Cummins/Onan DGCA Generator Set

The Cummins/Onan DGCA is a 40 kW (50 kVA) Diesel standby generator set powered by a Cummins/Onan 4BT3.9Gl engine. It is available at 24 V, 3-phase and 50 Hz. It holds about 16 L (4.2 gal) of oil and 21 L (5.5 gal) of coolant, with a maximum ambient rating of 40 °C. Starting uses 2 group-2 batteries rated 1080 CCA at 12 V. The set measures 2104×1016×1207 mm (82.8×40.0×47.5 in) and weighs about 780 kg (1720 lb). An integrated tank holds 25 L (6.6 gal).

40 kW
Standby
16.0 L
Oil capacity
4
Document types

How to read your Cummins/Onan serial & model number →

Typical fuel consumption for 40–45 kW Diesel generators →

Compare with other 40–45 kW Diesel generators →

Service parts for the DGCA

Grouped by system, with how many of each the parts manual calls for.

Belts

1 required

Prices captured from merchant listings; some links are affiliate links. Confirm against your serial number before ordering.

Specifications

FuelDiesel
Frequency50.0 Hz
Standby power40 kW
Standby kVA50
Prime power32 kW
EmissionsTier 1
ControllerPCC, PCC2100, PowerCommand 2100, PowerCommand PCC 3100, PowerCommand PCC2100
Oil capacity16.0 L
AlternatorUR (4-pole)
Voltage options24 V
Phasethree-phase
Power factor0.8
Battery group2
Battery cranking1080 CCA
Battery voltage12 V
Battery quantity2
Coolant capacity21 L
Max ambient40 °C
Dimensions (L×W×H)2104×1016×1207 mm
Dry weight780 kg
Fuel tank25.0 L

Engine

Cummins/Onan 4BT3.9Gl
Rated speed1800 rpm

Maintenance & consumables

for the Cummins/Onan 4BT3.9Gl
ItemSpecCapacityPart #Interval
Air filterReplace yearly or when service indicator pops up—8760 hr
Fuel filterChange per maintenance schedule—500 hr
Oil filterChange per maintenance schedule—500 hr
Battery1.225—
BeltBelt, V-Grooved328876800 eBay
CoolantRefer to Cummins engine Operation and Maintenance Manual for coolant recommendations/specifications29.5 L—500 hr
Coolant filterChange per maintenance schedule—500 hr
OilRefer to Cummins engine Operation and Maintenance Manual for lubricating oil classification and viscosity25.2 L—500 hr
Spark plug—

Service intervals

37
ItemActionHoursMonthsNotes
Charge air pipingCheck50 hrDaily or after 8 hours
Coolant levelCheck8 hrDaily or after 8 hours
Engine oil levelCheck8 hrDaily or after 8 hours
Fuel Filter(s)Drain8 hrDrain 1 cup or more of fuel to remove water and sediment. Refer to engine operation and maintenance manual for procedure.
Fuel Tanks (water and sediment)Drain8 hrDrain 1 cup or more of fuel to remove water and sediment.
Fuel levelCheck8 hrDaily or after 8 hours
General genset inspectionInspect8 hrDaily or after 8 hours. Check for oil, fuel, cooling and exhaust system leaks; check exhaust audibly and visually with set running.
Inspect GensetCheck8 hrCheck for oil, fuel, cooling and exhaust system leaks. Check exhaust system audibly and visually with set running and repair any leaks immediately.
Oil LevelCheck8 hrKeep oil level near the dipstick high mark without overfilling.
Air CleanerClean50 hrClean if required. Perform more often in dusty conditions.
Air cleaner (clean if required)Clean50 hrWeekly or after 50 hours; perform more often in dusty conditions
Battery charging systemCheck50 hrWeekly or after 50 hours
Coolant heaterCheck50 hrWeekly or after 50 hours
Crankcase OilDrain50 hrFirst service — Break-in: drain and replace the crankcase oil after the first 50 hours of operation on new generator sets.
Engine oil and filterChange50 hrFirst service — Drain and replace crankcase oil after first 50 hours on new generator sets
Exhaust condensate trapDrain50 hrWeekly or after 50 hours
Water and sediment from fuel tankDrain50 hrWeekly or after 50 hours; drain 1 cup or more of fuel to remove water and sediment
Radiator hoses for wear and cracksInspect100 hrMonthly or after 100 hours
Starting batteriesCheck100 hrMonthly or after 100 hours
Battery electrolyte levelCheck200 hrCheck at least every 200 hours of operation
Anti-freeze and DCA ConcentrationCheck250 hr3 moRefer to engine operation and maintenance manual.
Crankcase oil and filterChange250 hr12 moRefer to Cummins Engine Operation and Maintenance Manual. Standby applications: change every 12 months or 250 hours, whichever comes first.
Drive Belt TensionCheck250 hr3 moVisually check belt for evidence of wear or slippage. Replace if hard or brittle. Refer to engine operation and maintenance manual.
Fuel FiltersChange250 hr3 moRefer to engine operation and maintenance manual.
Governor AdjustmentCheck250 hr3 mo
Radiator Hoses for Wear & CracksCheck250 hr3 mo
Coolant FilterChange500 hr6 moRefer to engine operation and maintenance manual.
Cooling SystemClean500 hr6 moRefer to engine operation and maintenance manual.
Crankcase BreatherClean500 hr6 moRefer to engine operation and maintenance manual.
Generator bearingInspect1000 hrInspect for wear every 1000 hours by an Onan Distributor
Valve LashAdjust1000 hrAfter 1000 hours; contact an authorized service center for service
Alternator BearingsInspect4000 hr24 moInspect all sealed bearings every 4000 to 4500 hours (10000 hr/2 years)
Generator bearingReplace10000 hr24 moPrime power: every 10,000 hours or after two years; standby power: every five years
Alternator BearingsReplace30000 hr60 moReplace all sealed bearings every 30000 hr/5 years (or if necessary after 10000 hr/2 years)
Air cleaner elementChange500 hr12 moYearly or sooner if service indicator pops up
Air cleaner elementReplace12 moReplace yearly or sooner if service indicator pops up; more often in dusty conditions
Generator set exerciseTest1 moExercise at least once a month for a minimum of 30 minutes at not less than 30 percent of nameplate rating

