| 101 | IDLE MODE | Indicates that the engine is operating in idle mode; generator build-up is inhibited and engine governed at 800 RPM. | Warning | Remove ground from the engine idle input to return to normal speed and voltage. |
| 102 | EMERGENCY STOP | Indicates local or remote Emergency Stop. | Shutdown | Pull the button out; move the Run/Off/Auto switch to Off; press the Reset switch; select Run or Auto as required. Can only be reset at the PCC front panel. |
| 1122 | Rated/Idle Trans | | Info | |
| 1123 | Shutdown After Battle Short | A shutdown fault occurred while Battle Short was enabled and transitioned from enabled to disabled. | Shutdown | Review Fault History and perform corrective action. |
| 1124 | Delayed Shutdown | A shutdown fault became active while the Delayed Shutdown feature was enabled. | Warning | Review Fault History and perform corrective action. |
| 1131 | Battle Sh Active | Control is in Battle Short mode (bypasses several critical fault shutdowns). | Warning | None; used for genset operation during emergencies. |
| 121 | Speed Signal Lost | Mag pickup speed indication is not being sensed. | Shutdown | Restart and check RPM on digital display; inspect MPU wires/connector pins; check for 3.5 to 15 VAC at MPU while cranking. |
| 1311 | Customer Input #1 | | Warning | Optional customer selection (e.g., Low Fuel Day Tank, Water In Fuel, Ground Fault, Low Starting Hydraulic Pressure, Low Starting Air Pressure). Programmable: enable/disable, status/warning/shutdown, active closed or open, and display name. |
| 1311, 1312, 1317, 1318 | CUSTOMER INPUT #1 - #4 | Optional customer-selected fault input is active. | | Disconnect signal lead from TB1 and reset the control; check external wiring/active input selection. |
| 1312 | Customer Input #2 | | Warning | Optional customer selection; programmable (enable/disable, status/warning/shutdown, active open/closed, display name). Default #2 thru #4 - Warning. |
| 1317 | Customer Input #3 | | Warning | Optional customer selection; programmable (default #3 - Low Fuel). |
| 1318 | Customer Input #4 | | Warning | Optional customer selection; programmable (default #4 - Rupture Basin Fault). |
| 1334 | Crit Scaler Out Of Range | Incorrect feature or calibration was entered into control. | Shutdown | Reload correct feature/calibration file. |
| 1335 | Noncrit Scaler Out Of Range | Incorrect feature or calibration was entered into control. | Warning | Reload correct feature/calibration file. |
| 1337 | No Message | | Info | |
| 135 | Oil Pressure Sensor H | Engine oil pressure sender signal is shorted high. | Warning | Check sender/connectors/wires; verify fault simulation not enabled; check 0.5 to 4.5 VDC at P7-13 (OP OUT) and P7-17 (OP COM). |
| 141 | Oil Pressure Sensor L | Engine oil pressure sender signal is shorted low. | Warning | Check sender/connectors/wires; check for shorts/open circuits at P7-13, 17, 21. |
| 1416 | Fail To Shutdown | Genset continues to run after receiving shutdown command (Battle Short feature enabled). | Warning | Check Battle Short feature setting. |
| 1417 | Powr Down Error | Controller cannot power down because of an unknown condition. | Warning | Indicates controller cannot power down because of unknown condition. Possible drain on battery. Contact an authorized service center for service. |
| 143 | Pre-Low Oil Pres | Engine oil pressure dropped to an unacceptable level. | Warning | Indicates engine oil pressure has dropped below the warning trip point. If generator is powering critical loads and cannot be shut down, wait until next shutdown period and then follow code 415 procedure. |
| 1433 | Emergency Stop | Local Emergency Stop. | Shutdown | Pull the button out; move switch to O; press Fault Acknowledge/Reset; select Manual or Auto. |
| 1434 | Remote E-Stop | Remote Emergency Stop. | Shutdown | See code 1433 to reset. |
