds
OtherStop delay (PCC, remote stop in Auto)0 to 600seconds
OtherStop delay adjustment range0 to 600seconds
OtherSwitched B+ output fuse5ampF2, Base board, 12/24 volt
OtherUnder Frequency Roll Off (UFRO) knee point, 50 Hz units48 to 49Hz
OtherUnder Frequency Roll Off (UFRO) knee point, 60 Hz units58 to 59Hz
PressureAir cleaner cleaning compressed air pressure30psi (207 kPa)blow through element from clean side
PressureAir cleaner element cleaning, compressed air pressure30psi (207 kPa)blow through element from clean side; nozzle at least 1 inch (25 mm) away
PressureDetector oil pressure normal range after reset25 to 40psi (172 to 275 kPa)
PressureEngine oil pressure - K19 normal50-70psi (345-482 kPa)run mode
PressureEngine oil pressure - K38 normal45-65psi (310-448 kPa)run mode
PressureEngine oil pressure - K50 normal50-70psi (345-482 kPa)run mode
PressureEngine oil pressure - L10/M11 normal30-50psi (207-345 kPa)run mode
PressureEngine oil pressure - NTA 855 normal35-50psi (241-345 kPa)run mode
PressureEngine oil pressure - V28 normal50-90psi (345-620 kPa)run mode
PressureEngine oil pressure shutdown limit - L10/M1120psi (138 kPa)run mode value
PressureEngine oil pressure shutdown limit - L10/M118psi (55 kPa)idle mode value
PressureEngine oil pressure warning limit - L10/M1112psi (83 kPa)idle mode value
PressureEngine oil pressure warning limit - L10/M1125psi (172 kPa)run mode value
PressureIdle oil pressure (PCC)20psi (138 kPa)idle
PressureIdle oil pressure - shutdown limit10psi (69 kPa)idle oil pressure table, label order uncertain from source table layout
PressureIdle oil pressure - value 120psi (138 kPa)idle oil pressure table, label order uncertain from source table layout
PressureIdle oil pressure - warning limit15psi (103 kPa)idle oil pressure table, label order uncertain from source table layout
PressureIdle oil pressure shutdown limit (PCC)10psi (69 kPa)idle
PressureIdle oil pressure warning limit (PCC)15psi (103 kPa)idle
PressureK19 engine idle oil pressure20psi (138 kPa)idle
PressureK19 engine normal oil pressure50-70psi (345-482 kPa)normal run
PressureK19 oil pressure shutdown/warning limitsshutdown 35 psi (241 kPa) run; warning 40 psi (276 kPa) run; shutdown 10 psi (69 kPa) idle; warning 15 psi (103 kPa) idlepsi (kPa)
PressureK38 engine idle oil pressure20psi (138 kPa)idle

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Recommended fluids

FluidGradeStandardAmbientCapacityNotes
CoolantWater/antifreeze mixture (permanent type antifreeze)Water should be clean, low in mineral content, free of chloride, sulphate or acid; mix per supplier for lowest expected ambient temperature; do not use antifreeze containing anti-leak additives
Coolantsoft water / E.G. / DCA mixtureCooling system to be filled with soft water/E.G./DCA mixture (on-site review checklist).
Engine oilAPI Class CC/CD, maximum sulphated ash content 1.85 percentMultigrade/multiviscosity oils recommended; single grade oil not recommended; do not mix oils of different classification or brand
Engine oilSAE 5W syntheticAPI class CC/CD; sulphated ash not to exceed 1.85 percentbelow -25°CFor ambient temperature consistently below -30 deg F (-25 deg C) with no provision to keep engine warm; pour point 9 deg F (5 deg C) below lowest expected temperature; viscosity max 10,000 mPa.s at -31 deg F (-35 deg C) and min 4.1 mm2/s at 212 deg F (100 deg C); do not use petroleum base 5W grade oil
FuelASTM No. 2 dieselASTMAlternate diesel fuels per Cummins engine O&M Manual specifications
FuelDieselDay tank fuel transfer pump maintains reservoir of diesel fuel in the day tank.
FuelNo. 2 dieselEngine will also operate on No. 1 fuel or similar fuels if they meet specifications; consult engine manufacturer for non-standard fuel
GreaseKluber, type ASONIC GHY7275.0 gramsP7 generator bearing re-lubrication grease fill quantity; fill period 4000-4500 hours. Must not be mixed with any other type.
GreaseLithium based-30°C to 120°C81.0 mlMobilux No. 2 or Shell Alvania R3; generator end bearing; temperature range -22 F to +248 F (-30 C to +120 C); grease divided between bearing, bearing cap cavity and cartridge cavity.
GreaseLithium based grease, Mobilux No. 2 or Shell Alvania R3-30°C to 120°C2.74 oz (81 ml)End bearing lubricant; grease equally divided between bearing, bearing cap cavity and bearing cartridge cavity.
OtherDonaldsons D1400 solvent (or equivalent)Air cleaner element cleaning: soak filter at least 15 minutes in water and Donaldsons D1400 solvent.

