PCC2100 Controller

The PCC2100 is a generator-set controller. It is used on generator sets from Cummins/Onan, including the 350DFEG, 352DFEH, DFGB and DFGE.

35
Generator sets
Cummins/Onan
Brand
35–352 kW
Power range
2
Fuel types

Troubleshooting

60

Fault codes

CodeMeaningCauseRemedy
10Incorrect main fuel valve adjustment.Refer to Gaseous Fuel Adjustment (Type A or B) in Section 6.
11Incorrect secondary regulator adjustment.Refer to Initial Secondary Regulator Adjustment in Section 6.
1123Shutdown After Battle Short
1123Shutdown After Battle Short will be displayed for this type of shutdown.Battle Short is suspended and a shutdown occurs immediately if any of the following critical shutdown faults occur: Overspeed − Fault code 234, Emergency Stop − Fault code 1433, Remote Emergency Stop − Fault code 1434, Speed Signal Lost − Fault code 121, Excitation Fault − Fault code 2335. Moving the customer installed Battle Short switch to OFF with an active but overridden shutdown fault or a shutdown fault that was overridden at any time.
1124Delayed Shutdown
1131Battle Short Active
1131Battle Short Active.This feature must only be used during supervised, temporary operation of the genset. The faults that are overridden during Battle Short mode consist of faults that can affect genset performance or cause permanent engine, alternator, or connected equipment damage.
121Speed Signal Lost
1244Engine Normal Shutdown
1311Customer Input #1
1311Customer Inputs #1
1311, 1312, 1317, and 1318Customer Inputs #1-4
1312Customer Input #2
1312Customer Inputs #2
1317Customer Input #3
1317Customer Inputs #3
1318Customer Inputs #4
1318Service Engine Fault
1334Crit Scaler OR
1335Non-Crit Scaler OR
135Oil Pressure Sensor High
141Oil Pressure Sensor Low
1416Fail To Shut Down is displayed.The Fault Acknowledgement/Reset button will clear the fault message, but will remain in the Fault/History file with an asterisk sign (* equals active fault) as long as Battle Short mode is enabled.
1416Fail to Shut Down
1416Fail to Shutdown
1417Power Down Error
1417Power Down Failure
143Pre-Low Oil Pressure Sensor
1433Emergency Stop
1434Remote Emergency Stop
1435Low Coolant Temperature
1438Fail to Crank
144Coolant Temperature Sensor High
1442Weak Battery
1443Battery Failed
1444KW Overload
1445Short Circuit
1446High AC Voltage
1447Low AC Voltage
1448Under Frequency
1449Over Frequency
145Coolant Temperature Sensor Low
146Pre-High Cool Temp
1461Loss of Field
1466Modem Failure
1468Network Error
1469Speed/Hz Match
1471Over Current
1472Over Current
151High Coolant Temp
197Low Coolant Level
2323Network Faults 5 through 8
2323-2326Network Faults 5 through 8
2335Excitation Fault
2336Memory Error
234Overspeed
2341High Control Temperature
2342Too Long in Idle
235Low Coolant Level
2967Governor Fault

Fault codes and symptom→remedy steps extracted from this controller’s service/owner documentation; verify against the official manual before servicing. Aggregated from the service documentation of generator sets built on this controller.