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Service specifications

60
TypeItemValueUnitCondition
ClearanceFloat switch lift below C-clip stop1/8inch (3 mm)
ClearanceOverspeed switch magnet-to-fly arm air gap (minimum)0.005inches (0.13 mm)
GapMechanical overspeed switch air gap between magnet and fly arm (replace switch if less)0.005inches (0.13 mm)
OtherAVR DROOP preset at factoryfive percent droop at full load and zero power factor
OtherBattery electrolyte corrected specific gravity (fully charged)1.260electrolyte temperature corrected
OtherBattery electrolyte specific gravity, fully charged (corrected)1.260corrected to 80 °F (27 °C)
OtherBattery recharge threshold specific gravity1.215
OtherBattery specific gravity recharge threshold1.260specific gravityrecharge if below
OtherBattery specific gravity temperature correctionfour gravity points (0.004) for every ten degrees above 80 F (27 C)
OtherBattery specific gravity, fully chargedapproximately 1.260at 80°F (27°C)
OtherCoolant level below radiator cap opening2inches
OtherCycle crank crank and rest time7 to 20seconds
OtherCycle crank number of cycles3, 4, or 5
OtherCycle cranking option15seconds15 s crank, 15 s rest, 3 cycles
OtherECM fuse F1 (starter solenoid circuit)20amps
OtherECM fuse F2 (fuel solenoid circuit)20amps
OtherECM fuse F3 (continuous B+ to remote circuits)15amps
OtherECM fuse F4 (ECM circuits)5amps
OtherECM fuse F5 (engine gauge circuits)5amps
OtherFrequency adjustment range±5%%genset running
OtherFuse A31-F1 (control B+)5AmpEngine Interface board
OtherFuse A31-F3 (auxiliary B+)5AmpEngine Interface board; panel lights, run and start relays
OtherFuse A38-F1 (Network B+)10AmpGovernor Output Module
OtherFuse A38-F2 (Switched B+)10AmpGovernor Output Module
OtherFuse A38-F3 (Governor B+)10AmpGovernor Output Module
OtherFuse TB-Bat F1 (Customer B+)20AmpEngine Harness Assembly
OtherGOV RAMP adjustment range0 through 10seconds
OtherGovernor droop adjustment rangewithin 5percent of nominal frequency (3 Hz for 60Hz sets, 2.5 Hz for 50Hz sets)
OtherLow oil pressure / high engine temperature fault time delayabout 10secondsfollowing starter disconnect and inhibited during cranking
OtherOvercrank cranking limit75secondsstandard overcrank control
OtherOvercrank limit (Sentinel)60seconds
OtherOvercrank option limit (Detector)75seconds
OtherOverspeed warning range 60 Hz sets2000 to 2200RPM
OtherREG VHZ adjustment range1 through 50 (normal range 7 through 21)
OtherResponse jumper setting - 90 to 550 kWB to C
OtherResponse jumper setting - over 550 kWA to B
OtherResponse jumper setting - under 90 kWA to C
OtherSetup/calibration menu access code574
OtherStandard cycle cranking (Detector)three 15-second cranking cycles with two 15-second rest periods
OtherStart delay adjustment range0 to 300secondsremote starting in Auto mode
OtherStop delay adjustment range0 to 600secondsremote stopping in Auto mode
OtherTrailer brake shoe adjustment back-off10clicks
OtherTrailer surge brake actuator stroke length (service brakes if exceeds)1inch (25 mm)
OtherUnder-frequency roll-off (UFRO) threshold, 50 Hz applications49Hz
OtherUnder-frequency roll-off (UFRO) threshold, 60 Hz applications59Hz
OtherVoltage adjustment range±5%%genset running
PressureEngine oil pressure (normal)30 to 65psi (207 to 449 kPa)at normal operating temperature
PressureEngine oil pressure range (low oil pressure troubleshooting)25 to 65psi (172 to 449 kPa)
PressureFuel shutoff valve rating (TB1-8 and TB1-5)not more than 0.5amps120 or 240 VAC
PressureIdle oil pressure10 - 30psi (69 - 207 kPa)idle
PressureIdle oil pressure10-30psi (69-207 kPa)idle
PressureIdle oil pressure69-207kPaidle
PressureIdle oil pressure (normal)10-30psi (69-207 kPa)Engine model 6C, idle
PressureIdle oil pressure shutdown limit55kPaidle
PressureIdle oil pressure shutdown limit8psi (55 kPa)idle
PressureIdle oil pressure warning limit12psi (83 kPa)idle
PressureIdle oil pressure warning limit83kPaidle
PressureLow Oil Pressure shutdown threshold14psi (97 kPa)
PressureLow Oil Pressure shutdown threshold (less than)14psi
PressureLow oil pressure cutout switch test threshold (service lubricating system if less)10psiwhile cranking

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Recommended fluids

FluidGradeStandardAmbientCapacityNotes
Coolantsoft water/E.G./DCA mixtureInstallation review checklist item: cooling system must be filled with soft water/E.G./DCA mixture.
Coolant50/50 mix of water and antifreezeBalanced coolant mixture of water, antifreeze and coolant additivesDrain and replace the mixture every 6 months or after 500 hours of operation. Do not add cold coolant to a hot engine; allow engine to cool below 120 F (50 C) before adding coolant.
CoolantWater/antifreeze mixturePermanent type antifreeze mixed per supplier for lowest expected ambient; do not use anti-leak additives
Engine oilRefer to Cummins engine Operation and Maintenance Manual for lubricating oil classificationGensets are shipped with oil added.
Engine oil5W (Synthetic Oil)API CC/CD, sulphated ash max 1.85%below -23°CBelow -10 F (-23 C) and below; pour point 9 F (5 C) below lowest expected temperature
Engine oil10W-30API CC/CD-23°C to -10°C-10 F (-23 C) to 14 F (-10 C)
Engine oil15W-40API CC/CDabove -10°C14 F (-10 C) and above
Engine oil20W-40API CC/CDabove 0°C32 F (0 C) and above
FuelDieselDo not use zinc coated or copper fuel lines with diesel fuel.
FuelNo. 2 dieselNo. 1 fuel or similar acceptable; consult engine manufacturer for non-standard fuel
FueldieselDo not use zinc coated or copper fuel lines with diesel fuel.
Hydraulic oilDOT-3Trailer master cylinder reservoir - keep at least half full