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Fault codes

80
CodeNameMeaningSeverityAction
101IDLE MODEIndicates that the engine is operating in idle mode. Grounding the engine idle input causes generator build-up to be inhibited and the engine to be governed at 800 RPM.WarningRemove ground from engine idle input to return to normal speed and voltage.
102EMERGENCY STOPLocal or remote Emergency Stop activatedShutdownTurn the switch clockwise and allow it to pop out (local only). Move the Run/Off/Auto switch to Off. Press the Reset switch. Select Run or Auto, as required.
1122Rated/Idle TransInfo
1123Shutdown After Battle ShortShutdown fault occurred while Battle Short was enabled and then disabled.ShutdownReview Fault History and perform corrective action.
1124Delayed ShutdownShutdown fault became active while Delayed Shutdown feature was enabled.WarningReview Fault History and perform corrective action.
1131Battle Sh ActiveControl is in Battle Short mode.WarningBypasses several critical fault shutdowns for emergency operation.
121Speed Signal LostMag pickup speed indication is not being sensed.ShutdownRestart and check RPM on the digital display.
1311Customer Input #1Optional customer selection (e.g. Low Fuel Day Tank, Water In Fuel, Ground Fault). Programmable via service tool: enable/disable, status/warning/shutdown, active open/closed, display name.
1311, 1312, 1317, 1318CUSTOMER INPUT #1 - #4Optional customer-selected fault input is active.WarningCheck external wiring and active input (closed/open) selection.
1312Customer Input #2See code 1311.
1313-1316Network Fault 1 thru 4
1317Customer Input #3See code 1311.
1318Customer Input #4See code 1311.
1334Crit Scaler Out Of RangeIncorrect feature or calibration entered into control.ShutdownReload correct calibration.
1335Noncrit Scaler Out Of RangeIncorrect feature or calibration entered into control.WarningReload correct calibration.
1337No MessageInfo
135Oil Pressure Sensor HEngine oil pressure sender signal is shorted high.WarningCheck sender/connectors/wires.
141Oil Pressure Sensor LEngine oil pressure sender signal is shorted low.WarningCheck sender/connectors/wires.
1416Fail To ShutdownGenset continues to run after shutdown command.WarningCheck Battle Short feature enabled condition.
1417Powr Down ErrorController cannot power down.WarningController cannot power down; possible drain on battery. Contact an authorized service center.
143Pre-Low Oil PresEngine oil pressure has dropped to an unacceptable level.WarningIf generator is powering critical loads and cannot be shut down, wait until next shutdown period and then follow code 415 procedure.
1433Emergency StopLocal Emergency Stop.ShutdownPull button out; move switch to O; press Fault Acknowledge/Reset; select Manual or Auto.
1434Remote E-StopRemote Emergency Stop.ShutdownSee code 1433 to reset.
1435Low Coolant TempWarning LED illuminates when engine jacket water coolant temperature falls below 70°F (21°C); per NFPA 110 requirement, indicates engine may not accept load within 10 secondsWarningSet is not operating; occurs when coolant temperature is 70°F (21°C) or lower. Check coolant heater power/fuse/cord, check coolant level and leaks.
1438Fail To CrankEngine failed to crank after PCC received a start signal.ShutdownPossible fault with control, speed sensing, or starting system. See code 441 for corrective action.
144Coolant Sensor HighEngine coolant temperature signal is shorted high.WarningCheck sender/connectors/wires.
1442Weak BatteryBattery voltage at or below weak battery warning trip point during cranking.WarningSee code 441 for corrective action.
1443Battery FailedDead battery - engine will not start.ShutdownSee code 441 for corrective action.
1444KW OverloadGenerator output power exceeded 105% of genset rating.WarningCheck load and load lead connections; check CTs.
1445Short CircuitGenerator output current has exceeded 175% of rated.ShutdownCheck load and load lead connections.