| 1435 | Low Coolant Temp | Engine coolant heater is not operating or not circulating coolant (coolant <=70 F [21 C]). | Warning | Indicates engine coolant heater is not operating or is not circulating coolant. Check coolant heater power supply for blown fuse or disconnected cord; check for low coolant level and replenish; look for coolant leaks and repair. |
| 1438 | Fail To Crank | Engine failed to crank after the PCC received a start signal. | Shutdown | Test for B+ at the starter; check fuse F3 (2 Amps); check K4 start pilot relay and starter circuitry; refer to code 121. |
| 144 | Coolant Sensor High | Engine coolant temperature signal is shorted high. | Warning | Check sender/connectors/wires; check resistance between P7-30 (IH20) and P7-34 (IH20 COM). |
| 1442 | Weak Battery | During cranking battery voltage at or below weak battery trip point. | Warning | Recharge or replace battery; check electrolyte level and connections; check harness. |
| 1443 | Battery Failed | Dead battery - engine will not start. | Shutdown | See code 1438 instructions. |
| 1444 | KW Overload | Generator output power exceeded 105% of genset rating (3 sec at 110% of rated). | Warning | Check load and load lead connections; check CTs and CT connections. |
| 1445 | Short Circuit | Generator output current exceeded 175% of rated. | Shutdown | Check load and load lead connections (fault may not reset for several minutes). |
| 1446 | High AC Voltage | Phase voltage exceeded 130% of nominal, or 110% of nominal for 10 seconds. | Shutdown | Check fault simulation; clear fault and restart; refer to Generator/Base Board Isolation Procedure. |
| 1447 | Low AC Voltage | Phase voltage dropped below 85% of nominal for 10 seconds. | Shutdown | Check load; reconnect per reconnection diagram; check PMG/field wiring; check P8-21/P8-22 shunt connections. |
| 1448 | Under Frequency | Engine speed dropped below 90% of nominal for 10 seconds. | Shutdown | Check fuel supply, intake air supply and load; check P8 connections. |
| 1449 | Over Frequency | Frequency is 10% above base frequency for 20 seconds. | Warning | Check fuel or air delivery problem; repair P7/P8 connections. |
| 145 | Coolant Sensor Low | Engine coolant temperature signal is shorted low. | Warning | Check sender/connectors/wires; check for shorts at P7-30 and P7-34. |
| 1452 | Gen CB Not Close | Genset circuit breaker (S2) failed to close when PTC enabled. | Warning | Refer to Section 5. |
| 1453 | Gen CB Not Open | Genset circuit breaker (S2) failed to open when PTC enabled. | Warning | Refer to Section 5. |
| 1459 | Reverse Power | Improper CT phasing. | Shutdown | Check wiring to voltage sense circuit; refer to CT Installation in Section 6. |
| 146 | Pre-High Coolant Temp | Engine has begun to overheat (coolant temperature risen to an unacceptable level). | Warning | Reduce load; check air inlets/outlets and remove obstructions to airflow; if engine can be stopped follow code 151. |
| 1461 | Loss Of Field | Loss of field (electric) due to reverse kVAR. | Shutdown | Check field circuit. |
| 1466 | Modem Failure | Control cannot communicate with the modem. | Warning | Check for open, short circuit to ground, and loose connections to the modem. |
| 1468 | Network Error | Momentary loss of communication from the LonWorks Network. | Warning | Refer to the LonWorks Network publications. |
| 1469 | Speed/Hz Match | Measured speed and measured AC output frequency do not agree. | Shutdown | Check calibration file. |
| 1471 | Over Current | Generator output current exceeded 110% of rated for 60 seconds. | Warning | Check load and load lead connections. |
| 1472 | Over Current | Generator output current exceeded 110% of rated; time/current calculation initiated shutdown. | Shutdown | Check load and load lead connections (fault may not reset for several minutes). |