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Fault codes

80
CodeNameMeaningSeverityAction
101IDLE MODEIndicates that the engine is operating in idle mode; generator build-up is inhibited and engine governed at 800 RPM.WarningRemove ground from the engine idle input to return to normal speed and voltage.
102EMERGENCY STOPIndicates local or remote Emergency Stop.ShutdownPull the button out; move the Run/Off/Auto switch to Off; press the Reset switch; select Run or Auto as required. Can only be reset at the PCC front panel.
1122Rated/Idle TransInfo
1123Shutdown After Battle ShortA shutdown fault occurred while Battle Short was enabled and transitioned from enabled to disabled.ShutdownReview Fault History and perform corrective action.
1124Delayed ShutdownA shutdown fault became active while the Delayed Shutdown feature was enabled.WarningReview Fault History and perform corrective action.
1131Battle Sh ActiveControl is in Battle Short mode (bypasses several critical fault shutdowns).WarningNone; used for genset operation during emergencies.
121Speed Signal LostMag pickup speed indication is not being sensed.ShutdownRestart and check RPM on digital display; inspect MPU wires/connector pins; check for 3.5 to 15 VAC at MPU while cranking.
1311Customer Input #1WarningOptional customer selection (e.g., Low Fuel Day Tank, Water In Fuel, Ground Fault, Low Starting Hydraulic Pressure, Low Starting Air Pressure). Programmable: enable/disable, status/warning/shutdown, active closed or open, and display name.
1311, 1312, 1317, 1318CUSTOMER INPUT #1 - #4Optional customer-selected fault input is active.Disconnect signal lead from TB1 and reset the control; check external wiring/active input selection.
1312Customer Input #2WarningOptional customer selection; programmable (enable/disable, status/warning/shutdown, active open/closed, display name). Default #2 thru #4 - Warning.
1317Customer Input #3WarningOptional customer selection; programmable (default #3 - Low Fuel).
1318Customer Input #4WarningOptional customer selection; programmable (default #4 - Rupture Basin Fault).
1334Crit Scaler Out Of RangeIncorrect feature or calibration was entered into control.ShutdownReload correct feature/calibration file.
1335Noncrit Scaler Out Of RangeIncorrect feature or calibration was entered into control.WarningReload correct feature/calibration file.
1337No MessageInfo
135Oil Pressure Sensor HEngine oil pressure sender signal is shorted high.WarningCheck sender/connectors/wires; verify fault simulation not enabled; check 0.5 to 4.5 VDC at P7-13 (OP OUT) and P7-17 (OP COM).
141Oil Pressure Sensor LEngine oil pressure sender signal is shorted low.WarningCheck sender/connectors/wires; check for shorts/open circuits at P7-13, 17, 21.
1416Fail To ShutdownGenset continues to run after receiving shutdown command (Battle Short feature enabled).WarningCheck Battle Short feature setting.
1417Powr Down ErrorController cannot power down because of an unknown condition.WarningIndicates controller cannot power down because of unknown condition. Possible drain on battery. Contact an authorized service center for service.
143Pre-Low Oil PresEngine oil pressure dropped to an unacceptable level.WarningIndicates engine oil pressure has dropped below the warning trip point. If generator is powering critical loads and cannot be shut down, wait until next shutdown period and then follow code 415 procedure.
1433Emergency StopLocal Emergency Stop.ShutdownPull the button out; move switch to O; press Fault Acknowledge/Reset; select Manual or Auto.
1434Remote E-StopRemote Emergency Stop.ShutdownSee code 1433 to reset.
1435Low Coolant TempEngine coolant heater is not operating or not circulating coolant (coolant <=70 F [21 C]).WarningIndicates engine coolant heater is not operating or is not circulating coolant. Check coolant heater power supply for blown fuse or disconnected cord; check for low coolant level and replenish; look for coolant leaks and repair.
1438Fail To CrankEngine failed to crank after the PCC received a start signal.ShutdownTest for B+ at the starter; check fuse F3 (2 Amps); check K4 start pilot relay and starter circuitry; refer to code 121.
144Coolant Sensor HighEngine coolant temperature signal is shorted high.WarningCheck sender/connectors/wires; check resistance between P7-30 (IH20) and P7-34 (IH20 COM).
1442Weak BatteryDuring cranking battery voltage at or below weak battery trip point.WarningRecharge or replace battery; check electrolyte level and connections; check harness.
1443Battery FailedDead battery - engine will not start.ShutdownSee code 1438 instructions.
1444KW OverloadGenerator output power exceeded 105% of genset rating (3 sec at 110% of rated).WarningCheck load and load lead connections; check CTs and CT connections.
1445Short CircuitGenerator output current exceeded 175% of rated.ShutdownCheck load and load lead connections (fault may not reset for several minutes).
1446High AC VoltagePhase voltage exceeded 130% of nominal, or 110% of nominal for 10 seconds.ShutdownCheck fault simulation; clear fault and restart; refer to Generator/Base Board Isolation Procedure.
1447Low AC VoltagePhase voltage dropped below 85% of nominal for 10 seconds.ShutdownCheck load; reconnect per reconnection diagram; check PMG/field wiring; check P8-21/P8-22 shunt connections.
1448Under FrequencyEngine speed dropped below 90% of nominal for 10 seconds.ShutdownCheck fuel supply, intake air supply and load; check P8 connections.
1449Over FrequencyFrequency is 10% above base frequency for 20 seconds.WarningCheck fuel or air delivery problem; repair P7/P8 connections.
145Coolant Sensor LowEngine coolant temperature signal is shorted low.WarningCheck sender/connectors/wires; check for shorts at P7-30 and P7-34.
1452Gen CB Not CloseGenset circuit breaker (S2) failed to close when PTC enabled.WarningRefer to Section 5.
1453Gen CB Not OpenGenset circuit breaker (S2) failed to open when PTC enabled.WarningRefer to Section 5.
1459Reverse PowerImproper CT phasing.ShutdownCheck wiring to voltage sense circuit; refer to CT Installation in Section 6.
146Pre-High Coolant TempEngine has begun to overheat (coolant temperature risen to an unacceptable level).WarningReduce load; check air inlets/outlets and remove obstructions to airflow; if engine can be stopped follow code 151.
1461Loss Of FieldLoss of field (electric) due to reverse kVAR.ShutdownCheck field circuit.
1466Modem FailureControl cannot communicate with the modem.WarningCheck for open, short circuit to ground, and loose connections to the modem.
1468Network ErrorMomentary loss of communication from the LonWorks Network.WarningRefer to the LonWorks Network publications.
1469Speed/Hz MatchMeasured speed and measured AC output frequency do not agree.ShutdownCheck calibration file.
1471Over CurrentGenerator output current exceeded 110% of rated for 60 seconds.WarningCheck load and load lead connections.
1472Over CurrentGenerator output current exceeded 110% of rated; time/current calculation initiated shutdown.ShutdownCheck load and load lead connections (fault may not reset for several minutes).