1446High AC VoltageOne or more phase voltages exceeded 130% of nominal.ShutdownCheck fault simulation, load removal, threshold settings, Base board/generator.
1447Low AC VoltagePhase voltages dropped below 85% of nominal for 10 seconds.ShutdownCheck overload, output terminal connections, PMG/field wiring, rectifier diodes.
1448Under FrequencyEngine speed dropped below 90% of nominal for 10 seconds.ShutdownCheck fuel supply, intake air supply and load.
1449Over FrequencyFrequency is 10% above base frequency for 20 seconds.WarningCheck fuel or air delivery; check connections.
145Coolant Sensor LowEngine coolant temperature signal is shorted low.WarningCheck sender/connectors/wires.
1452Gen CB Not CloseGenset circuit breaker (S2) failed to close when PTC is enabled.WarningRefer to Section 5 troubleshooting charts.
1453Gen CB Not OpenGenset circuit breaker (S2) failed to open when PTC is enabled.WarningRefer to Section 5 troubleshooting charts.
1459Reverse PowerImproper CT phasing.ShutdownCheck wiring to voltage sense circuit; refer to CT Installation in Section 6.
146Pre-High Coolant TempEngine has begun to overheat.WarningReduce load; check air inlets/outlets; follow code 151 if engine can be stopped.
1461Loss Of FieldLoss of field (electric) due to reverse kVAR.ShutdownCheck excitation circuit.
1466Modem FailureControl cannot communicate with the modem.WarningCheck for open, short to ground and loose connections to the modem.
1468Network ErrorMomentary loss of communication from the LonWorks Network.WarningRefer to LonWorks Network publications.
1469Speed/Hz MatchMeasured speed and measured AC output frequency do not agree.ShutdownCheck calibration file.
1471Over CurrentGenerator output current exceeded 110% of rated for 60 seconds.WarningCheck load and load lead connections.
1472Over CurrentOutput current exceeded 110% of rated and time/current calculation initiated shutdown.ShutdownCheck load and load lead connections.
151High Coolant TempEngine has overheated above the shutdown trip point.ShutdownAllow engine to cool completely. Check coolant level and replenish if low, look for leaks and repair. Check for obstructions to cooling airflow. Check fan belt. Check blower fan/circulation pumps on remote radiator installations. Reset control and restart.
197Low Coolant LevelEngine coolant level has fallen below the warning trip point.WarningOptional. If generator is powering critical loads and cannot be shut down, wait until next shutdown period, then follow code 235 procedure. If engine can be stopped, follow code 235 procedure.
200LOW OIL PRESSUREIndicates engine oil pressure has dropped to an unacceptable level.WarningIf generator is powering critical loads and cannot be shut down, wait until next shutdown period and then follow 201-SHUTDOWN procedure. Access the Oil Pressure menu prior to clearing the fault.
201LOW OIL PRESSUREIndicates engine oil pressure has dropped below the shutdown trip point.ShutdownCheck oil level, replenish if low, reset control and restart; contact authorized service center.
204OIL PRES SENDERIndicates that the control has sensed that the engine oil pressure sender is out of its working range.WarningCheck that the engine oil pressure sender is properly connected.
210LOW COOLANT TEMPWarning occurs when engine coolant temperature is 70°F (21°C) or lower.WarningIndicates engine coolant heater is not operating or is not circulating coolant. Check coolant heater power supply, low coolant level, and heater element current draw.
211HIGH COOLANT TEMPIndicates the engine coolant temperature is getting close to the recommended maximum temperature limit: 215° F (102° C) − standby or 207° F (97° C) − primary.WarningReview 212 correction list; increase in load or higher ambient may cause shutdown.
212Oil Temp Sensor HIndicates engine has overheated (coolant temperature above 215° F (102° C) − standby or 207° F (97° C) − primary).WarningCool engine; check coolant level, airflow obstructions and fan belt; reset and restart.