| 151 | High Coolant Temp | Engine has overheated (coolant temperature above the shutdown trip point). | Shutdown | Engine has overheated. Allow engine to cool completely, then: check coolant level and replenish and repair leaks; check for obstructions to cooling airflow; check fan belt and repair or tighten; check blower fan and circulation pumps on remote radiator installations; reset control and restart. |
| 197 | Low Coolant Level | Engine coolant level has fallen below the warning trip point. | Warning | Indicates engine coolant level has fallen below warning trip point. If generator is powering critical loads and cannot be shut down, wait until next shutdown period, then follow code 235 procedure. If engine can be stopped, follow code 235 procedure. |
| 200 | LOW OIL PRESSURE | Indicates engine oil pressure has dropped to an unacceptable level. | Warning | If powering critical loads, wait until next shutdown period and follow 201-SHUTDOWN procedure; check oil pressure via menu prior to clearing fault. |
| 201 | LOW OIL PRESSURE | Indicates engine oil pressure has dropped below the shutdown trip point. | Shutdown | Check oil level, lines and filters; replenish if low; reset control and restart. Oil pressure limits in Table 4-3. |
| 204 | OIL PRESS SENDER | The control has sensed that the engine oil pressure sender is out of its working range. | Warning | Check that the engine oil pressure sender is properly connected. |
| 210 | LOW COOLANT TEMP | Warning occurs when engine coolant temperature is 70°F (21°C) or lower, indicating the engine coolant heater is not operating or is not circulating coolant. | Warning | Indicates engine coolant heater is not operating or is not circulating coolant; check coolant heater power supply/fuse, low coolant level, and open heater element. |
| 211 | HIGH COOLANT TEMP | Indicates the engine coolant temperature is getting close to the recommended maximum temperature limit: 215°F (102°C) standby or 207°F (97°C) prime. | Warning | Reduce load if possible; check air inlets/outlets; follow 212-SHUTDOWN procedure if engine can be stopped. |
| 212 | Oil Temp Sensor H | Indicates engine has overheated (coolant temperature above the shutdown trip point: 223°F (106°C) standby or 215°F (102°C) prime). | Warning | Check sender/connectors/wires; check resistance between P7-22 (OIL TEMP) and P7-26 (OIL TEMP COM). |
| 213 | Oil Temp Sensor L | Resistance of the coolant temperature sender is out of range. | Warning | Check the resistance of the sender; should be 500 to 2k ohms. |
| 214 | LOW COOLANT LVL | Indicates engine coolant level has fallen below the trip point. | Warning | Check coolant level in radiator and coolant recovery bottle; look for leakage; reset control and restart. |
| 215 | LOW COOLANT LVL | Indicates engine coolant level has fallen below the trip point. LOW COOLANT LVL Shutdown will not occur if genset is in Idle mode (low coolant warning only). | Shutdown | Check coolant level in radiator and recovery bottle and replenish if low; check defective coolant bottle hose or radiator cap; reset control and restart after correcting problem. Will not occur in Idle mode. |
| 220 | MAG PICKUP | Mag pickup speed indication is not being sensed or does not match generator set output frequency. | Shutdown | Restart and check RPM on the digital display; isolate per troubleshooting table 4-18. |
| 221 | FAIL TO CRANK | Possible fault with control or starting system; engine will not crank. | Shutdown | Check fuse F3 on the Engine Interface board; clean battery cable connections; recharge or replace battery. |
| 222 | OVERCRANK | Possible fuel system problem; engine stops cranking. | Shutdown | Check for empty fuel tank, fuel leaks, or plugged fuel lines; check/replace dirty fuel filter and air filter; reset and restart. |
| 223 | OVERSPEED | Indicates engine has exceeded normal operating speed (115% ±1% of nominal). | Shutdown | Inspect the mechanical fuel linkage and repair or replace; check the EFC for binding or damage; monitor the PCC duty cycle display and replace A32 or A38 as indicated. |