151High Coolant TempEngine has overheated (coolant temperature above the shutdown trip point).ShutdownEngine has overheated. Allow engine to cool completely, then: check coolant level and replenish and repair leaks; check for obstructions to cooling airflow; check fan belt and repair or tighten; check blower fan and circulation pumps on remote radiator installations; reset control and restart.
197Low Coolant LevelEngine coolant level has fallen below the warning trip point.WarningIndicates engine coolant level has fallen below warning trip point. If generator is powering critical loads and cannot be shut down, wait until next shutdown period, then follow code 235 procedure. If engine can be stopped, follow code 235 procedure.
200LOW OIL PRESSUREIndicates engine oil pressure has dropped to an unacceptable level.WarningIf powering critical loads, wait until next shutdown period and follow 201-SHUTDOWN procedure; check oil pressure via menu prior to clearing fault.
201LOW OIL PRESSUREIndicates engine oil pressure has dropped below the shutdown trip point.ShutdownCheck oil level, lines and filters; replenish if low; reset control and restart. Oil pressure limits in Table 4-3.
204OIL PRESS SENDERThe control has sensed that the engine oil pressure sender is out of its working range.WarningCheck that the engine oil pressure sender is properly connected.
210LOW COOLANT TEMPWarning occurs when engine coolant temperature is 70°F (21°C) or lower, indicating the engine coolant heater is not operating or is not circulating coolant.WarningIndicates engine coolant heater is not operating or is not circulating coolant; check coolant heater power supply/fuse, low coolant level, and open heater element.
211HIGH COOLANT TEMPIndicates the engine coolant temperature is getting close to the recommended maximum temperature limit: 215°F (102°C) standby or 207°F (97°C) prime.WarningReduce load if possible; check air inlets/outlets; follow 212-SHUTDOWN procedure if engine can be stopped.
212Oil Temp Sensor HIndicates engine has overheated (coolant temperature above the shutdown trip point: 223°F (106°C) standby or 215°F (102°C) prime).WarningCheck sender/connectors/wires; check resistance between P7-22 (OIL TEMP) and P7-26 (OIL TEMP COM).
213Oil Temp Sensor LResistance of the coolant temperature sender is out of range.WarningCheck the resistance of the sender; should be 500 to 2k ohms.
214LOW COOLANT LVLIndicates engine coolant level has fallen below the trip point.WarningCheck coolant level in radiator and coolant recovery bottle; look for leakage; reset control and restart.
215LOW COOLANT LVLIndicates engine coolant level has fallen below the trip point. LOW COOLANT LVL Shutdown will not occur if genset is in Idle mode (low coolant warning only).ShutdownCheck coolant level in radiator and recovery bottle and replenish if low; check defective coolant bottle hose or radiator cap; reset control and restart after correcting problem. Will not occur in Idle mode.
220MAG PICKUPMag pickup speed indication is not being sensed or does not match generator set output frequency.ShutdownRestart and check RPM on the digital display; isolate per troubleshooting table 4-18.
221FAIL TO CRANKPossible fault with control or starting system; engine will not crank.ShutdownCheck fuse F3 on the Engine Interface board; clean battery cable connections; recharge or replace battery.
222OVERCRANKPossible fuel system problem; engine stops cranking.ShutdownCheck for empty fuel tank, fuel leaks, or plugged fuel lines; check/replace dirty fuel filter and air filter; reset and restart.
223OVERSPEEDIndicates engine has exceeded normal operating speed (115% ±1% of nominal).ShutdownInspect the mechanical fuel linkage and repair or replace; check the EFC for binding or damage; monitor the PCC duty cycle display and replace A32 or A38 as indicated.
224FAIL TO SYNCHRONIZEThe generator set has not synchronized to the system bus within the allowable time frame.Check governor system stability and adjust governing/synchronizer parameters; check for fuel system problems causing engine instability; widen synchronizing window and reduce acceptance time delay.
226FAIL TO CLOSEIndicates that the paralleling breaker has been given a signal to close, but has not closed properly.Verify charging mechanism of paralleling breaker; check the close signal to the breaker; verify auxiliary contact signals from the breaker to the control are operational.
230LOW DC VOLTAGEIndicates battery voltage is below 10 VDC.WarningRecharge or replace battery; clean/tighten connections; check engine DC alternator; check battery charger float level.
231HIGH DC VOLTAGEIndicates battery voltage exceeds 32 VDC.WarningCheck voltage float level on battery charger if applicable (lower float level); check engine DC alternator and replace if normal battery charging voltage is not obtained.
232WEAK BATTERYIndicates battery voltage drops below 60% of nominal for two seconds, during starting.WarningRecharge or replace the battery; see 230 LOW DC VOLTAGE.
2327PTC FaultPTC module or communication link not working properly when PTC enabled.WarningCheck blinking light on PTC module; check B+ TB3-3 to TB3-4; check PTC status voltage TB3-5 to TB3-6 (~0.2 VDC); repower control.
2329Low S1 FrequencyLow utility (S1) frequency.WarningCheck S1 AC inputs and wiring to PTC at TB5; check sensor set points.
2331Low S1 VoltageLow utility (S1) voltage.WarningRepower PCC 2100 control to clear; check S1 AC inputs at TB5; check S1 pickup/dropout set points.
2335Excitation FaultLoss of all three voltage sense leads or failure in excitation circuit.ShutdownCheck field wiring (X1 and X2) for shorts or opens.
2336Memory ErrorControl memory error; data corruption of critical operating parameters.ShutdownTry reloading calibration file.
2337Pwr Tran DisabledPTC module available but PTC feature not enabled.WarningUse InPower to enable PTC feature; cycle power off for 5 seconds then repower.
2338Pwr Tran FailurePTC module trim enabled but control could not communicate with PTC module.WarningCheck blinking light and B+ TB3-3 to TB3-4; check connections between TB2 and TB3; cycle power.
2339Pwr Down EnabledPower Down (sleep) function enabled but PTC module or network board is active.WarningNone required.
234OverspeedEngine has exceeded normal operating speed.ShutdownClear fault and restart genset; check fault threshold; monitor RPM; check electronic governor actuator.
2341High Control TempControl temperature above normal (158 F [70 C]) for time greater than set time.WarningCheck genset room air flow.
2342Too Long In Idle (10 min.)Genset has been in Idle mode too long.WarningIndicates genset has been in Idle mode too long (10 minutes maximum).
235Low Coolant LevelEngine coolant level has fallen below the shutdown trip point.ShutdownCoolant level has fallen below the shutdown trip point. Allow engine to cool completely, then check coolant level and replenish, look for possible coolant leakage points and repair; reset control and restart.
2358High S1 VoltageUtility (S1) voltage increased above over voltage threshold.WarningMeasure S1 AC inputs at PTC module; check utility nominal voltage; check sensor set points.
2396S1 CB Not CloseUtility contact (S1) failed to close with PTC enabled.WarningRefer to Section 5.
2397S1 CB Not OpenUtility contact (S1) failed to open with PTC enabled.WarningRefer to Section 5.
240LOW FUEL-DAYIndicates day tank fuel supply is running low.WarningCheck fuel supply and replenish as required.