213Oil Temp Sensor LResistance of the coolant temperature sender is out of range.WarningContact authorized service center.
214LOW COOLANT LVLIndicates engine coolant level has fallen below the trip point.WarningCool engine; check coolant level and leaks; reset control and restart.
215LOW COOLANT LVLIndicates engine coolant level has fallen below the trip point.ShutdownCool engine; check coolant level and leaks; reset control and restart. Shutdown will not occur in Idle mode.
220MAG PICKUPMag pickup speed indication not sensed or does not match output frequencyShutdownRestart and check RPM; check PCC model setting; inspect and test MPU.
221FAIL TO CRANKPossible fault with control or starting system.ShutdownClean and tighten battery cables; recharge or replace battery; contact service center.
222OVERCRANKPossible fuel system problem.ShutdownCheck fuel tank, leaks, plugged lines, fuel filter and air filter; reset control and restart.
223OVERSPEEDIndicates engine has exceeded normal operating speed. (115% ±1% of nominal).ShutdownContact authorized service center.
224FAIL TO SYNCHRONIZEGenerator set has not synchronized to the system bus within the allowable time frame.WarningCheck governor system stability; adjust governing and synchronizer parameters; check fuel system.
226FAIL TO CLOSEParalleling breaker has been given a signal to close, but has not closed properly.ShutdownVerify breaker charging mechanism; check close signal; verify auxiliary contact signals.
230LOW DC VOLTAGEIndicates battery voltage is below 10 VDC.WarningRecharge or replace the battery; check the battery charger fuse. Clean and tighten battery cable connections. Check engine DC alternator; replace if normal charging voltage is not obtained. Check float level if applicable.
231HIGH DC VOLTAGEIndicates battery voltage exceeds 32 VDC.WarningLower battery charger float level if applicable; check engine DC alternator.
232WEAK BATTERYIndicates battery voltage drops below 60% of nominal for two seconds, during starting.WarningSee warning message 230 LOW DC VOLTAGE.
2323-2326Network Fault 5 thru 8
2327PTC FaultPTC module or communication link is not working properly.WarningCheck PTC module power, ground shield, cycle control power.
2329Low S1 FrequencyLow utility (S1) frequency.WarningCheck S1 AC inputs and wiring to PTC at TB5; check sensor set points.
2331Low S1 VoltageLow utility (S1) voltage.WarningCheck S1 AC inputs and wiring to PTC at TB5; check pickup/dropout set points.
2335Excitation FaultLoss of all three voltage sense leads or failure in excitation circuit.ShutdownCheck field wiring (X1 and X2) for shorts or opens.
2336Memory ErrorControl memory error; data corruption of critical operating parameters.ShutdownTry reloading calibration file.
2337Pwr Tran DisabledPTC module available but PTC feature not enabled.WarningEnable PTC feature with InPower; cycle control power.
2338Pwr Tran FailureControl could not communicate with the PTC module.WarningCheck PTC module power and cable ground shield; cycle control power.
2339Pwr Down EnabledPower Down (sleep) enabled but PTC module or network board is active.WarningNone required.
234OverspeedEngine has exceeded normal operating speed.ShutdownCheck for large block load removal, flammable vapors or leaking turbocharger seals.
2341High Control TempControl temperature above 158 F (70 C) for longer than set time.WarningCheck genset room air flow.
2342Too Long In Idle (10 min.)Genset has been in Idle mode too long.WarningExit idle mode.
235Low Coolant LevelEngine coolant level has fallen below the shutdown trip point.ShutdownOptional. Allow engine to cool completely. Check coolant level and replenish if low, look for leaks and repair. Reset control and restart.
2358High S1 VoltageUtility (S1) voltage increased above the over-voltage threshold.WarningMeasure S1 AC inputs at PTC module; check sensor set points.
2396S1 CB Not CloseUtility contact (S1) failed to close with PTC enabled.WarningRefer to Section 5 troubleshooting charts.

