PowerCommand 3200 Controller

The PowerCommand 3200 is a generator-set controller. It is used on generator sets from Cummins/Onan, including the 1500DQKB, 1650DQKC, 1750DQKB and 2000 DQKC.

14
Generator sets
Cummins/Onan
Brand
400–2000 kW
Power range
Diesel
Fuel

Troubleshooting

60

Fault codes

CodeMeaningCauseRemedy
101Engine continues to operate at reduced RPM.Indicates that the engine is operating in idle mode. When the set is operating in the RUN mode, grounding the engine idle input causes generator build-up to be inhibited and the engine to be governed at 800 RPM. When ground is removed from this input, the set returns to normal speed and voltage.
102Engine shuts down and will not crank.Indicates local or remote Emergency Stop.To reset the local Emergency Stop button: Pull the button out or turn the switch clockwise (button with arrow) and allow it to pop out. Move the Run/Off/Auto switch to Off. Press the Reset switch. Select Run or Auto, as required.
1123Shutdown After Battle Short
1124Delayed Shutdown
1131Battle Short Active
121Speed Signal Lost
1244Engine Normal Shutdown
1245CAN - Engine Shutdown
1246CAN - Unknown Engine Fault
1247CAN - Engine Unannounced Fault
1248CAN - Engine Warning Fault
1311Customer Inputs #1
1311 through 1318Customer Defined Fault
1312Customer Inputs #2
1317Customer Inputs #3
1318Customer Inputs #4
1334Crit Scaler OR
1335Non-Crit Scaler OR
135Oil Pressure Sensor High
141Oil Pressure Sensor Low
1416FAIL TO SHUTDOWNStatus ï indicates that the “Fault Bypass” mode is enabled. This mode is primarily used by service personnel for troubleshooting purposes.
1416Fail To Shut Down
1417POWER DOWN ERRORPossible drain on battery. Contact an authorized service center for service.
1417Power Down Failure
143Pre-Low Oil Pressure Sensor
1433Emergency Stop
1433 / 1434EMERGENCY STOP ï LOCAL / EMERGENCY STOP ï REMOTETo reset the local/remote Emergency Stop button: Pull the button out. Move the O/Manual/Auto switch to O (off). Press the front panel Fault Acknowledge button. Select Manual or Auto, as required.
1434Remote Emergency Stop
1435Low Coolant Temperature
1438FAIL TO CRANKA. Poor battery cable connections. Clean the battery cable terminals and tighten all connections. b. Discharged or defective battery. Recharge or replace the battery.
1438Fail to Crank
1439FUEL LEVEL LOW IN DAYCheck fuel supply and replenish as required.
144Coolant Temperature Sensor High
1442Weak Battery
1443Battery Failed
1444KW Overload
1445Short Circuit
1446High AC Voltage
1447Low AC Voltage
1448Under Frequency
1449Over Frequency
145Coolant Temperature Sensor Low
146HIGH COOLANT TEMP WARNINGA. Reduce load if possible by turning off non-critical loads. b. Check air inlets and outlets and remove any obstructions to airflow. If engine can be stopped, follow 151 High Coolant Temp Alarm procedure.
1461Loss of Field
1466Modem Failure
1468Network Error
1469Speed/Hz Match
1471Over Current
1472Over Current
151HIGH COOLANT TEMP ALARMA. Check jacket water coolant level and replenish if low. Look for coolant leakage and repair if necessary. b. Check for obstructions to cooling airflow and correct as necessary. c. Check fan belt and repair if necessary. d. Reset control and restart after locating and correcting problem.
152LOW COOLANT TEMPA. Coolant heater not connected to power supply. Check for blown fuse or disconnected heater cord and correct as required. b. Check for low jacket water coolant level and replenish if required. Look for possible coolant leakage points and repair as required.
197COOLANT LEVEL WARNINGA. Check jacket water coolant level and replenish if low. Look for possible coolant leakage points and repair if necessary. b. Reset control and restart after locating and correcting problem.
212Shutdown lamp lights.Indicates engine has overheated (coolant temperature has risen above the shutdown trip point: 223° F – standby / 215° F – primary) or the coolant level is low. Allow engine to cool down completely before proceeding with the following checks:A. Check coolant level and replenish if low. Look for coolant leakage and repair if necessary. b. Check for obstructions to cooling airflow and correct as necessary. c. Check fan belt and repair or tighten if necessary. d. Reset control and restart after locating and correcting problem. Contact an authorized service center if none of the above.
213The Shutdown LED will blink the fault code as follows: blink-blink-pause-blink-pause-blink-blink-blink. The Warning LED will blink once (2 seconds) to indicate the start of a new code.Press and release the Fault Acknowledge button less than one second to return to the most recent fault code.
213The light will display the fault codes (active or inactive) in succession, starting with the most recent. Up to 32 (unacknowledged) fault codes can be stored in control panel memory.
2331Low AC Voltage
2335Excitation Fault
2336Memory Error
234Overspeed
2341High Control Temperature

Fault codes and symptom→remedy steps extracted from this controller’s service/owner documentation; verify against the official manual before servicing. Aggregated from the service documentation of generator sets built on this controller.