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Procedures

12
Adjusting Values/Parameters adjustment

⚠ If Home button or Previous Main Menu button is pressed before pressing save symbol, changes are not saved.

  1. Press button next to symbol in display until + and − symbols are displayed.
  2. Press button next to arrow symbols to move to numeric character to change.
  3. Press button next to + symbol to increase value or select parameter.
  4. Press button next to − symbol to decrease value or select parameter.
  5. After adjusting values/selecting parameters, press symbol to save changes.
Convert Day Tank Controller 240 VAC to 120 VAC adjustment
  1. Remove the two jumpers between terminals TB1-6 and TB1-7.
  2. Connect one jumper between TB1-5 and TB1-6 and the other between TB1-7 and TB1-8.
  3. Move selector switch S103 on the control PCB to the up position for 120V.
  4. If equipped with a transformer, remove jumpers between H2 and H3 and connect one between H1 and H3 and the other between H2 and H4.
Day Tank Controller Conversion 240 VAC to 120 VAC adjustment
  1. Remove the two jumpers between terminals TB1-6 and TB1-7 and connect one between TB1-5 and TB1-6 and the other between TB1-7 and TB1-8.
  2. Move selector switch S103 on the control PCB to the up position for 120V.
  3. On the control transformer, remove the two jumpers between terminals H2 and H3 and connect one between H1 and H3 and the other between H2 and H4.
Dip Adjustment adjustment
  1. Turn the DIP pot clockwise to increase the voltage vs frequency slope for frequencies below the UFRO threshold.
  2. Greater slope gives greater voltage roll off as frequency drops, easing large load pickup but increasing voltage dip.
  3. Turn the pot fully counterclockwise to make the slope the same above and below the threshold frequency.
Dwell Adjustment adjustment
  1. Turn the DWELL pot clockwise to increase dwell time (voltage recovery time when frequency dips below threshold).
  2. Turn the DWELL pot fully counterclockwise to eliminate dwell.
  3. With no dwell, voltage recovery follows engine speed recovery.
Electric Governor Controller Adjustments adjustment

⚠ If adjustment must be made while the unit is running, use extreme caution around hot manifolds and moving parts

Tools: Frequency meter

  1. Move RUN/STOP/REMOTE switch to RUN and operate set at no load.
  2. Confirm DROOP potentiometer adjust is set at zero position.
  3. Set speed by adjusting the SPEED potentiometer to 50 or 60 Hz.
  4. Adjust GAIN potentiometer clockwise until engine starts to hunt, then counterclockwise until speed is stable.
  5. Adjust the 'B' potentiometer the same as GAIN.
  6. Adjust the 'I' potentiometer to decrease overshoot above rated speed.
  7. Apply 1/4 load and adjust the GAIN potentiometer again.
  8. Apply full load to be certain the set will carry it; lengthen actuator linkage if it will not.
Fuel Pump Control: Convert 120 VAC to 240 VAC adjustment
  1. Remove jumpers between TB1-5/TB1-6 and TB1-7/TB1-8; connect two jumpers between TB1-6 and TB1-7.
  2. Move selector switch S103 on control PCB to down position for 240 VAC.
  3. If equipped with a transformer, remove jumpers between H1/H3 and H2/H4 and connect two jumpers between H2 and H3.
  4. Attach a tag to the control box indicating the supply voltage.
Fuel Pump Control: Convert 240 VAC to 120 VAC adjustment
  1. Remove jumpers between TB1-6/TB1-7; connect one jumper TB1-5 to TB1-6 and one TB1-7 to TB1-8.
  2. Move selector switch S103 on control PCB to up position for 120V.
  3. If equipped with a transformer, remove jumpers between H2/H3 and connect one between H1-H3 and one between H2-H4.
Governor Adjustments (Type A Electric Governor) adjustment
  1. Set selector switch S1 to OFF, S2 to appropriate model position.
  2. Set pots initially: Gain 20%, I 20%, D 30%, Droop 0%.
  3. Start set, adjust Speed pot for required frequency (60Hz=1800RPM or 50Hz=1500RPM) at operating temperature.
  4. Disconnect load, turn Gain pot to 100% or until unstable, then back off until stable.
  5. Adjust D and I pots similarly; readjust Speed if necessary.
  6. Push throttle to minimum speed, release and observe overshoot (2-5 Hz acceptable); adjust I pot to reduce overshoot or hunting.
Initial Start Setup adjustment

⚠ Selecting this menu resets all operating parameters to default values; perform only by technically qualified personnel.

  1. Press RESET, MENU and PHASE SELECT simultaneously to invoke the Initial Start Setup menu.
  2. Toggle the Standby/Prime option.
  3. Select the correct generator set model, frequency and kW rating.
  4. Select the correct nominal line-to-line output voltage.
  5. Select DELTA or WYE.
  6. Select SAVE to save changes; MAIN MENU is then displayed.
Mechanical Governor Adjustment adjustment

Tools: Accurate frequency meter

  1. Using an accurate frequency meter, measure frequency under full load.
  2. Turn the speed adjustment screw on the governor to adjust to nominal 50 or 60 Hz.
Operating PowerCommand in Droop Mode adjustment
  1. Set the no load speed and voltage at the desired level (bus must be de-energized or disconnect Bus PT module).
  2. Apply 100% load and adjust KW load sharing gain for desired full load frequency; adjust KVAR load sharing gain for desired full load voltage.
  3. Repeat the process for other generator sets in the system.
  4. Test the system with all available load and verify approximately equal load sharing at no load and maximum load.