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Procedures

12
Aligning Generator with Engine (Angular Alignment) adjustment

⚠ Accidental starting of the generator set during this procedure presents the hazard of severe personal injury or death.

Tools: Dial indicator, Shims

  1. Disconnect the negative (-) battery cable(s) before beginning.
  2. Fasten a dial indicator to the generator shaft or cooling fan with the sensing point on the capscrew head or flat surface of the drive disc at the bolt circle diameter.
  3. Bar the engine over in a clockwise rotation as viewed from engine flywheel; do not allow it to roll back on compression.
  4. Determine the total indicator reading (T.I.R.) as the sum of the maximum positive and negative dial indicator readings over one revolution.
  5. Measure the distance from the center of the generator shaft to the indicator measuring point.
  6. Measure the distance from the generator side of the flex discs to the center of the generator mounting bolt.
  7. Compare the distances; multiply this ratio times one half the T.I.R. to approximate the amount of shims to remove or add.
Angular Alignment Procedure (750 kW gensets and larger) adjustment

⚠ Accidental starting during this procedure presents hazard of severe injury or death

⚠ Do not bar engine over by prying on fan blade

Tools: dial indicator

  1. Disconnect negative battery cable(s) before beginning
  2. Fasten dial indicator to generator shaft or cooling fan, sensing point on capscrew head or drive disc flat surface
  3. Bar engine over in clockwise rotation as viewed from flywheel, do not allow roll-back at end of travel
  4. Record total indicator reading (T.I.R.) as sum of max positive and negative readings over one revolution
  5. Calculate shim correction using ratio of generator shaft-to-indicator distance vs generator mounting bolt distance
  6. Add or remove shims from both generator mounting feet as calculated
Angular Alignment Procedure (Generator to Engine) adjustment

⚠ Accidental starting during this procedure presents the hazard of severe personal injury or death.

⚠ Do not bar engine over by prying on fan blade.

Tools: dial indicator

  1. Disconnect the negative (-) battery cable(s) before beginning.
  2. Fasten a dial indicator to the generator shaft or cooling fan with sensing point resting on the drive disc capscrew head/flat surface at the bolt circle diameter.
  3. Bar the engine over in a clockwise rotation as viewed from the engine flywheel; do not allow it to roll back on compression at the end of travel of each reading.
  4. Record the total indicator reading (T.I.R.) as the sum of the maximum positive and negative dial indicator readings over one engine revolution.
  5. Compare the measured T.I.R. to the maximum allowed (.001 in. per inch of radius from center of shaft to indicator axis); add or remove shims under the generator mounting feet to correct.
Axial Alignment Procedure (750 kW gensets and larger) adjustment

Tools: dial indicator

  1. Check axial alignment only when objectionable vibration is present after angular alignment
  2. Fasten dial indicator holding device to skid base/engine block/generator shell, sensor on generator shaft hub
  3. Bar engine over clockwise through a couple of rotations, recording readings at eight equally spaced points
  4. If out of tolerance, remove capscrews connecting drive discs and flywheel, mark discs, reposition holes 180 degrees
  5. Reinstall capscrews and retorque; recheck alignment; try 30/60/90 degree repositioning if unchanged
Axial Alignment Procedure (Generator to Engine) adjustment

