Procedure

  1. The CT has a dot on one side. This dot must face toward the generator (conventional current flowing into the dot).
  2. CT21 - U load leads (A phase); CT22 - V load leads (B phase); CT23 - W load leads (C phase).
  3. Route the appropriate load wires through each CT.
  4. CT secondaries have 3 pins: secondary wire marked 1 to pin 1; wire marked 2/3 to pin 2 for high voltage gensets or pin 3 for low voltage gensets.