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Voltage reconnection

VoltagePhaseConnectionLeadsNotes
AVR response jumperA to CFor generator output 90 kW or less (SX440 and MX321)
Auxiliary terminal board TB21K1, K2, P2, P3, P4, S2, S1, A2, A1A1 and A2 connect a VAR/power factor controller when paralleling with a utility; S1 and S2 connect a droop compensating CT when paralleling with a generator set or utility
CT1 - U load leads (A phase); CT2 - V load leads (B phase); CT3 - W load leads (C phase)6 lead gensets: generator output leads routed through CTs; 12 lead gensets: load wires routed through CTs12-lead sets have dual secondary CTs (3 pins); 6-lead sets have single secondary CTs (2 pins)
Day tank LO SHUTDOWN engine shutdown connectionTB1-14 to engine block ground; TB1-15 to TB2-16 on the ECM
Fault relay K8/K9 (Dry Contact Module)K8=Over Crank, Low Oil Pressure, High Engine Temperature, Low Coolant Level, Low Fuel Level; K9=Low Fuel Level, Rupture BasinContact ratings: 40A max carry/break N.O. 12V coil, 30A N.C. 12V coil, 20A N.O./10A N.C. 24V coil
MX321 PMG-excited jumper positions2-3, 4-5 and 6-7These jumpers must be in these positions
MX321 voltage regulator frequency jumper3-2 for 50 Hz; 3-1 for 60 Hz
SX440 voltage regulator frequency jumperC-50 for 50 Hz; C-60 for 60 Hz
TB3 (ECM alternative RUN/STOP/REMOTE connection)TB3-1=REMOTE, TB3-2=RUN, TB3-3=STOPProvides alternative direct connection to ECM for troubleshooting or customer connection
Voltage trimmer R21voltage regulator terminals 1 and 2There must be a jumper between terminals 1 and 2 when voltage trimmer R21 is not used
single phaseQSG-Series power distribution panel voltage selector switch S1 positionmain output terminalsRotary switch under lockable cover selects 120/240 VAC single phase
single phaseVoltage regulator terminal 6jumpered to terminal 8When the generator is connected for single-phase output, terminal 6 is not connected to the isolation transformer
three phaseQSG-Series power distribution panel voltage selector switch S1 positionmain output terminalsRotary switch selects 120/208 VAC three phase
110V - 120V L-NSingle phase, 2-wireJumper locations for single phase, 2-wirePTC Module AC wiring (0300-5382-01, -02)
120single phaseDay tank fuel pump control power reconnectionmove jumpers from TB1-6/TB1-7 to TB1-5/TB1-6 and TB1-7/TB1-8Move selector switch S103 on the control PCB to the up position for 120 V (factory set for 240 V, S103 down)
190, 200, 208, 220, 230, 240, 380, 416, 440, 460, 600 (L-L)3 (three phase)3 or 4 wiresVoltage Configuration submenu; default = 3Ph 208V 4W
190V - 240V L-LThree phaseJumper locations for three phase, 190V-240V L-LUse 0300-5382-01 for 190V-240V L-L, 50/60 Hz
200, 220, 230, 240 (L-L)1 (single phase)3 wiresVoltage Configuration submenu (Governor/Regulator Setup)
200V - 240V L-LSingle phase, 3-wireJumper locations for single phase, 3-wirePTC Module AC wiring
24Day tank fuel pump control logic power (two lead harness, no transformer)TB1-19 to positive (+) 24 V starter motor solenoid; TB-20 to negative (-)Provides 24 VDC for the control circuit
240single phaseDay tank fuel pump control default factory connectionjumpers between terminals TB1-6 and TB1-7Selector switch S103 on the control PCB in the down position for 240 V
380V - 600V L-LThree phaseJumper locations for three phase, 380V-600V L-LUse 0300-5382-02 for 380V-600V L-L, 50/60 Hz

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Common questions

What is the power rating of the Cummins/Onan DGCA?

The Cummins/Onan DGCA is rated 40 kW standby (50.0 kVA).

What engine does the Cummins/Onan DGCA use?

The Cummins/Onan DGCA is powered by the Cummins/Onan 4BT3.9Gl engine.

Is the Cummins/Onan DGCA diesel or gas?

The Cummins/Onan DGCA runs on Diesel.

What is the coolant capacity of the Cummins/Onan DGCA?

The Cummins/Onan DGCA cooling system holds 21 liters (5.5 US gallons) for the radiator system including the engine, per the manufacturer specification sheet.

How much oil does the Cummins/Onan DGCA take?

The Cummins/Onan DGCA has an engine oil capacity of 16 liters (16.9 US quarts), per the manufacturer specification sheet.

What is the prime power rating of the Cummins/Onan DGCA?

The Cummins/Onan DGCA is rated 32 kW prime (41 kVA), against 40 kW standby.

How much does the Cummins/Onan DGCA weigh?

The Cummins/Onan DGCA has a dry weight of 780 kg (1719 lb).

How big is the fuel tank on the Cummins/Onan DGCA?

The Cummins/Onan DGCA has a 25 liter (7 US gallon) fuel tank.

What voltages is the Cummins/Onan DGCA available in?

The Cummins/Onan DGCA is offered in 24 V, three-phase-phase.

How many cold cranking amps does the Cummins/Onan DGCA require?

The Cummins/Onan DGCA uses 2 batteryies, 12 V each, 1080 CCA, group 2, per the manufacturer specification sheet.

Which alternator is fitted to the Cummins/Onan DGCA?

The Cummins/Onan DGCA uses a UR alternator. It has 4 poles.

Troubleshooting

6

Symptoms & remedies

SymptomRemedy
Generator does not startCheck the fault codes and refer to the troubleshooting table for specific issues. Ensure that all connections are secure, and the control panel is powered on.
Generator produces low voltage outputRefer to the fault codes and troubleshooting table for possible causes such as a faulty alternator or incorrect settings. Check the generator's load and ensure it is within the rated capacity.
Generator produces high voltage outputRefer to the fault codes and troubleshooting table for possible causes such as a faulty alternator or incorrect settings. Check the generator's load and ensure it is within the rated capacity.
Generator produces inconsistent voltage outputRefer to the fault codes and troubleshooting table for possible causes such as a faulty alternator or incorrect settings. Check the generator's load and ensure it is within the rated capacity.
Generator produces inconsistent frequency outputRefer to the fault codes and troubleshooting table for possible causes such as a faulty alternator or incorrect settings. Check the generator's load and ensure it is within the rated capacity.
Generator produces noise during operationRefer to the fault codes and troubleshooting table for possible causes such as a faulty alternator or incorrect settings. Check the generator's load and ensure it is within the rated capacity.