Tools: dial indicator

  1. Fasten a dial indicator holding device to the skid base, engine block, or generator shell with the sensor point resting on the generator shaft hub.
  2. Bar the engine over in a clockwise rotation through a couple of rotations, recording indicator readings at eight equally spaced points around the shaft diameter to obtain axial T.I.R.
  3. Reduce the measured T.I.R. runout by one half if excessive vibration remains after angular alignment.
Electric Governor Preliminary Adjustments adjustment
  1. Idle Speed potentiometer: turn the screw counterclockwise 20 turns, then clockwise 10 turns to set mid position.
  2. Run Speed potentiometer: turn the screw counterclockwise 20 turns, then clockwise 10 turns to set mid position.
  3. Gain potentiometer: turn the screw fully counterclockwise.
  4. Droop potentiometer: turn fully counterclockwise for isochronous operation.
  5. Droop potentiometer: turn to approximately 40 for 3 percent droop, or approximately 80 for 5 percent droop.
Fine Speed Adjustment adjustment
  1. After the gain adjustment is made, adjust full load governed engine speed to equal the desired speed (60 Hz, 1800 RPM or 50 Hz, 1500 RPM).
  2. Use the SPEED ADJUST potentiometer on the engine instrument panel for fine speed adjustments of less than +/-100 RPM.
Gain Adjustment adjustment
  1. Close the main line circuit breaker and apply approximately 1/4 of the rated load.
  2. Make sure the engine speed is constant. If constant, turn the GAIN potentiometer clockwise slowly until the engine speed is not constant.
  3. Slowly turn the potentiometer counterclockwise until a constant speed is achieved.
  4. Turn the potentiometer counterclockwise an additional 1/2 division.
Generator/Base Board Isolation Procedure diagnostic

⚠ This test involves unregulated excitation of the generator.

⚠ Hazardous voltage; use insulated tools and stand on dry platform.

Tools: Voltmeter, Jumper leads, 12V battery

  1. Throw line circuit breaker OFF and shut down the set.
  2. Disconnect exciter stator leads X and XX from AC harness.
  3. Prepare to measure output voltage across generator terminals.
  4. Bring 12V battery jumpers to X (Field +) and XX (Field -).
  5. Verify polarity is correct before connecting.
  6. Start set; connect battery negative to XX lead.
  7. If rated voltage and balanced phases, generator is OK.
  8. If unbalanced troubleshoot main stator; if low troubleshoot exciter circuits.
Generator/PCC Control Isolation Procedure diagnostic

⚠ HIGH VOLTAGE. Touching uninsulated high voltage parts inside the control box can result in severe personal injury or death.

Tools: Voltmeter, Jumpers, 12 volt battery

  1. Throw the line circuit breaker OFF and shut down the set.
  2. Remove accessory box cover; remove plug P10 from A37 J10.
  3. Prepare to measure output voltage across generator terminals.
  4. Connect 12V battery jumpers to X (P10-6 red) and XX (P10-3 brown).
  5. Check polarity; incorrect polarity makes the test inconclusive.
  6. Start set and connect battery negative to the XX lead.
  7. Rated or higher balanced voltage means generator circuitry is OK.
  8. Unbalanced voltage: troubleshoot main stator; low voltage: exciter/field.
Ground Fault Relay Test diagnostic
  1. Verify N-G Fault Indicator on GFR is not lit; if lit, install bonding jumper at facility service entrance
  2. Move control switch to Run position
  3. Press TEST switch on ground fault relay
  4. Verify control panel warning message displayed and Fault Indicator (>I) lit on GFR
  5. Reset the control panel fault (also resets ground fault relay)
Insulation Resistance (Megger) & Polarization Index (PI) Testing diagnostic

⚠ The windings of medium-voltage (601 through 15,000 volts) generator sets must be dry before the generator is operated.

