Home›Repair guides›Cummins/Onan›Bus Voltage Calibration (C)

Cummins/Onan — Bus Voltage Calibration (C)

Adjustments · PowerCommand control bus voltage display

From a Cummins/Onan service manual — check it applies to your exact model before use.

Applies to: Cummins/Onan DFE

Before you start

  • Contacting hazardous voltage components can cause electrocution, resulting in severe personal injury or death.
  • Improper calibration or adjustment of the PowerCommand control can cause equipment malfunction or damage.

Procedure

  1. Display the Bus Voltage Calibration submenu.
  2. With all gensets OFF, attach a calibrated voltmeter to TB1-A (L1) and TB1-B (L2) of the bus PT module.
  3. Start another genset and allow it to reach normal operating speed and voltage; connect to the bus.
  4. Calibrate the voltage reading for Bus Volts L1 so display matches the calibrated meter.
  5. Shut the generator set OFF.
  6. Repeat steps 2 through 5 for Bus Volts L2 and L3.
  7. Exit menu to Save changes.

Tools required

  • Calibrated RMS multimeter (Fluke models 87 or 8060A) Amazon

Tool links are Amazon searches (affiliate links); manufacturer special tools may only be available from a dealer.

Specs & values

  • TB1-A - L1
  • TB1-B - L2
  • TB1-C - L3

Full service-parts list: Cummins/Onan DFE →

Source: Cummins/Onan service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.