Fault codes and symptom→remedy steps extracted from this model’s service/owner documentation; verify against the official manual before servicing. Full Cummins/Onan DGCA troubleshooting guide (96 entries) →

Parts

119
Part #DescriptionQtySystem
102-1147Gasket, Drain-Oil Pan1Gasket Amazon eBay
140-2159Clamp, Hose1Hose clamp Amazon eBay
140-2164Nut, Square (1/4-20)1Nut Amazon eBay KuduParts $10.00
150-2007Guard. Belt Screw. Cap - Hex Head (1/2-13 X 2-1/4“)1Belt Amazon eBay FridayParts $263.79 KuduParts $344.00
150-2201Sensor, Speed – Magnetic1Sensor Amazon eBay
187-0001Pump, Water1Pump Amazon eBay
187-0002Gasket Kit, End - Top1Gasket Amazon eBay
187-0008Belt, Drive4Belt Amazon eBay
187-0009Belt, Drive4Belt Amazon eBay
187-0011Filter, Fuel1Fuel filter Amazon
187-0013Pump, Transfer-FuelPump Amazon eBay $100.99
187-0018INJ. PUMPPump Amazon eBay
187-0020Thermostat1Thermostat Amazon eBay
193-0244Sender, Pressure - 0i11Sensor Amazon eBay
193-0353Sender, Temperature - Oil1Sensor Amazon eBay
193-0375# Sender, Water Temperature1Sensor Amazon eBay
234-0368Hose, Rubber1Hose Amazon eBay
300-3606Voltage Regulator Installation (PMG-Excited Generators), Rev. PAvr eBay
300-3607Voltage Regulator Installation (Self-Excited Generators), Rev. GAvr eBay
309-0269Sender, Temperature-Lo Engine1Sensor Amazon eBay $239.00
309-0272Regulator, Voltage - 24 VDC (Used on 35 A MP Alternator)1Alternator Amazon eBay
309-0561Alternator & Drive Components Group Pulley. Alternator - Multi Groove (Use with 35 A MP Alternator)1Alternator Amazon eBay
328876800Belt, V-Grooved1Belt eBay
353-0094-01Connector Housing and Contact Pins, 8 Pin (Less Pins)1Connector Amazon eBay
403-2575Screw, Cap - Hex Head (1/2 - 13 x l")1Screw Amazon eBay
405-3826-01Support, Engine - Screw, Cap - Hex Head (M12 x 1.75 x 65mm)1Support Amazon eBay
501-0441Line, Fuel - Flex (Fuel In)1Hose Amazon eBay
501-0502Line, Fuel-Flex (Fuel Out)1Hose Amazon eBay
503-0098Hose, Oil Drain - Bulk (Order By The Foot - 3 Feet Required)1Hose Amazon eBay
503-0183Clamp, Hose1Hose Amazon eBay
503-0197Clip, Hose1Hose Amazon eBay $7.99
503-0365Clamp, Hose1Hose Amazon eBay
503-0685Clamp, Hose1Hose Amazon eBay $15.00
503-0998Clamp, Hose2Hose clamp Amazon eBay
505-0059Sensor, Water Pressure1Sensor Amazon eBay
509-0125Key, Handle - Screw, Lock (3/8 - 16 x .75")1Seal Amazon eBay
625-2141Day Tank Pump Control Wiring, Rev. PPump eBay
750-1010Screw, Machine - Fillister Head (1/4-20 x 1")1Screw Amazon eBay
98-0961Decal, Level - Water2Decals Amazon eBay
M-1695Oil temperature senderSensor Amazon eBay
102-1237Adapter, Drain-Oil1Service part / kit Amazon eBay
151-0611Control, Governor1Service part / kit Amazon eBay FridayParts $249.00
155-2175Clamp, Muffler 4"1Service part / kit Amazon eBay
187-0007INJService part / kit Amazon eBay
187-0012Filter, Fuel1Service part / kit Amazon eBay $149.89 NAPA $17.15
187-0015Filter, Oil1Service part / kit Amazon eBay $39.95
205-0089Fan, Cooling-Generator1Service part / kit Amazon eBay
220-4289-31Main stator assembly (broad range generators)Service part / kit eBay
220-4289-32Main stator assembly (broad range generators)Service part / kit eBay
220-4289-33Main stator assembly (broad range generators)Service part / kit eBay
220-4289-34Main stator assembly (broad range generators)Service part / kit eBay
220-4289-35Main stator assembly (broad range generators)Service part / kit eBay
220-4298-31Main stator assemblyService part / kit eBay
220-4298-32Main stator assemblyService part / kit eBay
220-4298-33Main stator assemblyService part / kit eBay
220-4298-34Main stator assemblyService part / kit eBay
220-4298-35Main stator assemblyService part / kit eBay
220-4298-36Main stator assemblyService part / kit eBay
300-2810Board - Engine Monitor (All) (Includes Fuses)1Service part / kit Amazon eBay FridayParts $205.00
300-4111Auxiliary Relay Board (ARB), Rev. EService part / kit eBay
305-0823# Model MX3211Service part / kit Amazon eBay FridayParts $77.04
309-0553Switch, Temperature-Pre Water1Service part / kit Amazon eBay $127.46
309-0554SWITCH WATER1Service part / kit Amazon eBay $159.00
319-0969QS-Series Power Distribution Panel Wiring, Rev. GService part / kit eBay
323-1200# Socket, Contact (Used in J1, J2)1Service part / kit Amazon eBay
323-1304tiotming, Umector1Service part / kit Amazon eBay
323-1306Genset component (SJB series)1Service part / kit Amazon eBay
332-0051Clamp, Loop1Service part / kit Amazon eBay
332-0941*Tie, Cable2Service part / kit Amazon eBay
332-1279Terminal. Lug - Ring (3/86Service part / kit Amazon eBay
332-1445Tie, Cable 18 98-5219 1 Decal - Panel Front (Not I l l u s t r a t e d ) 19 98-5220 1 Decal3Service part / kit Amazon eBay
332-2739Bracket1Service part / kit Amazon eBay
332-2921Switch, Temperature - Washer, Lock (M8)1Service part / kit Amazon eBay
337-0090Strap, Electrical1Service part / kit Amazon eBay
357-0030# Rectifier, Silicon (CR2)1Service part / kit Amazon eBay
416-0446Cable, Battery - Jumper1Service part / kit Amazon eBay
504-0011Valve, Shutoff (1/2”)1Service part / kit Amazon eBay $59.95
505-0026Coupling, Pipe (1/8")2Service part / kit Amazon eBay
505-0050Elbow, Street (1/2' x 90 ° )1Service part / kit Amazon eBay
505-0098Band1Service part / kit Amazon eBay
505-0104Nipple, Pipe - Close1Service part / kit Amazon eBay
505-0185Nipple, Half (1/2' x 1.5' lg)1Service part / kit Amazon eBay
526-0008148-036’?1Service part / kit Amazon eBay
526-0018Gasket, Flange (1-3/4)1Service part / kit Amazon eBay
526-0115Washer (5/16 “)1Service part / kit Amazon eBay
526-0196Washer, Spacer - Shield JC)INT, BALL LINKAGE0Service part / kit Amazon eBay
526-0238Diode, Rectifier - Positive (CR1, CR2, CR3)1Service part / kit Amazon eBay
526-0327Control, GovernorService part / kit Amazon eBay
612-64877-Light DC Control Wiring Diagram, Sh 1 and 2 of 2, Rev. VService part / kit eBay
612-648812-Light DC Control Wiring Diagram, Sh 1 and 2 of 2, Rev. WService part / kit eBay
612-6489AC Control Wiring Diagram (Without Meters), Rev. S, modified 6/2001Service part / kit eBay
612-6490AC Control Wiring Diagram (With Meters), Rev. ZB, modified 1/2002Service part / kit Amazon eBay
625-2164Generator Reconnection Diagrams, Sh 1 and 2 of 2, Rev. KService part / kit eBay
625-2256QS-Series Generator Connections When The Voltage Selector Switch Is Provided, Rev. BService part / kit eBay
800-0012Screw, Cap - Hex Head (1/4-20 x 2-1/4”) Begin Spec C MANIFOLD KIT, INTAKE2Service part / kit Amazon eBay
800-0048Screw, Cap - Hex Head (3/8-16 x 3/4”)1Service part / kit Amazon eBay
800-2060Screw, Cap - Hex Head (M8x 1.25 x35)1Service part / kit Amazon eBay
800-2110Hood, Inlet - Air Molded1Service part / kit Amazon eBay
800-2112Screw. Cap - Hex Head (M12 x 30nin)2Service part / kit Amazon eBay
812-0075Screw-RHM(8-32xl/4)5Service part / kit Amazon eBay
813-0103Screw, Machine - Round Head (#10-32 x 3/4º)2Service part / kit Amazon eBay $19.00
815-0172Cover, Adapter Outlet1Service part / kit Amazon eBay
821-0018Screw, Self-locking - Hex Washer Head ( 1'4.20 x 5 8')1Service part / kit Amazon eBay
850-0025Screw, Machine - Round Head (#8-32 x 3/8" )2Service part / kit Amazon eBay
850-0030Washer, Lock - Spring (#10)1Service part / kit Amazon eBay
850-0050Washer, Lock - Spring (3/8”)2Service part / kit Amazon eBay
850-2006Washer, Lock - Spring (M6)1Service part / kit Amazon eBay
850-2008Washer, Lock (M8)1Service part / kit Amazon eBay
850-2012Washer, Lock - Spring (M12)3Service part / kit Amazon eBay
856-0013Washer, Lock - W/EIT (1/2)1Service part / kit Amazon eBay
860-2007Circuit Breaker Used With Westinghouse Circuit Breaker1Service part / kit Amazon eBay
862-00044 ttNut, Hex - Set Mounting - Key 2 HARDWARE SET, SET MOUNTING1Service part / kit Amazon eBay $5.99
863-0002Cleaner, Air (Includes Element)2Service part / kit Amazon eBay
870-0053Nut, Hex (s10-32)1Service part / kit Amazon eBay
870-0131Nut. Hex - with ET (#10-32)1Service part / kit Amazon eBay
870-0212Nut, Locking (1/4-20)2Service part / kit Amazon eBay
871-0010Nut, Hex - Srass (#10-32) Washer, Lock - EIT (#10) Washer, Lock - IT (#10)8Service part / kit Amazon eBay
871-0028NUT1Service part / kit Amazon eBay
960-0136Battery, 24V, 55Ah, AGM8Service part / kit Amazon eBay