Tools: Megger or insulation resistance meter, Grounding cluster, High voltage gloves

  1. Perform the Generator Set Grounding Procedure.
  2. Disconnect plug J10 from A37 and AC control leads 4,5,6,7,8.
  3. If RTD option installed, ground all six RTD temperature leads (18 leads).
  4. Perform Insulation Resistance Test and PI Test for desired windings.
  5. Megger test: apply voltage for up to one minute.
  6. PI test: apply voltage for ten minutes; record 1-minute and 10-minute readings.
  7. PI ratio of 2 or greater is good for new and in-service sets.
  8. Investigate and correct low readings before returning set to service.

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Voltage reconnection

VoltagePhaseConnectionLeadsNotes
12 lead generator setsLoad wires are routed through the CTsReconnectable gensets (12 leads) have dual secondary CTs (3 pins); CT wire 2/3 to pin 2 (high voltage) or pin 3 (low voltage).
6 lead generator setsGenerator output leads are routed through the CTsNon-reconnectable gensets (6 leads) have single secondary CTs (2 pins).
Cummins PowerCommand generic AC Reconnect Wiring Diagram 625-2755 (Rev. D) and 625-3100 (Rev. F)Applies to models DFAA, DFAB, DFAC, DFBF, DFCB, DFCC, DFEB, DFEC, DFFB, DFGA, DFGB, DFJA, DFJB, DFJC, DFJD, DFLB, DFLC, DFLD, DFMB (625-2755) and models DFAA-DFMB plus DFCE, DFED, DQAA, DQAB, DQBA, DQBB (625-3100).
A (U)CT21U load leads (A phase)CT dot must face the generator; CT terminal 1 connects to metering circuit, terminal 2/3 to ground.
B (V)CT22V load leads (B phase)CT dot must face the generator; terminal 1 to metering circuit, terminal 2/3 to ground.
C (W)CT23W load leads (C phase)CT dot must face the generator; terminal 1 to metering circuit, terminal 2/3 to ground.
110 V - 120 V L-N1Single phase, 2-wirePTC module jumper locations
190 V - 240 V L-L3Three phaseUse PTC module 0300-5382-01; 50/60 Hz
200 V - 240 V L-L1Single phase, 3-wirePTC module jumper locations
380 V - 600 V L-L3Three phaseUse PTC module 0300-5382-02; 50/60 Hz

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Parts cataloged across the Cummins/Onan KTTA50 family

11
Part #DescriptionCategory
140-2503Bracket, Mountingair_filter
140-3163Cleaner, Air (No Replaceable Element)air_filter
140-3230Cleaner, Air (Includes Elements - See Ref. No. 25 and 26)air_filter
0300-4623-33DFLE (600V)current_transformer
0300-4623-57DFLE BR (0-480V)current_transformer
140-1260Fitting, Safety Filterother_service
140-2395Tube, Air Inletother_service
140-2504-01Bracket - Right Sideother_service
140-2504-02Bracket - Left Sideother_service
140-2509Tube, Air Inletother_service
140-2528Shieldother_service

Parts cataloged across all variants of this engine family — verify the exact part fits your specific variant and serial number before ordering.

Common questions

What is the oil capacity of the Cummins/Onan KTTA50?

The Cummins/Onan KTTA50 engine has an oil capacity of 169.0 liters.

Which generators use the Cummins/Onan KTTA50 engine?

The Cummins/Onan KTTA50 powers 2 generator set(s), including Cummins/Onan DFLC, Cummins/Onan DFLE.

What is a common problem with the Cummins/Onan KTTA50 engine?

A commonly reported issue on generators using the Cummins/Onan KTTA50 is: Warning Status Indicator: This yellow lamp is lit whenever the control detects a warning condition.. Fix: After the condition is corrected, warning indicators can be reset by pressing the Reset switch. (It is not necessary to stop the generator set.) In auto mode, warning indicators can also be reset by cycling the remote reset input after the condition is corrected..