PowerCommand 3200 Controller

The PowerCommand 3200 is a generator-set controller. It is used on generator sets from Cummins/Onan, including the 1500DQKB, 1650DQKC, 1750DQKB and 2000 DQKC.

11
Generator sets
Cummins/Onan
Brand
400–2000 kW
Power range
Diesel
Fuel

Troubleshooting

60

Fault codes

CodeMeaningCauseRemedy
101Engine continues to operate at reduced RPM.Indicates that the engine is operating in idle mode. When the set is operating in the RUN mode, grounding the engine idle input causes generator build-up to be inhibited and the engine to be governed at 800 RPM. When ground is removed from this input, the set returns to normal speed and voltage.
102Engine shuts down and will not crank.Indicates local or remote Emergency Stop.To reset the local Emergency Stop button: Pull the button out or turn the switch clockwise (button with arrow) and allow it to pop out. Move the Run/Off/Auto switch to Off. Press the Reset switch. Select Run or Auto, as required.
111Internal ECM error
112Actuator not responding
1123Shutdown After Battle Short
1124Delayed Shutdown
113Actuator sensor fault
1131Battle Short Active
115No speed signal
116Time press sensor high
117Time press sensor low
118Pump press sensor high
119Pump press sensor low
121No engine speed signal
121Speed Signal Lost
122Manifold air press sensor
1244Engine Normal Shutdown
1245CAN - Engine Shutdown
1246CAN - Unknown Engine Fault
1247CAN - Engine Unannounced Fault
1248CAN - Engine Warning Fault
1311Customer Inputs #1
1311 through 1318Customer Defined Fault
1311 through 1318LAMP: Shutdown/Warning MESSAGE: Customer Defined FaultWhen any one of these customer defined inputs is detected by the control, the corresponding fault message is displayed. The nature of the fault is an optional customer selection. These fault functions can be programmed to initiate a shutdown or warning as indicated by the Warning or Shutdown lamp. Note: Customer fault messages are editable. The message displayed for the code shown (1311 through 1318) is determined by the customer.
1312Customer Inputs #2
1317Customer Inputs #3
1318Customer Inputs #4
1334Crit Scaler OR
1335Non-Crit Scaler OR
135Oil Pressure Sensor High
135Oil pressure sensor
141Oil Pressure Sensor Low
1416FAIL TO SHUTDOWNStatus ï indicates that the “Fault Bypass” mode is enabled. This mode is primarily used by service personnel for troubleshooting purposes.
1416Fail To Shut Down
1416LAMP: Warning MESSAGE: FAIL TO SHUTDOWNStatus – indicates that the “Fault Bypass” mode is enabled. This mode is primarily used by service personnel for troubleshooting purposes. In this mode the generator set ignores the majority of system shutdown faults.
1417LAMP: Warning MESSAGE: POWER DOWN ERRORIndicates that the control can not power down due to some unknown condition. Possible drain on battery. Contact an authorized service center for service.
1417POWER DOWN ERRORPossible drain on battery. Contact an authorized service center for service.
1417Power Down Failure
143Low oil pressure
143Pre-Low Oil Pressure Sensor
1433Emergency Stop
1433 / 1434EMERGENCY STOP ï LOCAL / EMERGENCY STOP ï REMOTETo reset the local/remote Emergency Stop button: Pull the button out. Move the O/Manual/Auto switch to O (off). Press the front panel Fault Acknowledge button. Select Manual or Auto, as required.
1433 / 1434LAMP: Shutdown MESSAGE: EMERGENCY STOP – LOCAL / EMERGENCY STOP – REMOTEIndicates local or remote Emergency Stop. Emergency Stop shutdown status can be reset only at the local control panel. To reset the local/remote Emergency Stop button: Pull the button out. Move the O/Manual/Auto switch to O (off). Press the front panel Fault Acknowledge button. Select Manual or Auto, as required.
1434Remote Emergency Stop
1435Low Coolant Temperature
1437FAULT HISTORY: 1 OF 24
1437FAULT HISTORY: 1 OF 24 CNTL HOURS 459 OCCURRENCES 5 ENGINE HOURS 334
1438FAIL TO CRANKA. Poor battery cable connections. Clean the battery cable terminals and tighten all connections. b. Discharged or defective battery. Recharge or replace the battery.
1438Fail to Crank
1438LAMP: Warning MESSAGE: FAIL TO CRANKIndicates possible fault with control or starting system. Check for the following conditions: a. Poor battery cable connections. Clean the battery cable terminals and tighten all connections. b. Discharged or defective battery. Recharge or replace the battery.
1439FUEL LEVEL LOW IN DAYCheck fuel supply and replenish as required.
1439LAMP: Warning MESSAGE: FUEL LEVEL LOW IN DAYIndicates fuel supply is running low. Check fuel supply and replenish as required.
144Coolant Temperature Sensor High
144Coolant temperature sensor
1441LAMP: Warning MESSAGE: FUEL LEVEL LOW IN MAINIndicates fuel supply is running low. Check fuel supply and replenish as required.
1442LAMP: Warning MESSAGE: BATTERY IS WEAKIndicates battery voltage drops below 14.4 volts for two seconds, during starting. Discharged or defective battery. See Warning message 441 Low Battery Voltage.
1442Weak Battery
1443Battery Failed
1443LAMP: Warning MESSAGE: BATTERY IS DEADIndicates battery has dropped below genset operating range (3.5 volts when cranking) to power the starter and the control circuitry. See Warning message 441 Low Battery Voltage.
1444KW Overload

Fault codes and symptom→remedy steps extracted from this controller’s service/owner documentation; verify against the official manual before servicing. Aggregated from the service documentation of generator sets built on this controller.