Service, wear & replacement parts referenced for this model and its engine — confirm the exact part for your serial number. See the full parts catalog to search and cross-reference.

Fuel consumption

RatingLoadL/hgal/h
Standby100%11.02.9

Available documents

Spec sheet — 4BT3.9 (Cummins/Onan)Operator's manual — 960-0107 Cummins DGBB DGCB DGDB DGFA Operator's Manual (7-2009) (Cummins/Onan)Operator's manual — 960-0136 Onan DGCA DGCB DGDA DGDB Operator's Manual (8-1987) (Onan)Operator's manual — 960-0615C Cummins DGBB DGC DGFA Series Operator's Manual (10-2003) (Cummins/Onan)Operator's manual — Cummins-DGBB-DGBC-DGCA-DGCB-DGCG-DGFA-DGFB-DGFC-DGFS-operator-manual (Cummins/Onan)Parts manual — 0932-0112 Onan Post-Sale Literature Index (07-1998) (Cummins/Onan)Parts manual — 0960-0210 I8 201512 (Cummins/Onan)Parts manual — 0960-0242 I1 198805 (Cummins/Onan)Parts manual — 960-0231 Onan DGB DGC Parts Manual (6-1993) (Cummins/Onan)Parts manual — 960-0242 Onan DGCA DGCB Parts Manual (5-1988) (Cummins/Onan)Service manual — 900-0524B Onan DGxx Power Command Control 3100 Series Paralleling Gensets Operation & Service manual (01-2002) (Cummins/Onan)Service manual — 960-0505 Onan DGxx QSxx Detector Controls Generator Set Service Manual (04-2001) (Cummins/Onan)Service manual — 960-0510B Onan DGBB thru DGFC Series Service Manual (10-1998) (Cummins/Onan)Service manual — 960-0511B Cummins DGBB DGC DGD DGF Series Service Manual (10-2001) (Cummins/Onan)Service manual — 960-0518D Cummins DGBB DGC DGDA DGFB Series Service Manual (2-2004) (Cummins/Onan)Service manual — 960-0618D Cummins DGBB DGCA DGEA DGFA Series Installation Manual (10-2001) (Cummins/Onan)Service manual — 960-0628D Cummins DGB DGC DGF Series Installation Manual (2-2004) (Cummins/Onan)Service manual — DG Generator Set Service Manual PCC 3100 (Cummins/Onan)

This page was generated from the 18 manufacturer documents above by automated extraction; every figure shown is copied from one of them. How the data is compiled.