| 224 | FAIL TO SYNCHRONIZE | The generator set has not synchronized to the system bus within the allowable time frame. | | Check governor system stability and adjust governing/synchronizer parameters; check for fuel system problems causing engine instability; widen synchronizing window and reduce acceptance time delay. |
| 226 | FAIL TO CLOSE | Indicates that the paralleling breaker has been given a signal to close, but has not closed properly. | | Verify charging mechanism of paralleling breaker; check the close signal to the breaker; verify auxiliary contact signals from the breaker to the control are operational. |
| 230 | LOW DC VOLTAGE | Indicates battery voltage is below 10 VDC. | Warning | Recharge or replace battery; clean/tighten connections; check engine DC alternator; check battery charger float level. |
| 231 | HIGH DC VOLTAGE | Indicates battery voltage exceeds 32 VDC. | Warning | Check voltage float level on battery charger if applicable (lower float level); check engine DC alternator and replace if normal battery charging voltage is not obtained. |
| 232 | WEAK BATTERY | Indicates battery voltage drops below 60% of nominal for two seconds, during starting. | Warning | Recharge or replace the battery; see 230 LOW DC VOLTAGE. |
| 2327 | PTC Fault | PTC module or communication link not working properly when PTC enabled. | Warning | Check blinking light on PTC module; check B+ TB3-3 to TB3-4; check PTC status voltage TB3-5 to TB3-6 (~0.2 VDC); repower control. |
| 2329 | Low S1 Frequency | Low utility (S1) frequency. | Warning | Check S1 AC inputs and wiring to PTC at TB5; check sensor set points. |
| 2331 | Low S1 Voltage | Low utility (S1) voltage. | Warning | Repower PCC 2100 control to clear; check S1 AC inputs at TB5; check S1 pickup/dropout set points. |
| 2335 | Excitation Fault | Loss of all three voltage sense leads or failure in excitation circuit. | Shutdown | Check field wiring (X1 and X2) for shorts or opens. |
| 2336 | Memory Error | Control memory error; data corruption of critical operating parameters. | Shutdown | Try reloading calibration file. |
| 2337 | Pwr Tran Disabled | PTC module available but PTC feature not enabled. | Warning | Use InPower to enable PTC feature; cycle power off for 5 seconds then repower. |
| 2338 | Pwr Tran Failure | PTC module trim enabled but control could not communicate with PTC module. | Warning | Check blinking light and B+ TB3-3 to TB3-4; check connections between TB2 and TB3; cycle power. |
| 2339 | Pwr Down Enabled | Power Down (sleep) function enabled but PTC module or network board is active. | Warning | None required. |
| 234 | Overspeed | Engine has exceeded normal operating speed. | Shutdown | Clear fault and restart genset; check fault threshold; monitor RPM; check electronic governor actuator. |
| 2341 | High Control Temp | Control temperature above normal (158 F [70 C]) for time greater than set time. | Warning | Check genset room air flow. |
| 2342 | Too Long In Idle (10 min.) | Genset has been in Idle mode too long. | Warning | Indicates genset has been in Idle mode too long (10 minutes maximum). |
| 235 | Low Coolant Level | Engine coolant level has fallen below the shutdown trip point. | Shutdown | Coolant level has fallen below the shutdown trip point. Allow engine to cool completely, then check coolant level and replenish, look for possible coolant leakage points and repair; reset control and restart. |
| 2358 | High S1 Voltage | Utility (S1) voltage increased above over voltage threshold. | Warning | Measure S1 AC inputs at PTC module; check utility nominal voltage; check sensor set points. |
| 2396 | S1 CB Not Close | Utility contact (S1) failed to close with PTC enabled. | Warning | Refer to Section 5. |
| 2397 | S1 CB Not Open | Utility contact (S1) failed to open with PTC enabled. | Warning | Refer to Section 5. |
| 240 | LOW FUEL-DAY | Indicates day tank fuel supply is running low. | Warning | Check fuel supply and replenish as required. |